Manual · Allen-Bradley
Allen-Bradley 1771-SIM Manual
Manual4 pagesPDF 268 KB
All 4 pages are below, each with its text.
Covers · 1 model
The models it covers
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley technical data (publication 1771-TD106B-EN-P, June 2001) for the 1771-SIM input/output simulation module, a single-slot module for any 1771 Universal I/O chassis. Its eight switches simulate inputs and its eight LEDs show which outputs are on, for testing programs without temporary field wiring. The sheet covers uses, addressing, backplane power and specifications.
- What it is
- Single-slot input simulation and output indicating module for any 1771 Universal I/O chassis p. 1
- I/O
- 8 input simulating switches and 8 output indicator LEDs p. 2, 3
- Backplane power
- +5V DC, 300mA maximum, from the I/O chassis power supply p. 3
- Connections
- All through the backplane connector; no user terminals p. 2
- Slot locations
- Lower or upper byte (slot 0 or 1) p. 3
- Addressing
- Switches and indicators address as a low byte slot device (00-07) or high byte slot device (10-17) p. 2
- Keying
- Between 14 and 16, and between 24 and 26 p. 3
- Publication
- 1771-TD106B-EN-P, June 2001; supersedes 1771-2.106 (January 1987) p. 4
What this manual walks you through
- Testing program response to inputs and outputs without field devices p. 2
- Addressing the module in high or low byte slots p. 2
- Adding the module to the chassis power budget p. 3
Good to know
- The module must be mounted in an enclosure whose interior opens only with a tool. p. 2
- Rated for Pollution Degree 2, overvoltage category II, at altitudes up to 2000 meters without derating. p. 2
- Check for existing keys before installing the module. p. 3
- Do not overload the chassis power supply or backplane. p. 3
Questions this manual answers
What is the Allen-Bradley 1771-SIM?
A single-slot module for 1771 Universal I/O chassis with eight switches to simulate inputs and eight LEDs to show active outputs. p. 1, 2
How much backplane current does the 1771-SIM draw?
Up to 300mA at +5V DC from the I/O chassis power supply. p. 3
Does the 1771-SIM need any wiring?
No, all connections and power come through its backplane connector, and it has no user terminals. p. 2
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
Technical Data
Input/Output Simulation Module 1771-SIM
Description
The 1771-SIM Module is an input simulation and output indicating module. It can be inserted into any 1771 Universal I/O chassis. The switches on this single-slot module simulate open/close devices; the LEDs identify which outputs are active.
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
2
Input/Output Simulation Module
Uses
Typical uses include:
- Testing programs for proper response to a specified input
- Testing programs for sending “turn on/turn off” signals to user-defined outputs
- Replacing manual input devises such as temporary switch-and-wire setups; has eight switches, one for each input
- Replacing temporary output test lamps; has eight built-in LEDs, one for each output
Status Indicators
Input Simulation Switches
ATTENTION
! IMPORTANT
This product must be mounted within a suitable system enclosure to prevent personal injury resulting from accessibility to live parts. The interior of this enclosure must be accessible only by the use of a tool.
This industrial control equipment is intended to operate in a Pollution Degree 2 environment, in overvoltage category II applications (as defined in IEC publication 664A), at altitudes up to 2000 meters, without derating.
Connections
All connections and power to the 1771-SIM module are through its backplane connector; therefore, no user-accessible terminals are provided.
Addressing
The module can be inserted into and addressed(1) in either high byte slots or low byte slots.
- INPUT: Each switch can be addressed(1) as either a low byte slot device (00-078) or a high byte slot device (10-178).
- OUTPUT: Each output indicator can be addressed(1) at either a low byte slot address (00-078) or at a high byte slot address (10-178).
(1)
Publication 1771-TD106B-EN-P - June 2001
When installed in the appropriate slot.
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
Input/Output Simulation Module
3
Backplane Power
The logic circuitry and the LEDs of the Simulation Module are powered by the I/O chassis power supply. The module requires +5V DC at a maximum of 300mA. Add the current requirements of the module into the total of the other modules in the I/O chassis to check current limits. Do not overload the supply or the I/O chassis backplane.
Specifications Specifications - 1771-SIM Module I/O per Module
8 input simulating switches 8 output indicators
Backplane Current300mA @ +5V DCSlot Locations
lower or upper byte (Slot 0 or 1)
Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Keying
ATTENTION
! IMPORTANT
0 to 60°C (32 to 140°F) -40 to 85°C (-40 to 185°F) 5 to 95% (non-condensing) between 14 and 16, 24 and 26 NOTE: Check for existing keys before installing the 1771-SIM module.
This product must be mounted within a suitable system enclosure to prevent personal injury resulting from accessibility to live parts. The interior of this enclosure must be accessible only by the use of a tool.
This industrial control equipment is intended to operate in a Pollution Degree 2 environment, in overvoltage category II applications (as defined in IEC publication 664A), at altitudes up to 2000 meters, without derating.
Publication 1771-TD106B-EN-P - June 2001
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
Publication 1771-TD106B-EN-P - June 2001 4 Supersedes Publication 1771-2.106 - January 1987
PN 957564-45 © 2001 Rockwell International Corporation. Printed in the U.S.A.