Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of IMC 123 Termination Panels (Cat. Nos. 1771-HT3, -HTR, -HTE, -HTT) Installation Data

Manual · Allen-Bradley

IMC 123 Termination Panels (Cat. Nos. 1771-HT3, -HTR, -HTE, -HTT) Installation Data

Manual7 pagesPDF 1.2 MB

Installation data for the Allen-Bradley 1771-HT3, -HTR, -HTE and -HTT termination panels of the IMC 123 motion controller.

Download the PDF1.2 MB

Covers · 1 model

The models it covers

Summary

What is in it

Allen-Bradley installation data for the four termination panels of the IMC 123 motion controller module: the 1771-HT3 E-stop and fast I/O panel, the 1771-HTE encoder feedback panel, the 1771-HTR resolver feedback panel and the 1771-HTT Temposonic feedback panel. It covers cable length limits, power available on the panels, panel layouts, system diagrams for encoder, resolver and Temposonic setups, and specifications for each panel. This scanned copy holds only some of the pages.

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

This is Allen-Bradley installation data for the IMC 123 Termination Panels, the 1771-HT3, 1771-HTR, 1771-HTE and 1771-HTT, which connect field devices to the IMC 123 motion controller module. The site files it under the 1771-HTE encoder feedback panel. The pages give the panel types, cable length limits, power, system diagrams for encoder, resolver and temposonic setups, and specifications.

Device
1771-HTE: encoder feedback termination panel for the IMC 123 motion controller module, for encoder feedback devices and servo drives p. 1
Mounting
1771-HTE: DIN-type rail, up to 10 cable feet (3 m) from the motion controller module p. 7
Dimensions
1771-HTE: 6.25 x 3 in. (15.8 cm x 7.5 cm) p. 7
Encoder cable length
Total from panel to feedback device: 40 cable feet for +5 VDC encoders without an external power supply, 90 cable feet with one p. 1
Encoder power
Isolated +5 VDC and +15VDC encoder power on board, chosen by wiring to the connector pin; +24VDC for fast I/O p. 2
Connections
1771-HTE: encoder channels A, B and Z (HI and LO), +5V and +15V encoder power, external power in and out, drive and feedback I/O p. 3
Connectors
Pluggable connectors; only a screwdriver and wirestripper needed p. 7
Rated cable run
1771-HTE: 85ft to an AB845L encoder with one axis, wired with 16GA twisted, shielded cable p. 7
Panel cable
1326-CEUxx Allen-Bradley cable, xx = length (15, 30, 50, 100 cable feet) p. 4
Controller
Encoder system: 1771-HS3A Motion Controller Module with a 1771-HTE panel per axis and a 1771-HT3 E-stop I/O panel p. 4, 5
Panel family
1771-HT3 E-stop and fast I/O, 1771-HTR resolver feedback, 1771-HTT temposonic feedback, 1771-HTE encoder feedback p. 1
E-Stop relay
1771-HT3: contacts rated 30VDC or 120/240VAC @ 3A continuous; 15ms operating time p. 7

What this manual walks you through

  • Choosing among the four IMC 123 termination panels p. 1
  • Power available on the termination panels p. 2
  • Encoder termination panel connections p. 3
  • Laying out an encoder system p. 4
  • Laying out resolver and temposonic systems p. 5, 6
  • Specifications of each termination panel p. 7

Good to know

  • The RS-232 port, RS-422 and user side power are not routed through the termination panels; all other user connections are. p. 2
  • Encoder cable runs are limited to 40 cable feet for +5 VDC encoders unless an external power supply is used. p. 1
  • For the resolver, E-stop and temposonic panels, longer runs than 90 cable feet need the factory's advice. p. 7

Questions this manual answers

What is the Allen-Bradley 1771-HTE?

The encoder feedback termination panel for the IMC 123 motion controller module, used for encoder feedback devices and servo drives. p. 1

How far can the 1771-HTE be from the motion controller?

Up to 10 cable feet (3 m), mounted on a DIN-type rail. p. 7

How long can the encoder cable be on a 1771-HTE?

40 cable feet for +5 VDC encoders without an external power supply, or 90 cable feet with one. p. 1

What size is the 1771-HTE panel?

6.25 x 3 in. (15.8 cm x 7.5 cm). p. 7

What encoder power does the 1771-HTE provide?

Isolated +5 VDC or +15VDC, chosen by wiring to the appropriate connector pin. p. 2

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 71-7

The file

Size and text

PublisherAllen-Bradley
Pages7
PDF1.2 MB
TextThe pages are scans; their text was read by OCR, which may hold reading errors.

The first pages · 3 of 7

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 7
Page 2
Page 2of 7
Page 3
Page 3of 7