Spec sheet · Allen-Bradley
Allen-Bradley 1771-SN Spec Sheet
Spec sheet4 pagesPDF 66 KB
All 4 pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Product data (publication 1771-2.91) for the Allen-Bradley 1771-SN Sub I/O Scanner Module, Series A, Revision D. It explains how the scanner adds remote discrete I/O to a PLC chassis through block transfers, which processors, adapters and I/O work with it, the response time to expect, and the specifications and connection parts.
- What it is
- Sub I/O scanner that expands a PLC's I/O by up to 896 digital remote I/O p. 1
- Remote chassis
- Up to 16 remote chassis or adapters, using up to seven rack numbers in quarter-rack increments p. 1
- Processors
- Any processor with block-transfer capability; the overview shows PLC-5, PLC-2, PLC-5/250 and PLC-3 p. 2, 3
- Remote I/O
- Discrete I/O modules only, through adapters with discrete transfer capability; no complementary I/O p. 3
- Link speed and length
- 10,000 cable-feet at 57.6k bits/s; 5,000 cable-feet at 115.2k bits/s p. 4
- Interconnect cable
- 1770-CD or equivalent twinaxial cable p. 2, 4
- Chassis
- 1771-A1B thru -A4B or later, and 1771-AM1 and -AM2 I/O chassis p. 4
- Backplane current
- 1.2A; 7W maximum power dissipation p. 4
- Keying
- Between 2 and 4; between 24 and 26 p. 4
- Block size
- Read and write blocks each 8 words of overhead plus 8 words per remote I/O rack p. 3
- Daisy-chain parts
- Phoenix connector (6-pin), part number 940611-01; 1771-ASB termination resistor 1770-XT p. 4
- Dropline parts
- 1770-XG T-connector (966308-01); 1770-SC station connector (966080-01); 1770-XF terminator set (966307-01) p. 4
- Response time
- Example: 203ms worst case with 2 remote chassis, 40ms local scan and 24ms input delay p. 2
- Suited to
- Thumbwheel switch inputs, pilot light outputs and other operator-interface devices p. 2
What this sheet walks you through
- How the scanner fits into a PLC system with remote I/O chassis p. 2
- Estimating remote I/O response time p. 2
- Compatible processors, adapters and remote I/O p. 3
- Data table use and block-transfer operation p. 3
- Specifications and connection part numbers p. 4
Good to know
- Meant for digital I/O that does not need fast response. p. 2
- Only discrete I/O modules can be used remotely, since the link carries a single word per I/O group. p. 3
- The module does not support complementary I/O. p. 3
Questions this sheet answers
How much I/O can a 1771-SN add?
Up to 896 digital remote I/O in up to 16 remote chassis, using as many as seven rack numbers. p. 1
Which processors work with the 1771-SN scanner?
Any processor with block-transfer capability. p. 3
Can I put analog modules in a 1771-SN remote chassis?
The product data says only discrete I/O modules can be used on the remote link. p. 3
How fast is 1771-SN remote I/O?
Slower than local I/O; the example gives a 203ms worst-case response with 2 remote chassis. p. 2
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
Sub I/O Scanner Module Cat. No. 1771-SN, Series A, Revision D Product Data
Expand your system with remote I/O. Use the 1771-SN Sub I/O Scanner to expand your I/O sub-system by up to 896 digital remote I/O.
Locate I/O in up to 16 remote chassis using as many as seven rack numbers. The sub I/O scanner can interface a maximum of 16 remote I/O adapters on an Allen-Bradley universal remote I/O link. The addressing scheme of the sub I/O scanner module can accommodate up to seven logical racks in quarter-rack increments.
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
Product Data Sub I/O Scanner Module Cat. No. 1771-SN
System Overview
The figure below shows a typical configuration using a 1771-SN Sub I/O Scanner Module with a local PLC processor. You install the scanner into an I/O module slot in the PLC chassis and connect it to the remote I/O adapters (using discrete I/O) through a twinaxial cable. 1771 – SN Scanner
Remote I/O Chassis
1771 – ASB Any slot PLC-5, PLC-2, PLC-5/250and PLC-3
Remote I/O Chassis1771 – ASBNode adapter devices
Up to sixteen devices total 18404
Response Time
Remote I/O response time is longer than local I/O response time. For example, with 2 remote I/O chassis, a local scan time of 40ms, and an input-circuit delay time of 24ms, the worst-case response of a remote output to a change at a remote input would be 203ms. Use the 1771-SN Scanner module for monitoring digital input and controlling digital outputs not requiring fast response times. For example, thumbwheel switch inputs, pilot light outputs and other operator-interface switching and read-out devices.
2
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
Product Data Sub I/O Scanner Module Cat. No. 1771-SN
Compatible Processors
Use the 1771-SN Scanner Module with any processor with block-transfer capability.
Compatible Adapters
The 1771-SN Scanner Module communicates only with adapters with discrete transfer capability. The module does not support complementary I/O.
Compatible Remote I/O
Communication on the remote I/O link is limited to single-transfer of I/O data (a single word of input and/or output data per I/O group). This means you must use only discrete I/O modules.
System Compatibility
You can use the 1771-SN Sub I/O Scanner Module in any 1771 I/O chassis. Communication between the scanner module and the processor is bi-directional. The processor block-transfers output data through the output image table to the module and block-transfers input data from the module through the input image table. The module also requires an area in the data table to store the read block and write block. I/O image table use is an important factor in module placement and addressing selection. We list module use of the processor’s data table in the following table: Catalog Number
Input-image BitsOutput-image BitsRead-block WordsWrite-block Words1771-SN8816–6416–64
The read and write blocks each require an overhead of 8 words plus an additional 8 words for each remote I/O rack
Operation
The 1771-SN Scanner Module communicates with the local processor using block-transfers. You enter the block-transfer instruction into your processor’s ladder program. A block-transfer write instruction placed in the processor’s ladder program transfers data from the processor’s data table to the 1771SN Scanner Module’s output image table to remote output modules. The 1771-SN Scanner Module maintains an input image table with data collected form the remote input modules. A block-transfer read instruction place in the processor’s ladder program transfers data from the 1771-SN Scanner Module’s input image table to a location in the processor’s data table.
3
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
Product Data Sub I/O Scanner Module Cat. No. 1771-SN
Specifications
1771-SN Sub I/O Scanner Module Module Location
1771-A1B thru -A4B or later I/O chassis and 1771-AM1 and -AM2 I/O chassis
Data Transmission Rate
10,000 cable-feet at 57.6k bits/s 5,000 cable-feet at 115.2k bits/s
Interconnect Cable
1770-CD or equivalent (refer to the Approved Cable Vendor List, pub. no. ICCG-2.2)
Backplane Current1.2APower Dissipation7W maximum @ 1.2AThermal Dissipation24 BTU maximum @ 1.2AKeying
Between 2 and 4 Between 24 and 26
Environmental Conditions: Operating Temperature Storage Temperature Relative Humidity
0° to 60°C (32° to 140°F) –40° to 85°C (–40° to 185°F) 5% to 95% (without condensation)
System
Supports PLC-2 rack addresses 1 thru 7 Supports up to 16 total adapters Does not support complementary I/O
Part Numbers and Catalog Numbers
Daisy-Chain configurations Phoenix Connector (6-pin) (Allen-Bradley part number 940611-01) 1771-ASB Remote I/O Adapter termination resistor (Cat. No. 1770-XT) Dropline Configurations T-Connector (Cat. No. 1770-XG), Allen-Bradley part number 966308-01) Station Connector (Cat. No. 1770-SC), (Allen-Bradley part number 966080-01) Terminator Set (Cat. No. 1770-XF), (Allen-Bradley part number 966307-01)
PLC, RediPANEL, PanelView, PLC-2/15, PLC-5/10, PLC-5/12 and Dataliner are trademarks of Allen-Bradley Company, Inc.
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world’s leading technology companies.
Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
4 Publication 1771-2.91 – May 1995 Supersedes Publication 1771-2.91 – December 1990
Copyright 1995 Allen-Bradley Company, Inc. Printed in USA