Page 1 of Auxiliary Power Supply (Cat. No. 1771-P2) Installation Data

Manual · Allen-Bradley

Auxiliary Power Supply (Cat. No. 1771-P2) Installation Data

Manual8 pagesPDF 154 KB

Installation data for the Allen-Bradley 1771-P2 auxiliary power supply for a 1771 I/O chassis: mounting, AC wiring and specs.

Download the PDF154 KB

Covers · 1 model

The models it covers

Summary

What is in it

Allen-Bradley installation data for the 1771-P2 Auxiliary Power Supply, which powers one bulletin 1771 I/O chassis. It covers preparing for installation, mounting the supply on the chassis side or separately, connecting backplane power with the 1771-CE or 1771-CD cable, setting the 120 or 220/240 V ac jumpers and fuses, connecting the AC line and ground, the output and its protection, LED troubleshooting and the specifications.

Its parts

  1. To the Installer
  2. Prepare for Installation
  3. Install the Power Supply and Connect Backplane Power
  4. Connect AC Power
  5. Power Supply Output
  6. Troubleshooting
  7. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley installation data for the 1771-P2 Auxiliary Power Supply, which powers one bulletin 1771 I/O chassis. It shows how to mount the supply, connect backplane and ac power, set the input voltage and fuse, read the D.C. ON light, and gives the specifications.

What it is
Auxiliary power supply for one bulletin 1771 I/O chassis with an adapter, Mini-PLC-2 or Mini-PLC-2/15 processor p. 1
Output
5.1V dc, 6.5A maximum p. 6
Input voltage
120V ac (98 to 132V ac) or 220/240V ac (196 to 250V ac), set by jumpers p. 4, 5
Input current
120V ac at .75A; 220/240V ac at .38A p. 7
Input power
65W real, 90VA apparent at full load p. 7
Frequency
60/50Hz p. 7
Fuses
1A slow-blow for 120V; 0.5A slow-blow for 220/240V; fuse kit 1771-FP p. 4
Power cables
1771-CE when mounted on the left side of the chassis; 1771-CD within 5 cable-feet p. 1
Battery backup
None; the 1771-P1 system power supply gives battery backup p. 1
Processor disable delay
13.5ms ± 2.5ms after input power loss p. 7
Weight
5.89 kg (13 lbs) p. 7
External transformer
160VA minimum at full load p. 5
Temperature
Operating 0 to 60°C (32 to 140°F); storage -40 to 85°C (-40 to 185°F) p. 7
Protection
Shuts down on output overvoltage, undervoltage or overcurrent p. 6

What this manual walks you through

  • Mounting the supply on the chassis side or separately p. 1, 2
  • Connecting backplane power with the 9-pin cable p. 3
  • Jumpering for 120V ac or 220/240V ac p. 4
  • Choosing and changing the fuse p. 4
  • Connecting the ac line and ground p. 5
  • Troubleshooting with the D.C. ON light p. 6
  • Sizing cooling, power cost and transformer p. 7

Good to know

  • Do not mount the supply below the I/O chassis; keep at least six inches vertical distance. p. 1, 2
  • Use the supplied flat washers, or the screws intrude into the chassis and block module insertion. p. 2
  • Wrong voltage jumpering may cause improper operation or damage the supply. p. 4
  • Ships set for 120V ac with a 1A fuse installed. p. 4
  • After a shutdown, cycle ac power to restart the supply. p. 6

Questions this manual answers

What does it mean if the D.C. ON light on a 1771-P2 is off?

The input voltage may be out of range, the fuse may be blown, or there may be an overcurrent. p. 6

How much current does the 1771-P2 supply?

It provides 5.1V dc at up to 6.5A to the chassis backplane. p. 6

Does the 1771-P2 provide battery backup?

No; for battery backup the document points to the 1771-P1 system power supply. p. 1

What fuse does the 1771-P2 use on 220/240V?

A 0.5A 3AG slow-blow fuse, which comes with the supply. p. 4

Which cable connects a 1771-P2 mounted on the chassis?

The 1771-CE cable when mounted on the left side of the chassis; the 1771-CD when mounted separately within 5 cable-feet. p. 1

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-2.7, Auxiliary Power Supply Installation Data1
  2. To the Installer1
  3. Prepare for Installation1
  4. Install the Power Supply snf Connect Backplane Power1
    1. Mount the Power Supply2
    2. Connect Backplane Power3
  5. Connect AC Power4
    1. Check the Input Voltage4
    2. Check the Fuse Protection4
    3. Connect AC Power Line5
  6. Power Supply Output6
  7. Troubleshooting6
  8. Specifications7
  9. Back Cover8

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8

The file

Revision and size

RevisionPublication 1771-2.7, December 1992
PublisherAllen-Bradley
Pages8
PDF154 KB
TextText from the PDF itself.

The first pages · 3 of 8

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 8
Page 2
Page 2of 8
Page 3
Page 3of 8