Manual · Allen-Bradley
Auxiliary Power Supply (Cat. No. 1771-P2) Installation Data
Manual8 pagesPDF 154 KB
Installation data for the Allen-Bradley 1771-P2 auxiliary power supply for a 1771 I/O chassis: mounting, AC wiring and specs.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley installation data for the 1771-P2 Auxiliary Power Supply, which powers one bulletin 1771 I/O chassis. It covers preparing for installation, mounting the supply on the chassis side or separately, connecting backplane power with the 1771-CE or 1771-CD cable, setting the 120 or 220/240 V ac jumpers and fuses, connecting the AC line and ground, the output and its protection, LED troubleshooting and the specifications.
Its parts
- To the Installer
- Prepare for Installation
- Install the Power Supply and Connect Backplane Power
- Connect AC Power
- Power Supply Output
- Troubleshooting
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley installation data for the 1771-P2 Auxiliary Power Supply, which powers one bulletin 1771 I/O chassis. It shows how to mount the supply, connect backplane and ac power, set the input voltage and fuse, read the D.C. ON light, and gives the specifications.
- What it is
- Auxiliary power supply for one bulletin 1771 I/O chassis with an adapter, Mini-PLC-2 or Mini-PLC-2/15 processor p. 1
- Output
- 5.1V dc, 6.5A maximum p. 6
- Input voltage
- 120V ac (98 to 132V ac) or 220/240V ac (196 to 250V ac), set by jumpers p. 4, 5
- Input current
- 120V ac at .75A; 220/240V ac at .38A p. 7
- Input power
- 65W real, 90VA apparent at full load p. 7
- Frequency
- 60/50Hz p. 7
- Fuses
- 1A slow-blow for 120V; 0.5A slow-blow for 220/240V; fuse kit 1771-FP p. 4
- Power cables
- 1771-CE when mounted on the left side of the chassis; 1771-CD within 5 cable-feet p. 1
- Battery backup
- None; the 1771-P1 system power supply gives battery backup p. 1
- Processor disable delay
- 13.5ms ± 2.5ms after input power loss p. 7
- Weight
- 5.89 kg (13 lbs) p. 7
- External transformer
- 160VA minimum at full load p. 5
- Temperature
- Operating 0 to 60°C (32 to 140°F); storage -40 to 85°C (-40 to 185°F) p. 7
- Protection
- Shuts down on output overvoltage, undervoltage or overcurrent p. 6
What this manual walks you through
- Mounting the supply on the chassis side or separately p. 1, 2
- Connecting backplane power with the 9-pin cable p. 3
- Jumpering for 120V ac or 220/240V ac p. 4
- Choosing and changing the fuse p. 4
- Connecting the ac line and ground p. 5
- Troubleshooting with the D.C. ON light p. 6
- Sizing cooling, power cost and transformer p. 7
Good to know
- Do not mount the supply below the I/O chassis; keep at least six inches vertical distance. p. 1, 2
- Use the supplied flat washers, or the screws intrude into the chassis and block module insertion. p. 2
- Wrong voltage jumpering may cause improper operation or damage the supply. p. 4
- Ships set for 120V ac with a 1A fuse installed. p. 4
- After a shutdown, cycle ac power to restart the supply. p. 6
Questions this manual answers
What does it mean if the D.C. ON light on a 1771-P2 is off?
The input voltage may be out of range, the fuse may be blown, or there may be an overcurrent. p. 6
How much current does the 1771-P2 supply?
It provides 5.1V dc at up to 6.5A to the chassis backplane. p. 6
Does the 1771-P2 provide battery backup?
No; for battery backup the document points to the 1771-P1 system power supply. p. 1
What fuse does the 1771-P2 use on 220/240V?
A 0.5A 3AG slow-blow fuse, which comes with the supply. p. 4
Which cable connects a 1771-P2 mounted on the chassis?
The 1771-CE cable when mounted on the left side of the chassis; the 1771-CD when mounted separately within 5 cable-feet. p. 1
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 1 part
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file