Manual · Allen-Bradley
Fast Response DC Input Module (Cat. No. 1771-IT) Installation Data
Manual5 pagesPDF 62 KB
Installation data for the Allen-Bradley 1771-IT fast response 8-point 12-24 V DC input module for 1771 I/O chassis.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley installation data for the 1771-IT fast response DC input module, an 8-input 12-24 V DC module for the 1771 I/O chassis suited to photoelectric switches, incremental encoders and DC proximity switches. It covers pre-installation considerations, power requirements, keying the I/O chassis, installing the module, wiring the 1771-WA field wiring arm (including driving it from a 1771-OB output module), reading the status indicators, and specifications.
Its parts
- To The Installer
- Pre-installation Considerations
- Power Requirements
- Installing Your Module
- Interpreting the Status Indicators
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation data (publication 1771-2.22, June 1990) for the Allen-Bradley 1771-IT Fast Response DC Input Module. It covers power requirements, keying the I/O chassis, installing and wiring the module, reading the status indicators and the specifications.
- Device
- Fast response DC input module, 8 inputs, for the 1771 I/O chassis p. 1, 5
- Input voltage
- 12-24V DC nominal; logic 0 at 0V to 4V, logic 1 at 10V to 27V p. 5
- Input current
- 8mA at 12V DC, 24mA at 24V DC p. 5
- Backplane current
- 74mA from the chassis power supply p. 1, 5
- Wiring arm
- 10-terminal field wiring arm 1771-WA, shipped with the module p. 3
- Status indicators
- 8 red LEDs, one per input, lit when the input is on p. 4
- Typical devices
- Photoelectric switches, incremental encoders and dc proximity switches p. 1
- Isolation
- 1500V AC (RMS) opto-electrical p. 5
- Input impedance
- On: 1-2K ohms; off: 2-3K ohms p. 5
- Power dissipation
- 5.9 Watts max., 0.4 Watts min. (20.0 BTU/hr max.) p. 5
- Terminals
- Inputs on terminals 0 to 7, DC common on B, A not used p. 3
- Wire
- Stranded 14 or 16 gauge; 14 gage maximum, 3/64 inch insulation maximum p. 3, 5
- Keying
- Keying bands between 6 and 8 and between 32 and 34 p. 2
- Humidity
- 5 to 95% without condensation p. 5
What this manual walks you through
- Adding the module's backplane current to the chassis power budget p. 1
- Keying an I/O chassis slot for this module p. 2
- Installing the module in the chassis p. 2, 3
- Wiring 2-wire input devices to the field wiring arm p. 3
- Driving the inputs directly from a 1771-OB output module p. 3, 4
- Reading the status indicators p. 4
Good to know
- Because of its fast response the module may not suit hard contact devices; the manual recommends a 1771-IB for those. p. 1
- Remove power from the chassis backplane and wiring arm before removing or installing the module. p. 2
- When a 1771-OB drives the inputs, power both modules from the same dc source so the commons match. p. 3
- The left-most chassis connector is reserved for adapter or processor modules. p. 2
Questions this manual answers
Can the 1771-IT be used with pushbuttons or other hard contacts?
It may not be suitable, because its fast response could register contact sources as input data; the manual recommends the 1771-IB for hard contacts. p. 1
How much backplane current does the 1771-IT draw?
74mA from the 1771 I/O chassis power supply. p. 1
What wiring arm does the 1771-IT use?
The 10-terminal field wiring arm, cat. no. 1771-WA, which is shipped with the module. p. 3
What input voltage does the 1771-IT accept?
12-24V DC nominal; an input reads as on from 10V to 27V and off from 0V to 4V. p. 5
Where do I put the keying bands for a 1771-IT?
Between 6 and 8 and between 32 and 34 on the backplane connector. p. 2
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 1 part
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file