Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 22 of 26

Allen-Bradley I/O Modules Wiring Diagrams: 19 - 1794 FLEX I/O Modules, pages 167 to 174

Pages 167 to 174 of 200, from Allen-Bradley I/O Modules Wiring Diagrams

The original document is the PDF (4.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1771-IT

Page 167

Chapter

19

1794 FLEX I/O Modules

1794-ACN15, 1794-ACN15K

1794-ACNR15, 1794-ACNR15K

Use terminal to pass 24V common to next module in series (if necessary)

24V Common

Network Access Port (NAP)

ControlNet Connector

Use terminal to pass 24V dc power to next module in series (if necessary)

24V dc

Network address switch (Valid address range 1 to 99)

WARNING

If you connect or disconnect the ControlNet cable with power applied to the adapter or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

REDUND

24V Common

ANT MEDIA

15

ControlNet Connector

Redundant ControlNet Connector

Network Access Port (NAP)

Network address switch (Valid address range 1 to 99)

WARNING

24V dc

Use terminal to pass 24V common to next module in series (if necessary)

Use terminal to pass 24V dc power to next module in series (if necessary)

If you connect or disconnect the ControlNet cable with power applied to the adapter or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

1794-ADN, 1794-ADNK

ATTENTION

When connecting wiring, torque terminal screws D, E, F and G to 7 pound-inches (0.8Nm). Power wiring must be less than 3 meters (9.8 ft) in length.

B DeviceNet Connector (connections listed below) WARNING

Conn ect

To

BLK Wire

-V

BLU Wire

CAN Low

Bare Wire

Drain

WHT Wire

CAN High

RED Wire

+V

1

1

24V Common 1

CAN = Controller Area Network

COM

24V dc 24V

Use terminal to pass 24V common to next module in series (if necessary)

If you connect or disconnect the DeviceNet cable with power applied to the adapter or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Use terminal to pass 24V dc power to next module in series (if necessary)

Publication CIG-WD001B-EN-P - May 2005

Page 168

19-2

1794 FLEX I/O Modules

1794-AENT 24V Common

Use terminal to pass 24V common to next module in series (if necessary) WARNING

24V dc

Ethernet Connector

If you connect or disconnect the Ethernet cable with power applied to the adapter or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Use terminal to pass 24V dc power to next module in series (if necessary)

1794-APB 24V Common

Use terminal to pass 24V common to next module in series (if necessary)

When you connect or disconnect the PROFIBUS cable while power is on, an electrical arc can occur This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING

Profibus Connector 24V dc

Use terminal to pass 24V dc power to next module in series (if necessary)

Connect the PROFIBUS drop cable to the 9-pin D-shell connector according to the following pin assignments and graphic: Pin # 1 2 3 4 5 6 7 8 9

RS-485 Reference

B/B' C/C'

A/A'

Signal Shield RP RXD/TXD-P CTNR-P DGND VP RP RXD/TXD-N CTNR-N

Metal Shell

Publication CIG-WD001B-EN-P - May 2005

1 . . 5

Description Shield, RC to earth ground not used Receive/transmit data - P not used Data ground Voltage plus (+5V) not used Receive/transmit data - N not used Earth Ground

6 . . 9

DROP CABLE

Shield Pin #1 0.01µF 500V dc

1 MΩ

Signal +

Pin #3

Signal -

Pin #8

Earth Ground Pin #5

+5V Data Ground

Pin #6

RCV/ Xmit Data + RCV/ Xmit Data -

Page 169

1794 FLEX I/O Modules

19-3

1794-ASB, 1794-ASB2, 1794-ASBK, 1794-ASB2K

ATTENTION

24V Common Use terminal to pass 24V common to next module in series (if necessary) Connect:

To:

BLU Wire

1

Shield Wire

SH

CLR Wire

2

Power wiring must be less than 10 meters (33ft) in length.

COM

Use terminal to pass 24V dc power to next module in series (if necessary)

24V

WARNING

24V dc

1 SH 2

If this is the last adapter, you must terminate the remote I/O link here. Use a terminating resistor connected across terminals 1 and 2. Refer to your processor manual for information on the size of the resistor.

Remote I/O Cable Connector (connections listed on left)

If you connect or disconnect the network cable with power applied to the adapter or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

1794-IA16 1794-TBN, 1794-TBNK Even numbered terminals 0 through 14

16 16

0

2

34

4

1

6

3

34

8

5

10

7

12

9

33

14

11

13

15

51

51

Odd numbered terminals 1 through 15

Inp ut Terminals Chan ne l TB3, TB3K, TB3S TBN, TBNK 0 A-0 B-0 1 A-1 C-1 2 A-2 B-2 3 A-3 C-3 4 A-4 B-4 5 A-5 C-5 6 A-6 B-6 7 A-7 C-7

16, 0, 2, 4, 6, B 8. 10. 12. 14. 33 34, 1, 3, 5, 7, C 9, 11, 13, 15, 51

33

1794-TB3, 1794-TB3K, 1794-TBB3S 0 16

1 17

34

2 18

3 19

35

4 20

36

5

6

21

37

7

22

38

8

23

39

9

24

40

10

25

41

11

26

42

27

43

44

12

13

28 45

29

14 30

46

47

15 31

48

0-15 32

49

A

33

16-33

B

51

50

34-51

120V ac Supply 1 TB3, TB3K, TB3S

C-35 C-36 C-37 C-38 C-39 C-40 C-41 C-42

Input Termin als Channe l TB3, TB3K, TB3S TBN, TBNK 8 A-8 B-8 9 A-9 C-9 10 A-10 B-10 11 A-11 C-11 12 A-12 B-12 13 A-13 C-13 14 A-14 B-14 15 A-15 C-15

120V ac Supply 1 TB3, TB3K, TB3S

C-43 C-44 C-45 C-46 C-47 C-48 C-49 C-50

A = Input terminals on the 1794-TB3, TB3K and TB3S. B0 - B14 and C1 -C15 are input terminals on the 1794-TBN and TBNK. B = B-16 through B-33 are internally connected on the 1794-TB3, TB3K and -TB3S. B-16 and B-33 are internally connected on the 1794-TBN and TBNK. Connect 120V ac L2 to B-16.

C

C = C-34 through C-51 are internally connected on the 1794-TB3, TB3K and -TB3S. C-34 and C-51 are internally connected on the 1794-TBN and TBNK. Connect 120V ac L1 to C-34.

1 - Auxiliary terminal strips are required when using the 1794-TBN or TBNK.

1794-IA8, 1794-IA8K Inpu t Channel

1794-TBN, 1794-TBNK Even numbered terminals 0 through 14

16 16

0

2

34

4

1

6

3

5

8

10

7

9

12

11

33

14

13

15

51

Odd numbered terminals 1 through 15

34

0 1 2 3 4 5 6 7

16, 0, 2, 4, 6, B 8. 10. 12. 14. 33 34, 1, 3, 5, 7, C 9, 11, 13, 15, 51

33

51

1794-TB2, 1794-TB3, 1794-TB3K, 1794-TB3S 0 16

1 17

34

2

3

18 35

19 36

4 20

37

5 21

38

6 22

39

7 23

40

8 24

41

9 25

42

10 26

43

11 27

44

12 28

45

13 29

46

14 30

47

15 31

48

0-15 32

49

33 50

B

51

34-51 Terminals 35 through 50 are not used on 1794-TB2

A = input terminals B = common terminals C = power terminals (C-34 through C-51 for TB3, TB3K and TB3S; C-34 and C-51 for TB2)

A 16-33

1794-TB2, 1794-TB3, 1794-TB3K, 1794-TBB3S Inpu t Terminal s 120V ac Su pp ly A-0 A-11/C-35 A-2 A-31/C-37 A-4 A-51/C-39 A-6 A-71/C-41 A-8 A-91/C-43 A-10 A-111/C-45 A-12 A-131/C-47 A-14 A-151/C-49

C

1794-TBN, 1794-TBNK Inpu t Terminal s 120V ac Su pp ly B-0 C-12 B-2 C-32 B-4 C-52 B-6 C-72 B-8 C-92 B-10 C-112 B-12 C-132 B-14 C-152 B = even numbered terminals B-0 through B-14, ac common terminals B-16 and B-33 C = Power Terminals C-34 and C-51, and odd numbered terminals 1 through 15

Connect 120V ac L2 (common) to B-16 Connect 120V ac L1 to C-34 1 2

A-1, 3, 5, 7, 9, 11, 13 and 15 on 1794-TB3, -TB3K, -TB3S, and -TB2 are internally connected in the module to 120V ac L1. C-1, 3, 5, 7, 9, 11, 13 and 15 on 1794-TBN and TBNK are internally connected in the module to 120V ac L1.

Publication CIG-WD001B-EN-P - May 2005

Page 170

19-4

1794 FLEX I/O Modules

1794-IA8I 1794-TBN, 1794-TBNK

Inpu t Channel

Even numbered terminals 0 through 14

16 16

0

2

34

4

1

6

3

5

8

10

7

12

9

11

13

Inpu t Terminal s

33

14

51

Odd numbered terminals 1 through 15

34

16, 0, 2, 4, 6, B 8. 10. 12. 14. 33 34, 1, 3, 5, 7, C 9, 11, 13, 15, 51

33

15

51

0 1 2 3 4 5 6 7

1794-TB2, 1794-TB3, 1794-TB3K, 1794-TBB3S 0 16

1 17

34

2

3

18

4

19

35

36

5

20 37

21 38

6

7

22 39

8

23 40

24 41

9 25

42

10 26

43

11 27

44

12

13

28 45

14

29 46

15

30 47

1794-TB2, 1794-TB3, 1794-TB3K, 1794-TBB3S

31

0-15 32

48

49

33

A 16-33

A = even numbered input terminals 0 thru 14 for customer input connections; corresponding odd numbered 120V ac common L2 terminals 1 through 15 for customer connections from isolated power supply

B

51

50

34-51

A-0 A-2 A-4 A-6 A-8 A-10 A-12 A-14

120V ac Co mmon L2 A-1 A-3 A-5 A-7 A-9 A-11 A-13 A-15

C

Terminals 35 through 50 are not used on 1794-TB2

1794-TBN, 1794-TBNK

Inp ut Termina ls B-0 B-2 B-4 B-6 B-8 B-10 B-12 B-14

120V ac Commo n L2 C-1 C-3 C-5 C-7 C-9 C-11 C-13 C-15

B = even numbered input terminals 0 through 14 for customer input connections C = odd numbered terminals 1 through 15 for 120V ac L2 common connections from isolated power supply

Auxiliary terminal strips are required to connect 120V ac L1 of each isolated power supply to the input device that it is driving.

1794-IB10XOB6 1794-TB3, 1794-TB3K, 1794-TB3S Inputs 0

1

2

3

4

5

Outputs

6

7

8

9

1 0

1 1

1 2

1 3

1 4

15

A 17

16

1 8

1 9

2 0

2 1

2 2

2 3

2 4

2 5

2 6

2 7

2 8

2 9

3 0

3 1

3 2

33

B -V Common

Commons

34

35

3 6

3 7

3 8

3 9

4 0

4 1

4 2

-V Common 4 3

4 4

4 5

4 6

4 7

4 8

4 9

5 0

51

C Voltage In +V

Voltage Out +V

Voltage

Connect +V to C-34 Connect +V common to B-16 Use B-33 and C-51 for daisy chaining to next terminal base unit

(1794-TB3 shown)

2 and 3-Wire Input Wiring 0-15 A 16-33 B 35-51 C A = Sink Input B = Common C = +V dc

2-Wire Device (Sourcing Output)

3-Wire Device (Sourcing Output)

Sink Input Channel 0 1 2 3 4 5 6 7 8 9 Source Output Channel 0 1 2 3 4 5 +V dc Common

Input 1

Common

Sup ply

A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9

B-17 B-18 B-19 B-20 B-21 B-22 B-23 B-24 B-25 B-26

C-35 C-36 C-37 C-38 C-39 C-40 C-41 C-42 C-43 C-44

A-10 A-11 A-12 A-13 A-14 A-15

B-27 B-28 B-29 B-30 B-31 B-32 C-34 through C-51 B-16 through B-33

1. Two-wire input devices use input and supply terminals. Three-wire devices use input, common and supply terminals. +V common internally connected to terminal 16 through 33. +V dc power internally connected to terminal 34 through 51.

Publication CIG-WD001B-EN-P - May 2005

C-45 C-46 C-47 C-48 C-49 C-50

Page 171

1794 FLEX I/O Modules

19-5

1794-IB16, 1794-IB16K, 1794-IB8

0

1

2

3

4

5

6

7

8

9

1 0

1 1

1 2

1 3

1 4

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 +V dc Common

15

A Inputs 17

16

1 8

19

2 0

2 1

2 2

2 3

24

2 5

2 6

2 7

2 8

2 9

3 0

3 1

32

33

B Commons

Common (-V) 34

35

3 6

3 7

3 8

3 9

4 0

41

Common (-V)

4 2

4 3

4 4

4 5

4 6

4 7

4 8

4 9

5 0

51

C +V Voltage In

Input Terminal

Supply Terminal

Common 2 Terminal

A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15 C-34 through C-51

C-35 C-36 C-37 C-38 C-39 C-40 C-41 C-42 C-43 C-44 C-45 C-46 C-47 C-48 C-49 C-50

B-17 B-18 B-19 B-20 B-21 B-22 B-23 B-24 B-25 B-26 B-27 B-28 B-29 B-30 B-31 B-32

Input 1 Channel

1794-TB3, 1794-TB3K, 1794-TB3S

+V Voltage Ou t

Voltage

(1794-TB3 shown)

Connect +V to C-34 Connect +V common to B-16 Use B-33 and C-51 for daisy chaining to next terminal base unit

2 and 3-Wire Input Wiring 0-15 A 16-33 B 35-51 C

B-16 through B-33

1. 1794-IB8 - Inputs 0 through 7; 1794-IB16 - Inputs 0 through 15 A = Sink Input B = Common C = +V dc

2-Wire Device (Sourcing Output)

2. Two-wire input devices use input and supply terminals. Three-wire devices use input, common and supply terminals.

3-Wire Device (Sourcing Output)

+V common internally connected to terminal 16 through 33. +V dc power internally connected to terminal 34 through 51.

1794-IB16D

1794-TB32, -TB32S 0

1

2

3

4

5

6

7

8

9

1 0

1 1

1 2

1 3

1 4

15

A Input Terminals 0-15 17

16

1 8

19

2 0

2 1

2 2

2 3

24

2 5

2 6

2 7

2 8

2 9

3 0

3 1

32

33

B NC

NC

Sensor Power Terminals 0-15 34

35

3 6

3 7

NC

+V1

COM1 +V1

3 8

3 9

4 0

41

4 2

4 3

4 4

4 5

4 6

4 7

4 8

4 9

5 0

51

C COM1 +V1

COM1 +V1

COM1 +V2

COM2 +V2

COM2 +V2

COM2 +V2

COM2 NC

(1794-TB32 shown) + V2 = Terminals 43, 45, 47 and 49 Voltage applied to Inputs 0-15 and Sensor power 0-15 C OM1, COM2 = Terminals 36, 38, 40, 42, 44, 46, 48 and 50 Common for inputs 0 through 15 and sensor power 0 through 15 N C = No connections (terminals 16, 33, 34 and 51) + V1 = Terminals 35, 37, 39 and 41 (not used)

Sensor Power Te rminal

Input Channel

Input Terminal

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 +V2 dc power COM dc

A-0 B-17 -V common +V2 connected connected to to terminals 43, A-1 B-18 terminals 36, 38, 45, 47 and 49 A-2 B-19 40, 42, 44, 46, 48 and 50 A-3 B-20 A-4 B-21 A-5 B-22 A-6 B-23 A-7 B-24 A-8 B-25 A-9 B-26 A-10 B-27 A-11 B-28 A-12 B-29 A-13 B-30 A-14 B-31 A-15 B-32 Power terminals 43, 45, 47 and 49 (power terminals are internally connected together in the module) Common terminals 36, 38, 40, 42, 44, 46, 48 and 50 (common terminals are internally connected together in the module)

Common

Supp ly

Publication CIG-WD001B-EN-P - May 2005

Page 172

19-6

1794 FLEX I/O Modules

1794-IB16XOB16P 1794-TB32, -TB32S 0

1

2

3

4

5

6

7

8

9

1 0

1 1

1 2

1 3

1 4

15

A IN0

IN1

IN2

IN3

IN4

IN5

IN6

IN7

IN8

IN9

IN10

IN11

IN12

IN13

IN14

IN15

2 7

2 8

2 9

3 0

3 1

32

Input Channel

Input Terminal

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15

Inputs 17

1 8

19

2 0

2 1

2 2

2 3

OUT0

OUT1

OUT2

OUT3

OUT4

OUT5

OUT6

24

2 5

2 6

OUT8

OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15

33

B NC

OUT7

NC

Outputs

C 35 3 6 3 7 3 8 +V1 COM1 +V1 COM1

34 NC

3 9 +V1

4 0 41 COM1 +V1

4 2 43 44 45 COM1 +V2 COM2 +V2

46 47 COM2 +V2

+V1 = Terminals 35, 37, 39 and 41 +V2 = Terminals 43, 45, 47 and 49 COM1 = Terminals 36, 38, 40 and 42 COM2 = Terminals 44, 46, 48 and 50 NC = No connections (terminals 16, 33, 34 and 51)

48 49 50 COM2 +V2 COM2

51 NC

(1794-TB32 shown)

+V1 dc power Com1 dc Return

2 and 3-Wire Input Wiring 0-15 A 16-33 B 35-51 C

Common V1 common connected to terminals 36, 38, 40 and 42

Supply 1

Output Channel 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

+V1 connected to terminals 35, 37, 39 and 41

Power terminals 35, 37, 39 and 41 Common terminals 36, 38, 40 and 42

+V2 dc power Com2 dc Return

Output Terminal B-17 B-18 B-19 B-20 B-21 B-22 B-23 B-24 B-25 B-26 B-27 B-28 B-29 B-30 B-31 B-32

Common V2 Return connected to terminals 44, 46, 48 and 50

Power terminals 43, 45, 47 and 49 Common terminals 44, 46, 48 and 50

1. 2-wire input devices use input and supply terminals; 3-wire devices use input, common and supply terminals.

A = Sink Input B = Common C = +V dc

2-Wire Device (Sourcing Output)

3-Wire Device (Sourcing Output)

1794-IB32

1794-TB32 and 1794-TB32S 0

1

2

3

4

5

6

7

8

9

1 0

1 1

1 2

1 3

1 4

15

A Inputs 17

16

1 8

19

2 0

2 1

2 2

2 3

24

2 5

2 6

2 7

2 8

2 9

3 0

3 1

32

33

B NC

NC

Inputs 34

35

3 6

NC

+V1

COM1 +V1

3 7

3 8

3 9

4 0

41

4 2

4 3

4 4

4 5

4 6

4 7

4 8

4 9

5 0

51

C COM1 +V1

COM1 +V1

COM1 +V2

COM2 +V2

+V1 = Terminals 35, 37, 39 and 41 +V2 = Terminals 43, 45, 47 and 49 COM1 = Terminals 36, 38, 40 and 42 COM2 = Terminals 44, 46, 48 and 50 NC = No connections (terminals 16, 33, 34 and 51)

COM2 +V2

COM2 +V2

COM2 NC

(1794-TB32 shown)

Input Channel

Input Terminal

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 +V1 dc power Com1 dc Return

A-0 +V1 connected to V1 common connected to terminals 35, 37, A-1 terminals 36, 38, 39 and 41 A-2 40 and 42 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15 Power terminals 35, 37, 39 and 41 Common terminals 36, 38, 40 and 42

Common

Sup ply 1

Input Channel 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 +V2 dc power Com2 dc Return

Input Terminal

1. 2-wire input devices use input and supply terminals; 3-wire devices use input, common and supply terminals.

Publication CIG-WD001B-EN-P - May 2005

Common

Sup ply 1

V2 common B-17 +V2 connected to connected to terminals 43, 45, B-18 terminals 44, 46, 47 and 49 B-19 48 and 50 B-20 B-21 B-22 B-23 B-24 B-25 B-26 B-27 B-28 B-29 B-30 B-31 B-32 Power terminals 43, 45, 47 and 49 Common terminals 44, 46, 48 and 50

Page 173

1794 FLEX I/O Modules

19-7

1794-IC16

1794-TB3, 1794-TB3K, 1794-TB3S 0

1

0

2

1

16

17

18

34

3

2

36

5

4

19

35

4

3 20

21

37

6

5

38

6 22

7

8

9

10

11 12 13 14 15

7

8

9

10

11

23

39

24

40

41

25

26

42

43

27 44

12 28

45

13 29

14 30

46

47

15 31

48

0-15 32

49

33

A 16-33

B

51

50

34-51

C

Connect +V to C-34 Connect +V common to B-16 Use B-33 and C-51 for daisy-chaining to the next terminal base unit.

Input Channel

Input Terminal

0 1 2 3 4 5 6 7 Common

A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7

Supply Terminal

C-35 C-36 C-37 C-38 C-39 C-40 C-41 C-42 B-16 through B-33

1794-TB3, 1794-TB3K, 1794-TB3S Input Input Channel Terminal

Common 1 Terminal B-17 B-18 B-19 B-20 B-21 B-22 B-23 B-24

8 9 10 11 12 13 14 15 +V dc

A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15

Supply Terminal

Common 1 Terminal

C-43 C-44 C-45 C-46 C-47 C-48 C-49 C-50 C-34 through C-51

B-25 B-26 B-27 B-28 B-29 B-30 B-31 B-32

1. 2-wire devices use input and supply terminals; 3-wire input devices use input, common and supply terminals.

1794-ID2 Terminal Base Units 1794-TB2, -TB3, -TB3K and -TB3S

1794-TB2, 1794-TB3, 1794-TB3K, 1794-TB3S 0 1 0 16

1 17

34

35

3

2 2

18

3 19

36

37

7 8 9

4 5 6 4

20

5 21

38

6

7

22 39

23 40

8 24

10 11 12 13 14 15

9

10

25

41

42

26 43

11 27

44

12

13

28 45

29 46

14 30

47

48

Input

0-15

15 31

32 49

50

A 16-33

33 51

34-51

B

1794-TBN, 1794-TBNF, 1794-TBNK 16 0

34

34

1

Even Numbered Terminals 0 through 14

33

2

33

4

3

6

5

8

7

10

9

12

11

14

13

15

Odd numbered terminals 1 through 15

16, 0, 2, 4, 6, B 8, 10, 12, 14, 33 51 34, 1, 3, 5, 7, C 9, 11, 13, 15, 51 51

Connect +V to C-34 Connect +V common to B-16 Use B-33 and C-51 for daisy-chaining to the next terminal base unit.

12/24V dc

Terminal Base Units 1794-TB2, -TB3, -TB3K and -TB3S

Input

Input

Pulse Counter Channel 0 C

Terminals 35 through 50 are not used on 1794-TB2

16

OV dc (common)

Terminal Base Units 1 1794-TBN, -TBNK and -TBNF

OV dc (common)

12/24V dc

Terminal Base Units 1 1794-TBN, -TBNK and -TBNF Input

Pulse Counter Channel 1

A+

A-0

B-17

C-35

B-0

A+

A-8

B-25

C-43

A-

A-1

B-18

C-36

C-1

A-

A-9

B-26

C-44

C-9

B+

A-2

B-19

C-37

B-2

B+

A-10

B-27

C-45

B-10 C-11

B-8

B-

A-3

B-20

C-38

C-3

B-

A-11

B-28

C-46

Z+

A-4

B-21

C-39

B-4

Z+

A-12

B-29

C-47

B-12

Z-

A-5

B-22

C-40

C-5

Z-

A-13

B-30

C-48

C-13

G+

A-6

B-23

C-41

B-6

G+

A-14

B-31

C-49

B-14

G-

A-7

B-24

C-42

C-7

G-

A-15

B-32

C-50

C-15

Common

Terminals 16 and 33 (1794-TB2, -TBN, -TBNK and -TBNF) Terminals 16 through 33 (1794-TB3, -TB3K, -TB3S)

+V dc

Terminals 34 and 51 (1794-TB2, -TBN, -TBNK and -TBNF) Terminals 34 through 51 (1794-TB3, -TB3K, -TB3S)

1. Auxiliary terminal blocks are required when using these terminal base units.

Publication CIG-WD001B-EN-P - May 2005

Page 174

19-8

1794 FLEX I/O Modules

1794-IE12 1794-TB3G, -TB3GK, -TB3GS 0

1

2

3

4

5

6

7

8

9

10

Channel

11

12

13

14

15

Input 0

A I0 V0

I1

17

16

18

V1

I2 V2

I3 V3

20

21

22

23

I8 V8

I9

V9 C2 C3 C4 C5 I10 V10 I11 V11 C6 C7 Chassi s Ground

19

I4

24

V4 I5 25

26

V5 27

I6

28

V6 29

I7 V7

30

31

Input 1

32

33

B Chassi s C0 C1 Ground 35

34

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

Input 2 Input 3

51

C

Input 4

+V COM NC C8 Ch. C9 C10 Ch. C11 NC +V COM 24C dc Gnd Chassis Grounds for Shields Gnd 24C dc Supply In Supply Out I = Current V = Voltage (1794-TB3G shown) C0 thru C11 = Returns for I or V connections 0 through 11 +24V dc = Terminals C34 and C50 COM = C35 and C51 Chassis Ground = Terminals B16, B33, C38, C40 thorugh 45, and C47 NC = No connection For daisy-chaining: Supply in - C34 (+) and C35 (-) Supply out - C50 (+) and C51 (-)

Input 5 Input 6 Input 7 Input 8 Input 9

To reduce susceptibility to noise, power analog modules and digital modules from separate power supplies. Do not exceed a length of 33 ft (10m) for dc power cabling.

ATTENTION

!

Input 10 Input 11

Do not daisy chain power or ground from this terminal base unit to any ac or dc digital module terminal base units.

-V dc Common +V dc Power Chassis Ground (Shield)

Do not exceed a length of 33 ft (10m) for signal cabling.

Signal Ty pe

Label Ma rk in g

1794-TB3G, -TB3GK, -TB3GS Input Commo n Te rm inal

Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage

I0 V0 I1 V1 I2 V2 I3 V3 I4 V4 I5 V5 I6 V6 I7 V7 I8 V8 I9 V9 I10 V10 I11 V11

A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15 B-19 B-20 B.21 B-22 B-27 B-28 B-29 B-30

B-17 B-18 B-23 B-24 B-25 B-26 B-31 B-32 C-37 C-39 C-46 C-48

Terminals 35 and 51 are internally connected in the terminal base unit. Terminals 34 and 50 are internally connected in the terminal base unit. Terminals 16, 33, 38, 40 through 45, and 47 are internally connected to chassis ground.

1794-IE4XOE2 1794-TB2, 1794-TB3, 1794-TB3K, 1794-TB3S, 1794-TB3T and 1794-TB3TS

0

1

0 16

1 17

34

2

3

2 18

35

4

3 19

36

4 20

37

5 5 21

38

6 6

22 39

7 7

23 40

8 8 24

41

9 9 25

42

10

11 12 13 14 15

10

11

26 43

27 44

12 28

45

13 29

46

14 30

47

Channel

15 31

48

0-15 32

49

33 50

A 16-33 34-51

Terminals 35 through 50 are not used on 1794-TB2

ATTENTION

!

Only connect either a voltage input or a current input per channel, not both. To reduce susceptibility to noise, power analog and digital modules from separate power supplies. Do not exceed a length of 3M (9.8 ft) for DC power cabling.

Connect +V to C-34 Connect +V common to B-16 Use B-33 and C-51 for daisy-chaining to the next terminal base unit.

In 0

B

51

C In 1

In 2

In 3

Sign al Type

TB2, TB3, TB3K, TB3S, TB3T, TB3TS Inpu t Termi nal s

TB2, TB3, TB3K, TB3S

TB 3T, TB 3TS

Co mmon T ermi nal s

Shi el d

Current

A-0

B-17

B-17

C-39

Voltage

A-1

B-18

B-17

C-39

Chan nel

Out 0

TB 3T, TB 3TS Sh ie ld

Current Signal

A-8

C-43

Current Common

A-91

C-43

Current

A-2

B-19

B-19

C-40

Voltage Signal

A-10

C-44

Voltage

A-3

B-20

B-19

C-40

Voltage Common

A-111

C-44

Current

A-4

B-21

B-21

C-41

Voltage

A-5

B-22

B-21

C-41

Out 1

Current Signal

A-12

C-45

Current Common

A-131

C-45

Current

A-6

B-23

B-23

C-42

Voltage Signal

A-14

C-46

Voltage

A-7

B-24

B-23

C-42

Voltage Common

A-151

C-46

Common for TB2, TB3, TB3K, TB3S: B-16 through B-33 Common for TB3T and TB3TS: B16, 17, 19, 21, 23, 25, 27, 29, 31 and 33.

+V dc Power for 1794-TB2: C-34 and C-51; +V dc Power for 1794-TB3, TB3K and TB3S: C-34 through C-51 +V dc Power for 1794-TB3T and -TB3TS: C-34, 35, 50 and 51

Connect any signal wiring shields to functional ground as near as possible to the module when using the 1794-TB2, -TB3, -TB3K, and -TB3S. With the 1794-TB3T and -TB3TS, use terminals C-39 through C-46. 1. A-9, A-11, A-13 and A-15 are internally connected in the module to +V dc common.

Publication CIG-WD001B-EN-P - May 2005

Sig nal Type

TB2, TB3, TB3K, TB3S, TB3T, TB3TS Output Termi nal s