Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual: E - Quick Reference, pages 463 to 471

Pages 463 to 471 of 490, from Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1772-LW /LWD, Allen-Bradley 1772-LWP, Allen-Bradley 1772-LX / LXP and Allen-Bradley 1772-LZP

Page 463

Appendix E Quick Reference

Help

Help Directories Function

Key Sequence

Mode

Description

Help directory

[HELP]

Any

Displays a list of the keys that are used with the [HELP] key to obtain further directories.

Control function directory

[SEARCH] [HELP]

Any

Provides a list of all control functions that use the [SEARCH] key.

Record function directory

[RECORD] [HELP]

Any

Provides a list of functions that use the [RECORD] KEY.

Clear memory directory

[CLEAR MEMORY] [HELP]

Remote Prog

Provides a list of all functions that use the [CLEAR MEMORY] key.

Data monitor directory

[DISPLAY] [HELP]

Any

Provides the choice of data monitor display accessed by the [DISPLAY] key.

File instruction directory

[FILE] [HELP]

Any

Provides a list of all instructions that use the [FILE] key.

Sequencer instruction directory

[SEQ][HELP]

Any

Provides a list of all instructions that use the [SEQ] key.

Block transfer directory

[BLOCK XFER] [HELP]

Any

Provides a list of all instructions that use the [BLOCK XFER] key.

[CANCEL COMMAND]

Any

To terminate.

All directories

E-19

Page 464

Appendix E Quick Reference

Memory Layout

To examine memory layout: SEARCH

The word SEARCH appears in the lower left hand corner of the screen. Memory Layout Display

54

Mini-PLC-2/16

Mini-PLC-2/17

Data Table Size 128 words

Data Table Size 128 words

User Program Area 0001 words

User Program Area 0001 words

User Message Area 0000 words

User Message Area 0000 words

Unused Memory Available 3967 words

Unused Memory Available 7807 words

Mini-PLC-2/02 Data Table Size 128 words User Program Area 0001 words User Message Area 0000 words Unused Memory Available 1919 words

This illustrates the memory layout display for a 178 word data table. Even if there are no messages or programs in the memory, the END statement is there and it requires one word. Adding the number of words in the four areas equals the memory size (decimal).

E-20

Page 465

Appendix E Quick Reference

Memory Structure Total Decimal Words

8

Data Table Factory Configured for 2-Slot Addressing Decimal Words Per Area

8

Word Address

Processor Work Area No. 1

Bit Address 000

00

007 010

17 00

017 020

17 00

026 027 030

17

077 100

17 00

107 110

17 00

117 120

17 00

Output 7 Image Table 16

8 Bit/Word Storage

24

64

72

8

40

8

Reserved

1

2

Timer/Counter Accumulated Values (AC) (or Bit/Word Storage)

Processor Work Area No. 2 Input Image Table

80

8 Bit/Word Storage

88

8 Timer/Counter Preset Values (PR) (or Bit/Word Storage)

3

4

00

FactoryConfigured Data Table 6

5

127 130

17 00

177 200

17 00

128

40

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

1920 3968 7808

1792 3840 7680

Expanded Data Table and/or User Program

3577 17 7577 17 17177 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

2048 4096 7936

128 128 128

User Program

3777 17 7777 17 17377 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

1 2 3 4 5 6 7

May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. Unused timer/counter memory words can reduce data table size and increase user program area. May not be used for preset values. Do not use word 127 for block transfer data storage. Can be decreased to 48 words. Do not use for bit/word storage.

10148-I

E-21

Page 466

Appendix E Quick Reference

Data Table Configured for 1-Slot Addressing

Total Decimal Words

Decimal Words Per Area

8

8

Word Address

Bit Address 000 00

Processor Work Area No. 1

007 17 010 00

Output Image Table Rack 1 6 16

8

017 17 020 00

Output Image Table Rack 2 1 1 24

8

Reserved

2

7

64

40

Timer Counter Accumulated Values (AC) (or Bit Word Storage) 3

72

8

Processor Work Area No. 2

026 17 027 030 00 077 17 100 00

Configured for 1-Slot Addressing Data Table 5

107 17 110 00

Input Image Table Rack 1 6 80

8

88

8

Input Image Table Rack 2 6

128

40

Timer Counter Preset Values (PR) (or Bit Word Storage)

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

1920 3968 7808

1792 3840 7680

Expanded Data Table and/or User Program

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

2048 4096 7936

128 128 128

User Program

1 2 3 4 5 6 7

E-22

117 17 120 00 4

127 17 130 00 177 17 200 00 3577 17 7577 17 17177 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

3777 17 7777 17 17377 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. Unused timer/counter memory words can reduce data table size and increase user program area. Do not use word 127 for block transfer data storage. Can be decreased to 48 words. Used with 1-slot addressing. You cannot put an output or block transfer module in rack 2, I/O group 7 when using 1-slot addressing. You can put an input module in rack 2, I/O group 7.

10349–I

Page 467

Appendix E Quick Reference

Data Table Configured for 1/2-Slot Addressing Word Address

Total Decimal Words

Decimal Words Per Area

8

8

Processor Work Area No. 1

16

8

Output Image Table Rack 1

24

8

Output Image Table Rack 2 1 Reserved 2 6

32

8

Output Image Table Rack 3

40

8

64

24

Output Image Table Rack 4 Timer/Counter Accumulated Values (AC) 3 (or Bit/Word Storage)

72

8

Processor Work Area No. 2

Bit Address 000 00 007 17 010 00 017 17 020 00 026 17 027 030 00 037 17 040 00 047 00 050 00 077 17 100 00

Configured for 1/2-Slot Addressing Data Table 5

107 17 110 00

Input Image Table Rack 1 80

8

88

8

Input Image Table Rack 2

96

8

Input Image Table Rack 3

8

Input Image Table Rack 4

24

Timer/Counter Preset Values (PR) (or Bit/Word Storage)

104

128 Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

1920 1792 3968 3840 7808 7680

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

2048 4096 7936

128 128 128

117 17 120 00 4

127 17 130 00 137 17 140 00 147 00 150 00

Expanded Data Table and/or User Program

177 17 200 00 3577 17 7577 17 17177 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

User Program

3777 17 7777 17 17377 17

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. 3 Unused timer/counter memory words can reduce data table size and increase user program area. 4 Do not use word 127 for block transfer data storage. 5 Can be decreased to 48 words. 6 You cannot put an output or block transfer module in rack 2, I/O Group 7 when using 1/2-slot addressing. You can put an input module in rack 2, I/O group 7. 1 2

10350–I

E-23

Page 468

Appendix E Quick Reference

PID Control Block

Control Word 01 Bit Descriptions: Status Bits 00

- Equation (Set by User) Independent Gain =0

Dependent Gain = 1

01

- Mode (Set by User) Auto = )

Manual = 1

02

- Control Action (Set by User) Direct (SP-PV) = 0

Reverse (PV-SP) = 1

03

- Output Limiting (Set by User) No - 0

Yes = 1

04

- Set Output (Set by User) Inhibited = 0

Enabled = 1

05

- Cascade Bit (Set by User) 3 No = 0 Secondary Cascade Loop = 1

06

- Derivative Uses Error (set by User) 3 PV = 0 E=1

07

- Input Format (for Series C or later) Binary = 0 BCD = 1

10

- Dead Band (set by Instruction) 1 Out of DB = 0 Within DB = 1

11

- Maximum Output Alarm (set by Instruction) 1 Within limit = 0 Above limit = 1

12

- Minimum Output Alarm (Set by Instruction) 1 Within limit = 0 Below limit = 1

13

- Set point Error (Set by Instruction) 1 In range = 0 Out of range = 1

14

- Reserved

15

- Done bit (set by Instruction) 1 Not executed = 0 Executed = 1

16

- Reserved

17

- Enabled bit (set by Instruction) 1 Not enabled = 0 Enabled = 1

1 2 3

E-24

2

2

Do not change. Values are set by PID function. Do not change Reserved bits. Do not change while the processor is operating.

Page 469

Appendix E Quick Reference

Control Word 02 Bit Descriptions: Status and SIgn Bits 00

-

01

- KP/10 (Set by User) Do not move decimal = 0 Move decimal = 1

02

- Feedforward/Bias Sign (Set by User) Pos = 0 Neg = 1

03

- Maximum Scaling Sign (Set by User) Pos = 0 Neg = 1

04

- Minimum Scaling Sign (Set by User) Pos = 0 Neg = 1

05

- Set Point Sign (Set by User) Pos = 0 Neg = 1

06

- Process Variable Sign (Set by Instruction) 1 Pos = 0 Neg = 1

07

- Error Sign (Set by Instruction) 1 Pos = 0 Neg = 1

10

- Resume Control From Last State 2 Disabled - on first scan, a new CO is calculated Enabled = on first scan, the accumulated integral value is back-calculated from the last CO value

11

- Bumpless Transfer With Proportional Controllers 3 0 = no adjustment to Bias 1 = bumpless manual to auto mode by adjusting Bias

1 2 3

KIx10 (Set by User) Do not move decimal = 0 Move decimal to right = 1

Do not change these vales. They are set by the PID function. This bit should only be set after the PID program has been run to obtain a valid last CO value Do not change while the processor is operating.

E-25

Page 470

Appendix E Quick Reference

Words 03 through 09 All range values are unitless unless noted otherwise. Independent Gain Equation Range

Range

Dependent Gain Equation Word 03

0000-9999

Set Point - SP Word 04

00.00-99.99

Word 05

Range

Range 1 2 3

E-26

Term 1/TI Range 00.00-99.99

Integral Gain

Units Word 06

Term KD Range Bit set 00.01-99.99 Bit reset 000.1-999.9 Units - sec

Unites - min

3

Range

Feedforward - FFWD 1 Word 08

0000-9999

Maximum Scaling Value 1 Word 09

0000-9999 rep/min

Term TD Range 00.00-99.99

Derivative Gain

Word 07 0000-4095 or 0000-FFFF

0000-9999

Range 00.00-99.99

Proportional Gain

Term KI Range Bit set 0.000-9.999 Bit reset 0.000-9.999 Units rep/sec

Range

Range 1

Minimum Scaling Value

Can be negative number by setting appropriate sign bits. Do not change while processor is operating. With word 02 Bit 11 set.

Range 2

Range

0000-4095 or 0000-FFFF

0000-9999

0000-9999

3

Page 471

Appendix E Quick Reference

Table 1.B Words 10 through 24 Independent Gain Equation Range

Range Units Range Unites

Range Units

Range Units

Range

Range

Range Units

Dependent Gain Equation Word 10

0000-9999

Zero Crossing Dead Band

Word 11 0000-100% Percent 0000-100%

Set Output Value Word 12 Maximum Control Output

Percent Word 13 0000-100%

Minimum Control Output

Percent Word 14 0000-99.99

Loop Update Time sec Word 15 0000-9999

Process Variable - PV Word 16

0000-9999

Error 2 Word 17

0000-100%

Control Output 2

Percent

Range Units

Range Units Range Units

Range Units

Range Units

Range

Range

Range Units

0000-9999 0000-9999

0000-100% Percent 0000-100% Percent

0000-100% Percent

00.00-99.99 sec

0000-9999

0000-9999

0000-100% Percent

Words 18 through 24 Reserved 3 1 2 3

Do not change while processor is operating. Do not change. These values are set by the PID function. Do not change Reserved bits.

E-27