For the Allen-Bradley 700-HS12BA1
Page 1
AB_Relay_700-HS12BA1_spec_D904
ALLEN BRADLEY TIMING RELAY
Configuration Details Product: 700-HS12BA1 Description: 700-HS General Purpose Square Base Timing Relay, On Delay Timer, 1.0 to 180 seconds, DPDT, 120V AC 50/60Hz
CONTROL RELAY DATA: Timing Fixed Mode Timing Mode
Adjustable Timer On Delay Timer
Contact Configuration Timing Range Coil Voltage
DPDT Contact Arrangement 1.0 to 180 seconds 120V AC 50/60Hz
CERTIFICATIONS AND APPROVALS: UR CSA CE
Bulletin 700-HS • Timing Relay (On-Delay or Off-Delay) • Rugged Blade Style Quick Connect Socket Mounting • 12 A, DPDT Contact Rating • 0.1 s…180 s Range Available As a Single Range or Fixed Timing (0.1 s…600 s)
Page 2
PRODUCT SELECTION:
Single Range Timing Relay with Blade Style Quick Connect/Solder Terminations Operating Mode Wiring Diagrams U.S./Canada International On- Delay
Socket
700- HN154 or 700- HN153
700- HN153
700- HN154 or 700- HN153
700- HN153
Off-Delay
Bulletin 700- HS DPDT 2- Pole 2 Form C Contacts
Socket
700–HS 2 2 A A1 a b c d e a Timer Type Code Description HS Square Base Adjustable Timing Relay b Mode Type Code Mode 1 On- Delay 2 Off-Delay
Page 3
c Number of Poles Code Description 2 2PDT d Timing Range Code A B C D E
Adjustable Time, Type HS 0.1…10 s 1.0…100 s 0.1…10 min 1.0…100 min 0.1…10 hr e Coil Voltage Code U12 U24 U120
Volts 12V AC/DC, 50/60 Hz 24V AC/DC, 50/60 Hz 120V AC/DC, 50/60 Hz
Fixed Timing Relays Description Bulletin 700- HSF fixed timing relays feature a plug-in square base with blade style terminations. Construction is the same as the Bulletin 700- HS timing relay except that the adjustment knob has been removed to help prevent unwanted tampering. The timing and output specifications are identical to those of the Bulletin 700- HS timing relay. Setting will be ±5% of the time ordered. Socket: Cat. No. 700- HN153 or 700- HN154
Bulletin 700HSF DPDT 2 Pole 2 Form C Contacts
700–HSF 2 2 025 S U24 a b c d e a Timer Type Code Description HSF Square Base Fixed Timing Relay b Mode Type Code Mode 1 On- Delay 2 Off-Delay f
Page 4
c Number of Poles Code Description 2 2PDT d Timing Value ¬ Code Value 001…999 The three digit code represents a numeric value with one decimal place. For example: code 001 is 0.1, code 025 is 2.5, and code 999 is 99.9 The acceptable range for each time unit is listed below: Seconds - 001…999 Minutes - 001…999 Hours - 001…100 e Timing Units ¬ Code S M H
Units Seconds Minutes Hours f Coil Voltage Code U12 U24 U120
Volts 12V AC/DC, 50/60 Hz 24V AC/DC, 50/60 Hz 120V AC/DC, 50/60 Hz
¬ Use both the Timing Value and Timing Units tables to properly select the desired fixed time relay. For example: 700-HSF22025SU24 selects a timer value of 2.5 seconds and 700-HSF22025MU24 selects a timer value of 2.5 minutes.
Page 5
Accessories Description
Pkg. Qty.
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting. Guarded Terminal Construction 11-blade socket for use with Bulletin 700- HB and - HJ relays and - HS timing relays. Order must be for 10 sockets or multiples of 10. Safe separation between coil and contacts.
10
700- HN153
Screw Terminal Base Socket, Panel or DIN Rail Mounting. Open Style Construction 11-blade for use with Bulletin 700- HB and - HJ relays and - HS timing relays. Order must be for 10 sockets or multiples of 10.
10
700- HN154
DIN (#3) Symmetrical Rail 35 mm x 7.5 mm x 1 m long Zinc-plated, yellow chromated
10
199- DR1
Retainer Clip for Cat. Nos. 700- HN153 and - HN154 Sockets with Bulletin 700- HS Timing Relays¬ Secures relay in socket. Order must be for 10 clips or multiples of 10.
10
700- HN160
Cat. No. 700- HN153
Cat. No. 700- HN154
Cat. No. 199- DR1
Sample Retainer Clips 10 Pre-printed identification tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays. Blank identification tags, contains 10 sheets of blank identification tags for 10 customer specialized printing. Each sheet contains 546 blank tags. Tags are peel- off with sticky backing for easy placement on relays.
¬ Bulletin 700-HS Timing Relay, Socket, and Retainer Clip Reference Chart
Relay Type Socket 700- HS
Retainer Clip
700- HN153 700- HN160 700- HN154
700- N40
700- N41
Page 6
Specifications Cat. No. 700HS…
Cat. No. 700-HSF…
Electrical Ratings Pilot Duty Rating † Rated Thermal Current (I th) Rated Insulation Voltage (Ui ) Contacts
Inductive
120V AC 240V AC Resistive 30V DC Permissible Coil Voltage Variation
Power Consumption ±10%
AC 24V AC 120V AC 240V AC DC
NEMA B300 12 A 250V IEC, 300V UL/CSA Make Break
Hp
Make
Break
Hp
30 A 3A 1/3 30 A 3A 15 A 1.5 A 1/2 15 A 1.5 A 12 A 12 A, 12 A 12 A 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC 2 VA 3 VA, 1.3 W
1/3 1/2, Design Specification/Test Requirements Dielectric Withstand Voltage
Pole-to- Pole, same circuit (VRMS) Pole-to- Pole, different circuits (VRMS) Contact-to- Coil (VRMS)
Electrical Life Operations Switching Frequency Operations Coil Voltages
1000V AC 2000V AC 2000V AC 100,000 minimum 360/hr See product selection
Mechanical Degree of Protection Mechanical Life Operations Switching Frequency Operations Timing Duty Cycle Repeat Accuracy (constant voltage and temperature)
Open Type (Guarded Terminal Sockets) 10 x 106 18,000/hr Continuous ±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)
Repeat Accuracy (variable voltage and temperature)
±15%
Fixed Time Setting Accuracy, Scale Tolerance Reset Time
High End of Range Low End of Range ON Delay OFF Delay
+5% –50% 100 ms 40 ms
Operating
–28…+65 °C (–18…+149 °F) –55…+85 °C (–67…+185 °F) 2000 m (6560 ft)
Environmental Temperature
Storage Altitude
±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s),
Page 7
SPECIFICATIONS CONTINUED: Construction Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets
Certifications
Standards
Molded High Dielectric Material Impact Resistant Dust Cover Silver Nickel In accordance with EN 50 005 8- or 11-Blade (On = 8, Off = 11) 700- HN153 - HN154 CSA Certified, File LR1234, UL Recognized, File E3125 Guide NLDX 2, Listed Ind. Cont. Eq. 700- HN153 and 700- HN154 sockets, CE Marked (per EU Low Voltage Directive 93/68 EEC) EN 61812, EN 60947-5-1, CSA 22.2, UL 508
¬ Performance Data, See Important 2, publication A115. † NEMA Rating Chart is on page 19 of publication 700- SG003B- EN- P.