Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual: 15 - EAF Log, Trig, and FIFO Instructions, pages 194 to 202

Pages 194 to 202 of 490, from Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1772-LW /LWD, Allen-Bradley 1772-LWP, Allen-Bradley 1772-LX / LXP and Allen-Bradley 1772-LZP

Page 194

Chapter

15

EAF Logarithmic, Trigonometric, and FIFO Instructions

Chapter Objectives

This chapter describes the Logarithmic, Trigonometric, and FIFO Load, and FIFO Unload EAF instructions. Table 15.A EAF Function Numbers If you want to perform an operation of this type

Use this function number

The Mini-PLC-2/02, Mini-PLC-2/16 and Mini-PLC-2/17 can perform these functions FIFO Load FIFO Unload Log10 Sin x Cos x

(28) (29) (30) (35) (36)

The Mini-PLC-2/17 can perform these additional functions. Loge

One Operand EAFs

(31)

When a processor executes an EAF, it uses the data table format shown in Figure 15.1. The Operand represents the number you manipulate.

15-1

Page 195

Chapter 15 EAF Logarithmic, Trigonometric and FIFO Instructions

Figure 15.1 EAF One Operand Word and Digit Format in the Data Table 17

16

15

14 13

S Operand

Result

X

S

0

10 7

43

0 Data Address b

Digit 1 MSD

Digit 2

Digit 3

Digit 4

Digit 5

Digit 6 d

Digit 7

Digit 8

Digit 9 g

Digit 10

Digit 11

Digit 12 LSD k

Result Address r

O/U r+1 r+2 r+3 10363-I

The Operand and the Result words have the format xxx xxx . xxx xxx. You can enter them from the keyboard of your 1770-T3 terminal or through ladder diagram instructions. If you select a data address (inside the EAF) other than 010 for the Operand, you can locate the data anywhere in your data table. However, you must select four consecutive data table addresses (Figure 15.2). If you choose to enter the default address (010) as the Data Address inside the EAF instruction, the processor seeks its data from the Get instructions in the Operand rung. Address 010 will not be altered or used by this instruction. The Get instruction must be located in the rung immediately before the EAF instruction. You may select up to four data table addresses (Figure 15.2). You can locate the Result word anywhere in your program. However, you must select four consecutive addresses for the result. If you select an address of 060 for the Result, the EAF automatically reserves the next three higher addresses. To enter the number ABC use only one Get or one data table word. Important: If there is only one Get, the value is placed immediately to the left of the decimal point. ––––[G]––– +/– ABC

15-2 xxx ABC . xxx xxx

Page 196

Chapter 15 EAF Logarithmic, Trigonometric and FIFO Instructions

To enter the number ABC DEF use two Gets or two data table words. ––––[G]–––[G]––– +/– ABC DEF

ABC DEF . xxx xxx

To enter the number ABC DEF . GHI use three Gets or three data table words. ––––[G]–––[G]–––[G]––– +/– ABC DEF GHI

ABC DEF . GHI xxx

To enter the number ABC DEF . GHI JKL use four Gets or four data table words. ––––[G]–––[G]–––[G]–––[G]––– ABC DEF . GHI JKL +/– ABC DEF GHI JKL The numbers have a fixed decimal point that is implied but not displayed. The Result word can be placed in any legal location in the data table. However, you must select four consecutive address locations. The Result word format is similar to the Operand format except that there are three status bits. Bits 14-17 of the result word are reserved for status bits: This Bit: 14

Stores this: overflow/underflow 1 you entered a number that is out of range 0 result is in range Log10 and Loge 1 you tried to find the log of zero and the result indicates zero; or you tried to fin the log of a negative number and the result indicates 999 999 . 999 999 0 result is in range

15 zero indicator 1 zero result 0 non-zero result

16 sign bit 1 negative (-) 0 positive (+)

17 not used

15-3

Page 197

Chapter 15 EAF Logarithmic, Trigonometric and FIFO Instructions

Data Table Format After Address Entry Be careful not to select operand (data) and result addresses so that they overlap. Figure 15.2 EAF Word Format in the Data Table After Address Entry 17

16 S

15

Operand

X

Result

S

0

14 13 10 7 43 Digit 1 Digit 2 Digit 3 MSD

0 Data Address 040

Digit 4

Digit 5

Digit 6

041

Digit 7

Digit 8

Digit 9

042

Digit 10

Digit 11

Digit 12 LSD

043 Result Address 060

O/U

061 062 063 10364-I

Entry and Display of Input and Result Values Figure 15.3 shows one method for displaying operand (data) values and the result values of an EAF, not using the default address (010) as the Data Address inside the EAF instruction. The first branch contains the Result. The second branch contains the Operand. Addresses of the Operand do not have to be consecutive (if the Data Address in the instruction is 010). Figure 15.3 EAF Operand and Result Rung 060 G 000 040 G 000

15-4

061 G 012 041 G 144

062 G 000 042 G 000

063 G 000 043 G 000

EXECUTE AUX FUNCTION FUNCTION NUMBER: 05 DATA ADDR: 040 RESULT ADDR: 060

Page 198

Chapter 15 EAF Logarithmic, Trigonometric and FIFO Instructions

Keystrokes Enter an EAF input and result rung (like Figure 15.3) by performing the following steps. 1.

Press

2.

Enter the result branch with its four Gets. Press operand with its four Gets.

3.

Enter the values for the Operand.

4.

Complete the parallel branches.

5.

Press [Shift] [EAF].

6.

Enter the appropriate function number (Table 15.A).

7.

Enter the data and result addresses.

. and enter the

ATTENTION: Do not enter data in hexadecimal. Enter all data in BCD. Failure to observe this warning could cause unwanted machine motion and may injure personnel.

Log to Base 10 or Log to Base e

The EAF log instruction is a feature of the Mini-PLC-2/17 processor only. Word formats for log10 or the loge are the same. The only difference between the two EAFs is their function number: log10 is 30 and the loge is 31. log10 xxx xxx . xxx xxx = 000 00y . yyy yyy loge xxx xxx . xxx xxx = 000 0yy . yyy yyy Enter an EAF rung like that in Figure 15.4 Figure 15.4 EAF Log to Base 10 Function, Operand and Result Rung 060 G 000 040 G 000

061 G 002 041 G 648

062 G 811 042 G 000

063 G 572 043 G 000

EXECUTE AUX FUNCTION FUNCTION NUMBER: 30 DATA ADDR: 040 RESULT ADDR: 060

15-5

Page 199

Chapter 15 EAF Logarithmic, Trigonometric and FIFO Instructions

Enter the value for the operand. Entry of operand (base 10) = 648 produces the result 2.811572. Figure 15.5 shows how the result is stored in the data table. Figure 15.5 EAF Log to Base 10 Format in the Data Table After Execution

Operand

17

16

X

S

X

S

15 0

0

14 13 O/U

O/U

Result

Sine and Cosine

10 7

43

Data 0 Address 040

0

0

0

6

4

8

0

0

0

0

0

0

043

041 042

0

0

0

Result Address 060

0

0

2

061

8

1

1

062

5

7

2

063

10365-I

This EAF trigonometric function finds the sine (or cosine) of an angle. The angle operand (data) is in degrees. Word formats for sine and cosine are the same. The only difference between the two EAFs is their function numbers: sine is 35 and cosine is 36. Both functions operate based on 6-digit operands. sine +/–xxx xxx . xxx xxx = +/–yyy yyy . yyy yyy Enter an EAF rung like that shown in Figure 15.6 Figure 15.6 EAF Sine Function, Operand and Result Rung 060 G 000 040 G 000

061 G 002 041 G 060

062 G 866 042 G 000

063 G 025 043 G 000

EXECUTE AUX FUNCTION FUNCTION NUMBER: 35 DATA ADDR: 040 RESULT ADDR: 060

Enter the value of the angle in degrees (operand rung). Enter the angle from the keyboard of your 1770-T3 terminal or through ladder diagram instructions. Entry of the angle 060 in word 041 produces the result

15-6

Page 200

Chapter 15 EAF Logarithmic, Trigonometric and FIFO Instructions

0.866025 for the sine function and and 0.500 for the cosine function. Figure 15.7 shows how it is stored in the data table. Figure 15.7 EAF Sine Function Format After Execution 17

FIFO Load and FIFO Unload

15 14 13

0

Operand

Result

16

X

S

O

10 7

43

Data 0 Address 040

0

0

0

0

6

0

0

0

0

0

0

0

043

041 042

0

0

0

Result Address 060

0

0

0

061

8

6

6

062

0

2

5

063

10366-I

The FIFO Load and FIFO Unload are output instructions that can be used together to construct an asynchronous word shift register. Length of the FIFO can be a maximum 999 words long. Upon a false-to-true transition of the FIFO Load rung, the contents of the Input Word is transferred into the File as long as the input word is non-zero. Upon a false-to-true transition of the FIFO Unload rung, the word at the top of the file (highest file address) is transferred out of the File to an Output Word. Important: Only non-zero values can be loaded. Use the full and empty flags in your ladder program to assure that the data being loaded/unloaded to/from the file is not lost or invalid.

15-7

Page 201

Chapter 15 EAF Logarithmic, Trigonometric and FIFO Instructions

Bits 14-17 of the result word are reserved for status bits: This Bit: 14

Stores this: file empty indicator 1 file is empty 0 file has data You cannot unload data from an empty file. If the FIFO file is empty, there is no data to unload. Use this bit to condition a FIFO Unload.

15 file full indicator 1 file is full 0 file has data You cannot load data after the FIFO file is full. If you attempt to load any data it will be lost. As soon as you unload the first word, the bit resets (0). Use this bit to condition a FIFO Load. Data transfers with a false to true (0 to 1) transition of the EAF rung. You can monitor this transition with bits 16 or 17.

16 unload enabled 1 FIFO is enabled 0 FIFO is not enabled

17 load enabled 1 FIFO is enabled 0 FIFO is not enabled

Important: The FIFO Load and FIFO Unload instructions must have the same File Address, Result Address and File Length. Data is loaded into and unloaded from the same addressed file. You can enter a ladder diagram for executing FIFO Loads and FIFO Unloads by entering a ladder diagram like that in Figure 15.8. This figure identifies all words and certain bits used in FIFO Load and FIFO Unload. Rungs 2, 3, 4 and 6 are included as display rungs and are not necessary for proper FIFO operation.

15-8

Page 202

Chapter 15 EAF Logarithmic, Trigonometric and FIFO Instructions

Figure 15.8 FIFO Load and FIFO Unload Ladder Diagram File Full Bit FIFO Load Conditioning Bit

File Address

130 00

15

060 G 000

030 G 040

031 G 005

032 G 060

050 G 000 040 G 000 FIFO Unload Conditioning Bit

050

Input Word Address Current Data Being Loaded

Input Word Address (

File Length Result Word Address (Number of Words Currently in File)

042 G 000

130

050

01

14

061 G 000

043 G 000

044 G 000

The File

Output Word Address Current Data Being Unloaded

FIle Enpty Bit

File Address

070 ) 00

070 ) 00 070 ( ) 00

( 041 G 000

033 G 040

EXECUTE AUX FUNCTION FUNCTION NUMBER:28 DATA ADDR: 030 RESULT ADDR: 050

034 G 005

035 G 061

EXECUTE AUX FUNCTION FUNCTION NUMBER:29 033 DATA ADDR: 050 RESULT ADDR:

Output Word Address

(

070 ) 00

File Length

Important: Read chapter 19 and become familiar with the concepts introduced in this chapter before attempting FIFO instructions. Figure 15.9 shows data (111) in the Input Word 060 ready to be loaded into the File. Toggle the precondition bit 13000 from false to true (0 to 1). Each time data is entered into the file, it is placed in the highest available address in the file. Observe that transferring data from the Input Word to the File does not destroy the data in the Input Word. Also, the Result Word (050) increments by 1 each time a transfer is performed. The Result Word indicates the number of words in your file at any given time. You can monitor the Result Word for this information.

15-9