For the Allen-Bradley 1760-IB12XOW4IF and Allen-Bradley 1760-LDF

Page 10

10

Pico and Pico GFX-70 Programmable Controllers

Select Communications

The Pico controller supports 2 connection methods. • Point-to-point serial interface with remote processor, 1760-RM-PICO • DeviceNet communications module The Pico GFX-70 supports 3 connection methods. • Pico-Link • Point-to-point serial connection between two processors (also point-to-point serial interface with remote processor, 1760-RM-GFX) • DeviceNet communications module The Pico-Link intraconnect can be used to connect up to 8 processors. Each processor is considered a Pico-Link station, and they can share all visualization and I/O data. The serial interface allows connection between two processors. One processor could be located for operator access to a keypad and display to share data with a second processor located behind a panel. Both connections support 3 modes of operation. • Run mode/Stop mode • Card mode (processor starts up using the program stored on the installed memory module) • Terminal mode This allows you to remotely control other devices. This is especially useful if the other device is located in an inaccessible place. Terminal mode can also be used to show the menus and displays of devices that do not have their own display or keypad. Terminal mode can be used both with the serial interface and in the Pico-Link network. The serial interface enables you to access a remote device. If you use the Pico-Link network, all other network stations can be addressed.

IMPORTANT

Publication 1760-SG001F-EN-P - May 2006

Terminal mode is a separate operating mode like RUN mode. It only functions when a program is not running. For this mode to be active, the GFX controller must be in STOP mode. All connected devices must also support Terminal mode.

Page 11

Pico and Pico GFX-70 Programmable Controllers

11

Pico-Link with GFX-70 Devices This topology allows: • processing of additional inputs and outputs. • faster and improved control using decentralized programs. • synchronize date and time. • read and write inputs and outputs. • send values to other stations. • receive values from other stations. • load a program to or from another station. • high level of real-time capability.

GFX-70

GFX-70

GFX-70

GFX-70

Pico-Link Operation and Serial Interface Connections This topology is a combination of Pico-Link operation and serial interface operation. The access rights of the individual Pico-Link devices and in the corresponding point-to-point serial interface.

GFX-70

GFX-70

The same conditions apply as with serial operation without the Pico-Link. The following data access operations are possible from the active station to the remote station. • Local inputs and outputs • Pico-Link diagnostics bits • Write/read accesses to markers

GFX-70

GFX-70

Publication 1760-SG001F-EN-P - May 2006

Page 12

12

Pico and Pico GFX-70 Programmable Controllers

Terminal Mode Using the Point-to-Point Serial Interface

TERMIN AL

Active Station

Remote Station

This interface connection allows the reading of input/output states as well as the reading and writing of marker ranges. This data can be used for setpoint entry or for display functions. The stations have different functions. The active station controls the point-to-point connection. The remote station responds to the requests of the active station.

Terminal Mode using the Pico-Link Topology

Terminal mode allows the active station to control any processor within the Pico-Link.

First Station on the Pico-Link

Terminating Resistor

Location 1 Station 1

R 1 - 12

GFX-70 S1-8

TERMIN

A

Location 2

GFX-70

GFX-70

Station 2

Location 3

GFX-70

Station 3

Last Station on the Pico-Link

Location 4 Station 4

Publication 1760-SG001F-EN-P - May 2006

GFX-70

Terminating Resistor

Page 13

Pico and Pico GFX-70 Programmable Controllers

13

DeviceNet Communications Module The Pico DeviceNet module, 1760-DNET, allows you to have a Pico controller operate as a slave device on the DeviceNet network. The DeviceNet module connects to the Pico controller like an expansion I/O module. It can be used with the Pico 18- and 20-point controllers and the Pico GFX-70 controller. 24V dc power must be provided to the device. DeviceNet Master

Pico Controllers as Slave Devices

The DeviceNet module is equipped with Network and Module status LEDs. It uses the following communication profile. • Predefined master/slave communication settings – The I/O polling connection is used for the transfer of 3 bytes of input data (R1 to R16) and 3 bytes of output data (S1 to S8) between the Pico controller and the DeviceNet master. – The I/O Change of State/Cyclic connection (acknowledged, unacknowledged) is used to transfer 2 bytes of diagnostic data from the Pico controller to the DeviceNet master. – The explicit connection set-up is used for read/write access to function relay parameters in the Pico controller. This type of connection set-up also supports the configuration, diagnostics and management services. • DeviceNet Communication adapter profile (device type 12) • Group 2 server • UCMM-capable device • Dynamic set-up of explicit and I/O connections are possible • Device Heartbeat Message • Device Shutdown Message • Offline communication settings

Publication 1760-SG001F-EN-P - May 2006