Page 1 of DS/DD Bar Code Decoder to 2760-RB/PLC-5 Application Note

Manual · Allen-Bradley

DS/DD Bar Code Decoder to 2760-RB/PLC-5 Application Note

Manual12 pagesPDF 80 KB

Allen-Bradley application note on connecting a 2755-DS/DD bar code decoder to a 2760-RB interface module and PLC-5.

Download the PDF80 KB

Covers · 1 model

The models it covers

Summary

What is in it

An Allen-Bradley application note on interfacing the 2755-DS/DD bar code decoder to the 2760-RB flexible interface module in a 1771 rack with a PLC-5, using dumb terminal protocol over RS-232 and a 2760-SFC1 or -SFC2 protocol cartridge. It lists the hardware and software needed and related manuals, gives DIP switch settings for the PLC-5, chassis backplane and 2760-RB, the decoder and 2760-RB configuration screens, two example PLC block transfer programs and cable diagrams.

Its parts

  1. Overview
  2. Hardware Requirements
  3. Software Requirements
  4. Related Publications
  5. Configuration
  6. Running the Application

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Application note (publication 2755-2.54, September 1995) on connecting a 2755-DS or 2755-DD bar code decoder to a 2760-RB interface module over RS-232 dumb terminal protocol, using a 2760-SFC1 or -SFC2 protocol cartridge, with a PLC-5 in a 1771 rack. It gives the DIP switch settings, configuration screens, cable pinouts and example block transfer ladder programs.

Device
Flexible interface module for a 1771 rack with a PLC-5 processor p. 1
Mounting
Slot 0 of the 1771 chassis, next to the PLC p. 2
Protocol cartridge
2760-SFC1 or 2760-SFC2 p. 1
Ports
Serial ports 1 to 3 and a configuration port, 25-pin D male; the decoder uses Port 1 p. 2, 9
Serial settings
RS232, 9600 bps, 8 bits no parity, XON/XOFF and modem control disabled p. 6
Remote I/O
A 1771-ASB can also reach the 2760-RB over the backplane via Remote I/O p. 2
Bar code decoder
2755-DD or 2755-DS enhanced decoder p. 1
Port protocol
Dumb terminal unspecified protocol (screen 21) p. 6
2760-RB DIP switches
All off except SW-4 switch 3 on p. 3
Revision shown
2760-RB Series A Revision J screens p. 5
Message trailer
2 trailer bytes, hex a and d p. 6
Configuration terminal
PC with terminal emulator software, or a VT-100 type terminal p. 1
Programming tools
6200 software for the PLC-5 and a 1784-KT card or equivalent p. 1
Example rack
PLC-5, 2760-RB with SFC1 or SFC2 cartridge, 1771-P4 power supply p. 3

What this manual walks you through

  • Choosing the example program by 2760-RB revision and PLC-5 type p. 2
  • Setting the PLC-5, backplane and 2760-RB DIP switches p. 3
  • Configuring the 2755-DS/DD host communications screens p. 4
  • Resetting the 2760-RB and entering configuration screens 3, 21 and 11 p. 4, 5, 6
  • Block transfer ladder example for PLC-5/10, -15, -25 or 1771-ASB p. 7
  • Ladder example with IIN for a Revision H or later 2760-RB and PLC-5/20 to 5/50 p. 8
  • Wiring cables to the configuration port, Port 1 and the decoder p. 9

Good to know

  • The 2760-RB is reset to factory defaults (menu selection 90B) before the screens are entered. p. 4
  • The BRR bit is not a reliable sign of a read; the done bits show a completed transfer. p. 7
  • The block transfer read should come before the write. p. 8
  • The IIN rung applies only to a local rack, not remote rack use. p. 8
  • New Generation PLC-5 processors need the BT compatibility bit S26/4 set in program mode. p. 2

Questions this manual answers

Which slot does the 2760-RB go in?

Slot 0 of the 1771 chassis, next to the PLC-5. p. 2

Which protocol cartridge does the 2760-RB need to read a 2755 bar code decoder?

A 2760-SFC1 or 2760-SFC2 cartridge, using dumb terminal protocol over RS-232. p. 1

What serial settings connect a 2755-DS decoder to a 2760-RB?

RS232 at 9600 bps, 8 bits, no parity, with XON/XOFF and modem control disabled. p. 6

How do I reset a 2760-RB to factory defaults?

Choose main menu selection 90B from the configuration menu. p. 4

Can a 2760-RB work through a 1771-ASB remote I/O adapter?

Yes, a 1771-ASB can communicate with the 2760-RB over the chassis backplane via Remote I/O. p. 2

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Overview1
  2. Hardware Requirements1
  3. Software Requirements1
  4. Related Publications2
  5. Configuration2
  6. Running the Application4
  7. Back Cover12

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 31-3
  2. Pages 4 to 124-12

The file

Revision and size

Part no.2755-2.54
RevisionSeptember 1995
PublisherAllen-Bradley
Pages12
PDF80 KB
TextText from the PDF itself.
2755-2.54

The first pages · 3 of 12

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 12
Page 2
Page 2of 12
Page 3