Chapter 21 Sequencer

Start by positioning your cursor on the words SEQUENCER INPUT. Use the arrow keys to move the cursor. DISPLAY

0

The word display appears in the lower left hand corner of the screen. BINARY DATA MONITOR SEQUENCER OUTPUT STEP: 001 SEQUENCER LENGTH: COUNTER ADDR: 200 FILE: 400- 413 201 OUTPUT ADDR: 110 DATA: 00000000 00000000 00000000 00000000 MASK ADDR: 070 DATA: 00000000 00000000 STEP 001 002 003 004 005 006

006

071 00000000 00000000

WORD 1 WORD 2 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 DATA: 00000000 00000000

The cursor is located on the last digit of the first word of DATA in the Command Buffer. The digits in step 1 for word 1 are intensified. 00000010 00000000

BINARY DATA MONITOR SEQUENCER OUTPUT STEP: 001 SEQUENCER LENGTH: COUNTER ADDR: 200 FILE: 400- 413 201 OUTPUT ADDR: 110 DATA: 00000000 00000000 00000000 00000000 MASK ADDR: 070 071 DATA: 00000000 00000000 00000000 00000000 STEP WORD 1 WORD 2 001 00000000 00000000 00000000 00000000 002 00000000 00000000 00000000 00000000 003 00000000 00000000 00000000 00000000 004 00000000 00000000 00000000 00000000 005 00000000 00000000 00000000 00000000 006 00000000 00000000 00000000 00000000 DATA: 00000010 00000000

006

21-9

Page 335

Chapter 21 Sequencers

INSERT

BINARY DATA MONITOR SEQUENCER OUTPUT STEP: 001 SEQUENCER LENGTH: COUNTER ADDR: 200 FILE: 400- 413 201 OUTPUT ADDR: 110 DATA: 00000000 00000000 00000000 00000000 MASK ADDR: 070 071 DATA: 00000000 00000000 00000000 00000000 STEP WORD 1 WORD 2 001 00000010 00000000 00000000 00000000 002 00000000 00000000 00000000 00000000 003 00000000 00000000 00000000 00000000 004 00000000 00000000 00000000 00000000 005 00000000 00000000 00000000 00000000 006 00000000 00000000 00000000 00000000 DATA: 00000010 00000000

006

Data is inserted into Step 001 of Word 1. ↓ ↓

Cursor down one line. The cursor is on the last digit of the second word of DATA in the command buffer. The digits in step 2 for word 2 are intensified.

00000010 00000001

21-10

BINARY DATA MONITOR SEQUENCER OUTPUT STEP: 001 SEQUENCER LENGTH: COUNTER ADDR: 200 FILE: 600- 613 013 OUTPUT ADDR: 012 DATA: 00000000 00000000 00000000 00000000 MASK ADDR: 075 076 DATA: 00000000 00000000 00000000 00000000 STEP WORD 1 WORD 2 001 00000010 00000000 00000000 00000000 002 00000000 00000000 00000000 00000000 003 00000000 00000000 00000000 00000000 004 00000000 00000000 00000000 00000000 005 00000000 00000000 00000000 00000000 006 00000000 00000000 00000000 00000000 DATA: 00000010 00001001

006

Page 336

Chapter 21 Sequencer

INSERT

↓ ↓

BINARY DATA MONITOR SEQUENCER OUTPUT STEP: 001 SEQUENCER LENGTH: COUNTER ADDR: 200 FILE: 600- 613 013 OUTPUT ADDR: 012 DATA: 00000000 00000000 00000000 00000000 MASK ADDR: 075 076 DATA: 00000000 00000000 00000000 00000000 STEP WORD 1 WORD 2 001 00000010 00000000 00000000 00000000 002 00000010 00000001 00000000 00000000 003 00000000 00000000 00000000 00000000 004 00000000 00000000 00000000 00000000 005 00000000 00000000 00000000 00000000 006 00000000 00000000 00000000 00000000 DATA: 00000010 00000001

006

Cursor down one line.

The cursor is on the last digit of the third word of DATA in the command buffer. The digits in step 3 for word 3 are intensified. Continue inserting your data. 003: 004: 005: 006:

00000010 00000010 00000010 00000010

00010001 00010001 01000001 00000000

To add data to WORD 2 press [Shift] [→] and cursor up or down as needed. Do not press [Cancel Command]. We will use the display to add a mask. DISPLAY

The word DISPLAY appears in the lower left hand corner of the screen.

21-11

Page 337

Chapter 21 Sequencers

000

BINARY DATA MONITOR SEQUENCER OUTPUT STEP: 001 SEQUENCER LENGTH: COUNTER ADDR: 200 FILE: 400- 413 201 OUTPUT ADDR: 110 DATA: 00000000 00000000 00000000 00000000 MASK ADDR: 070 071 DATA: 00000000 00000000 00000000 00000000 STEP WORD 1 WORD 2 001 00000010 00000000 00000000 00000000 002 00000010 00000001 00000000 00000000 003 00000010 00010001 00000000 00000000 004 00000010 00010001 00000000 00000000 005 00000010 01000001 00000000 00000000 006 00000010 00000000 00000000 00000000 DATA: 00000010 00000000

006

The cursor is on the first digit of DATA in the command buffer. The digits for INPUT ADDR 110, DATA are intensified. Cursor down one line. The display for MASK ADDR 070, DATA are intensified.

00000010 01010001

21-12

BINARY DATA MONITOR SEQUENCER OUTPUT STEP: 001 SEQUENCER LENGTH: COUNTER ADDR: 200 FILE: 400- 413 201 OUTPUT ADDR: 110 DATA: 00000000 00000000 00000000 00000000 MASK ADDR: 070 071 DATA: 00000000 00000000 00000000 00000000 STEP WORD 1 WORD 2 001 00000000 00000000 00000000 00000000 002 00000000 00000001 00000000 00000000 003 00000000 00000000 00000000 00000000 004 00000000 00000000 00000000 00000000 005 00000000 00000000 00000000 00000000 006 00000000 00000000 00000000 00000000 DATA: 00000010 01010001

006

Page 338

Chapter 21 Sequencer

SHIFT

CANCEL COMMAND

Sequencer Output

BINARY DATA MONITOR SEQUENCER OUTPUT STEP: 001 SEQUENCER LENGTH: COUNTER ADDR: 200 FILE: 400- 413 201 OUTPUT ADDR: 110 DATA: 00000000 00000000 00000000 00000000 MASK ADDR: 070 071 DATA: 00000010 01010001 00000000 00000000 STEP WORD 1 WORD 2 001 00000010 00000000 00000000 00000000 002 00000010 00000001 00000000 00000000 003 00000010 00010001 00000000 00000000 004 00000010 00010001 00000000 00000000 005 00000010 01000001 00000000 00000000 006 00000010 00000000 00000000 00000000 DATA: 00000010 01010001

006

To display your rung.

The Sequencer Output instruction transfers the values of the current sequencer step to a specified output word. Here are some characteristics of the sequencer output instruction. You can transfer up to 64 bits. This instruction is programmed as an output instruction (can be programmed in the same rung as a sequencer input instruction). You can mask the unused output bits. The counter is internally indexed by the instruction (external counter instruction is not required). The instruction requires 5-8 words of your program. If the rung condition becomes: True False

The counter increments to the next step and transfers the data. No action is taken.

21-13

Page 339

Chapter 21 Sequencers

ATTENTION: The counter address for the Sequencer Output instruction should be reserved for that instruction. Do not manipulate the counter accumulated or preset values. Inadvertent changes to these values could result in hazardous machine operation or a RUN TIME ERROR. Damage to equipment and/or personal injury could result.

You are now ready to insert this instruction. The word SEQUENCER appears in the lower left hand corner of the screen.

0

SEQUENCER INPUT COUNTER ADDR: CURRENT STEP: SEQ LENGTH: WORDS PER STEP: FILE: 400MASK: 070INPUT WORDS 2: 1: 110 3: 4:

200 001 006 2 413 071 201

SEQUENCER INPUT COUNTER ADDR: 030 CURRENT STEP: 001 SEQ LENGTH: 001 WORDS PER STEP: 1 FILE: 110- 110 MASK: 010- 010 INPUT WORDS 2: 1: 010 3: 4:

030 EN 17 030 DN 15

Notice that the words SEQUENCER OUTPUT are flashing, the cursor is on the first digit of the counter address, and the default values are shown. Insert the following values. Your cursor will move automatically throughout the block instruction. The values are: COUNTER ADDR: CURRENT STEP: SEQ LENGTH: WORDS PER STEP: FILE: MASK: OUTPUT WORDS:

21-14

200 001 006 2 600 075 1: 012 2: 013

Page 340

Chapter 21 Sequencer

Your sequencer output instruction should look like this: SEQUENCER INPUT COUNTER ADDR: CURRENT STEP: SEQ LENGTH: WORDS PER STEP: FILE: 400MASK: 070INPUT WORDS 2: 1: 110 3: 4:

200 001 006 2 413 071 201

SEQUENCER INPUT COUNTER ADDR: CURRENT STEP: SEQ LENGTH: WORDS PER STEP: FILE: 600MASK: 075INPUT WORDS 2: 1: 012 3: 4:

200 001 006 2 613 076

200 EN 17 200 DN 15

013

To continue, enter your data using the binary data monitor mode. You will get your data from the worksheet in Figure 21.6. A filled-in block means that a 1 should be inserted in the corresponding bit location.

21-15

Page 341

Chapter 21 Sequencers

Figure 21.6 Completed Sequencer Output Worksheet

PROJECT NAME

ALLEN-BRADLEY Programmable Controller Sequencer Table Bit Assignments

PAGE

PROCESSOR

Mini–PLC–2/16

Bottle Filling Applications

DESIGNER

SEQUENCER FILE

OUTPUT

COUNTER ADDR:

200

WORD ADDR:

012

013

MASK ADDR:

075

076

WORD #1

TO

613

10 07

SEQ LENGTH:

006

WORD #3 00 17

10 07

WORD #4 00 17

10 07

00

Timer

CM

CMT

00 17

FTM

FTR

SOL

FTF

D E N V A I M C E E

600

WORD #2

10 07

FTS

17

2

TO

DATA TABLE ADDR

Engineer

OF

2

MASK STEP

1 2 3 4 5 6

FROM ADDR TO ADDR

Note: A filled-in box means that each device is actuated

21-16

10148-I