Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual: 7 - Memory Organization

Pages 108 to 119 of 492, from Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1772-LX / LXP

Page 108

7

Chapter

Memory Organization

Chapter Objectives

This chapter discusses: hardware and its relationship to your program memory and its components This chapter provides detailed concepts of the memory’s organization and its structure. Understanding these concepts aids you in programming your processor.

Introduction

Before we explain memory organization and its structure, read the following definitions: Bit - the smallest unit of information that memory is capable of retaining Byte - a group of 8 consecutive bits (00-0708 or 10-1708) Word - a group of 16 consecutive bits (00-1708) Bits

17

16

15

14

13

12

11

10

07

Byte (upper)

06

05

04

03

02

01

00

Byte (lower) Word

10346-I

In the program, the input or output instruction address is associated with a specific I/O terminal. See chapter 5 for more information.

7-1

Page 109

Chapter 7 Memory Organization

Memory Areas

Memory is divided into three major areas: data table, user program, and message storage area. These areas store input status, output status, and program instructions and messages. Data Table The first part of memory is the data table (Figure 7.1). The processors are factory configured for 128 words. Figure 7.2 shows memory structure with a factory configured data table. The specific concepts throughout this publication refer to a factory configured data table. Figure 7.1 Simplified Memory Structure

Data Table

Main Program User Program Subroutine Message Storage Area

7-2

10151-I

Page 110

Chapter 7 Memory Organization

Figure 7.2 Data Table Factory Configured for 2-Slot Addressing Total Decimal Words

8

Decimal Words Per Area

8

Word Address

Processor Work Area No. 1

Bit Address 000

00

007 010

17 00

017 020

17 00

026 027 030

17

077 100

17 00

107 110

17 00

117 120

17 00

Output 7 Image Table 16

8 Bit/Word Storage

24

64

72

8

40

8

Reserved

1

2

Timer/Counter Accumulated Values (AC) (or Bit/Word Storage)

Processor Work Area No. 2 Input Image Table

80

8 Bit/Word Storage

88

8 Timer/Counter Preset Values (PR) (or Bit/Word Storage)

3

4

00

FactoryConfigured Data Table 6

5

127 130

17 00

177 200

17 00

128

40

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

1920 3968 7808

1792 3840 7680

Expanded Data Table and/or User Program

3577 17 7577 17 17177 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

2048 4096 7936

128 128 128

User Program

3777 17 7777 17 17377 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

1 2 3 4 5 6 7

May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. Unused timer/counter memory words can reduce data table size and increase user program area. May not be used for preset values. Do not use word 127 for block transfer data storage. Can be decreased to 48 words. Do not use for bit/word storage.

10148-I

7-3

Page 111

Chapter 7 Memory Organization

Figure 7.3 Data Table Configured for 1-Slot Addressing

Total Decimal Words

Decimal Words Per Area

8

8

Word Address

Bit Address 000 00

Processor Work Area No. 1

007 17 010 00

Output Image Table Rack 1 6 16

8

017 17 020 00

Output Image Table Rack 2 1 1 24

8

Reserved

2

7

64

40

Timer Counter Accumulated Values (AC) (or Bit Word Storage) 3

72

8

Processor Work Area No. 2

026 17 027 030 00 077 17 100 00

Configured for 1-Slot Addressing Data Table 5

107 17 110 00

Input Image Table Rack 1 6 80

8

88

8

Input Image Table Rack 2 6

128

40

Timer Counter Preset Values (PR) (or Bit Word Storage)

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

1920 3968 7808

1792 3840 7680

Expanded Data Table and/or User Program

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

2048 4096 7936

128 128 128

User Program

1 2 3 4 5 6 7

7-4

117 17 120 00 4

127 17 130 00 177 17 200 00 3577 17 7577 17 17177 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

3777 17 7777 17 17377 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. Unused timer/counter memory words can reduce data table size and increase user program area. Do not use word 127 for block transfer data storage. Can be decreased to 48 words. Used with 1-slot addressing. You cannot put an output or block transfer module in rack 2, I/O group 7 when using 1-slot addressing. You can put an input module in rack 2, I/O group 7.

10349–I

Page 112

Chapter 7 Memory Organization

Figure 7.4 Data Table Configured for 1/2-Slot Addressing Word Address

Total Decimal Words

Decimal Words Per Area

8

8

Processor Work Area No. 1

16

8

Output Image Table Rack 1

24

8

Output Image Table Rack 2 1 Reserved 2 6

32

8

Output Image Table Rack 3

40

8

64

24

Output Image Table Rack 4 Timer/Counter Accumulated Values (AC) 3 (or Bit/Word Storage)

72

8

Processor Work Area No. 2

Bit Address 000 00 007 17 010 00 017 17 020 00 026 17 027 030 00 037 17 040 00 047 00 050 00 077 17 100 00

Configured for 1/2-Slot Addressing Data Table 5

107 17 110 00

Input Image Table Rack 1 80

8

88

8

Input Image Table Rack 2

96

8

Input Image Table Rack 3

8

Input Image Table Rack 4

24

Timer/Counter Preset Values (PR) (or Bit/Word Storage)

104

128 Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

1920 1792 3968 3840 7808 7680

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

2048 4096 7936

128 128 128

117 17 120 00 4

127 17 130 00 137 17 140 00 147 00 150 00

Expanded Data Table and/or User Program

177 17 200 00 3577 17 7577 17 17177 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

User Program

3777 17 7777 17 17377 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. 3 Unused timer/counter memory words can reduce data table size and increase user program area. 4 Do not use word 127 for block transfer data storage. 5 Can be decreased to 48 words. 6 You cannot put an output or block transfer module in rack 2, I/O Group 7 when using 1/2-slot addressing. You can put an input module in rack 2, I/O group 7. 1 2

10350–I

7-5

Page 113

Chapter 7 Memory Organization

Data Table Areas The following areas make up the data table. They are: processor work area no. 1 output image table bit/word storage (020-027) timer/counter accumulated values and internal storage processor work area no. 2 input image table bit/word storage (120-127) timer/counter preset values and internal storage Chapter 2 describes the input and output image tables. The following sections describe the remaining areas. Processor Work Areas There are two processor work areas. They are located at addresses 000 00 to 007 17 and 100 00 to 107 17. The processor uses these 16 words for its internal control functions. You cannot address these data table words. Bit/Word Storage There are two bit/word storage areas (providing you are not using 1-slot addressing). They are located at addresses 020-026 and 120-127. Diagnostic Word: Word 027 Bits in word 027 are used by the processor for internal control functions. This Bit:

Stores this Information:

00

(Battery low) - set when the battery is low.

01

(EEPROM) - set indicates that EEPROM transferred at power-up. This bit is always reset (0) when the processor powers down

02

(STI too long) - set indicates subroutine execution time plus program transition time exceed service time.

03

Reserved.

04 05 06

7-6

07

Reserved for Data Highway - set when the processor is connected to the line and actively communicating with the Data Highway.

10-15

Used in Report Generation for message request bits

16

Report Generation Busy bit

17

Report Generation Done bit

Page 114

Chapter 7 Memory Organization

Adjusting the Data Table

You can adjust the size of a data table at any time during programming or editing. Using the 1770-T3 terminal, you can expand the data table in steps of two words from 48 words to 256 words and then in steps of 128 words to 1,920 words for a Mini-PLC-2/02, 3,968 words for a Mini-PLC-2/16 or 7,808 words for a Mini-PLC-2/17. You can expand the data table to accommodate the full I/O capacity of the processor. Expanding the data table provides more timer/counters or up to 488 timers/counters maximum and space for files (see chapter 11). Expanding the data table reduces the size of the user program and memory storage area. You should allow sufficient room for both data table and user program. To use the data table to its fullest capacity, remember the following: The processor initially reserves the first 128 words in the memory for the data table. You can adjust the data table size in two word increments to 256 words. Then, you can increase the data table size in blocks of 128 words. When the data table is set to 256 words, you can program up to 104 timer/counter instructions. If a block transfer instruction in your program addresses a module in rack 2 and you have a 1770-T3 series A or B terminal, you cannot decrease the size of the data table but you can increase it. You can use the two GET method for performing block transfers in rack 2 (see chapter 18).

Expanding the Data Table To expand your data table to any size between 48 and 128 words, do this: Between 48 and 128 Words SEARCH The word SEARCH appears in the lower left hand corner of the screen. 50

DATA TABLE CONFIGURATION NUMBER OF 128-WORD D. T. BLOCKS NUMBER OF INPUT/OUTPUT RACKS NUMBER OF T/C (if available) DATA TABLE SIZE

01 2 040 0128

This illustration shows a factory-configured data table. The numbers shown are default values. Numbers must be replaced by user-entered values. Enter the number of timer/counters equivalent to the size of the data table (Table 7.A).

7-7

Page 115

Chapter 7 Memory Organization

Table 7.A The Data Table Sizes Between 48 and 256 Words Number of Timers and Counters

Data Table Size

Number of Timers and Counters

Data Table Size

Number of Timers and Counters

Data Table Size

000

0048

001 002 003 004 005

0050 0052 0054 0056 0058

036 037 038 039 040

0120 0122 0124 0126 0128

071 072 073 074 075

0190 0192 0193 0196 0198

006 007 008 009 010

0060 0062 0064 0068

041 042 043 044 045

0130 0132 0134 0136 0138

076 077 078 079 080

0200 0202 0204 0206 0208

011 012 013 014 015

0070 0072 0074 0076 0078

046 047 048 049 050

0140 0142 0144 0146 0148

081 082 0873 084 085

0210 0212 0214 0216 0218

016 017 018 019 020

0080 0082 0084 0086 0088

051 052 053 054 055

0150 0152 0154 0156 0158

086 087 088 089 090

0220 0222 0224 0026 0228

021 022 023 024 025

0090 0092 0094 0096 0098

056 057 058 059 060

0160 0162 0164 0166 0168

091 092 093 094 095

0230 0232 0234 0236 0238

026 027 028 029 030

0100 0102 0104 0106 0108

061 062 063 064 065

0170 0172 0174 0176 0178

096 097 098 099 100

0240 0242 0244 0246 0248

031 032 033 034 035

0110 0112 0114 0116 0118

066 067 068 069 070

0180 0182 0184 0186 0188

101 102 103 104

0250 0252 0254 0256

For 92 words, enter 022. 022

DATA TABLE CONFIGURATION NUMBER OF 128-WORD D. T. BLOCKS NUMBER OF INPUT/OUTPUT RACKS NUMBER OF T/C (if available) DATA TABLE SIZE

7-8

01 2 022 0092

Page 116

Chapter 7 Memory Organization

Three things happen to the display. The cursor returns to the NUMBER OF 128–WORD D.T. BLOCKS. NUMBER OF T/C changes to 022. DATA TABLE SIZE becomes 92.

Expanding the Data Table Between 130 and 256 Words 02

To expand your data table to any size between 130 and 256 words, do this: DATA TABLE CONFIGURATION NUMBER OF 128-WORD D. T. BLOCKS NUMBER OF INPUT/OUTPUT RACKS NUMBER OF T/C (if available) DATA TABLE SIZE

01 2 104 0258

Three things happen to the data table configuration: The cursor jumps to the Number of T/C. Number of T/C changes to 104. Data table size becomes 256. Enter the number of timer/counters equivalent to the desired size of the data table (Table 7.A). 065

DATA TABLE CONFIGURATION NUMBER OF 128-WORD D. T. BLOCKS NUMBER OF INPUT/OUTPUT RACKS NUMBER OF T/C (if available) DATA TABLE SIZE

021 2 165 0178

Three things happen to the data table configuration: The cursor returns to the NUMBER OF 128–WORD D.T. BLOCKS. NUMBER OF T/C changes to 065. DATA TABLE SIZE becomes 178. If you want to increase the data table size to 256 words, press 02 and then CANCEL COMMAND. If you want to increase the data table size beyond 256 words, remember the data table increases in steps of 128 words. See Table 7.B.

7-9

Page 117

Chapter 7 Memory Organization

Table 7.B The Data Table Sizes Between 384 and 7,808 words Enter

Data Table Size

Enter

Data Table Size

The Mini-PLC-2/02 has this number of data table blocks. 3 4 5 6 7 8 9

384 512 640 768 896 1024 1152

10 11 12 13 14 15

1280 1408 1536 1664 1792 1920

The Mini-PLC-2/16 has this additional number of data table blocks. 16 17 18 19 20 21 22 23

2048 2176 2304 2432 2560 2688 2816 2944

24 25 26 27 28 29 30 31

3072 3200 3328 3456 3584 3712 3840 3968

32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

4096 4229 4352 4480 4608 4736 4864 4992 5120 5248 5376 5504 5632 5760 5888

47 48 49 50 51 52 53 54 55 56 57 58 59 60 61

6016 6144 6272 6400 6528 6656 6784 6912 7040 7168 7296 7424 7552 7680 7808

After you have adjusted the data table, press CANCEL COMMAND and we will continue.

7-10

Page 118

Chapter 7 Memory Organization

User Program

The second major part of memory is the user program (Figure 7.1). It is divided into two areas: This Area:

Stores this:

main program

The program is a group of ladder diagram instructions that control an application that guides the processor. These instructions can examine or change the status of bits in the memory of the processor. The status of these bits determines the operation of your output devices. When you write a program, you specify the things you want done in your application and the conditions that must be met before those things should be done.

subroutine area

This area stores small programs that are periodically accessed. The subroutine area is not scanned unless you program the processor to jump to this area (which is located in the memory between the main program and the message store areas). This area acts as the end of program statement for the main program.

The user program area begins at the end of the data table.

Message Storage

The third major part of memory is the message storage area (Figure 7.1). You are able to print messages in hard copy. You can store up to 70 messages using the 1770-T3 terminal, or 198 messages using the 1770-RG module and an RS-232-C device. Message storage follows the end statement of your program and is limited by the number of unused words remaining in memory. Each word stores two alphanumeric characters. A character is any alpha or numerical figure (this includes blank spaces).

7-11

Page 119

Chapter 7 Memory Organization

Examining the Memory If you want to examine the memory layout:

SEARCH The word SEARCH appears in the lower left hand corner of the screen. 54

Memory Layout Display Mini-PLC-2/17 Mini-PLC-2/16 Data Table Size 128 words

Data Table Size 128 words

User Program Area 0001 words

User Program Area 0001 words

User Message Area 0000 words Unused Memory Available 3967 words

User Message Area 0000 words Unused Memory Available 7807 words

Mini-PLC-2/02 Data Table Size 128 words User Program Area 0001 words User Message Area 0000 words Unused Memory Available 1919 words

This illustrates the memory layout display for a 128 word data table. Even if there are no messages or programs in the memory, the END statement is there and it requires one word. Adding the number of words in the four areas equals the memory size (decimal).

7-12