For the Allen-Bradley 700-HX
Page 1
Installation Instructions
Digital Timing Relay Bulletin 700-HX
Description
This document provides the general specifications, installation procedures, and programming instructions for the Bulletin 700-HX digital timing relay. The Bulletin 700-HX digital timing relay is a programmable timing device. You can program it to display either elapsed or time remaining. The timing relay has a four-character liquid crystal display (LCD) for monitoring and display purposes. The four-digit display is back-lit for easy visibility and shows all the functions of the timer, including the mode, time setting, and the time elapsed or remaining. Refer to Figure 1 and Table 1. The timer can be programmed only after it is de-energized or removed from the socket. This device has a key protection (KP) feature that is indicated on the LCD. Key protection prevents the changing of mode, range, and direction, but the time setting can be adjusted. Use the protective cover to protect the timing relay and prevent inadvertent tampering. It is recommended that the timing relay be mounted in an enclosure door using the mounting bracket provided (Bulletin 700-HN130).
AT0
ATTENTION: The 700-HX digital timing relay contains a lithium battery to retain the program and timing setting when power is removed. When the battery is worn out, the device must be replaced. The timing program will be lost and operation will become unpredictable. One indication of a worn out battery is a dim display. This dimness indicates the useful life of the timing relay has expired, and it must be replaced. The life of the battery is estimated at 10 years when used at 25°C. At the end of this time, remove the lithium battery before discarding the timer. Do not incinerate, crush, unsolder, open, or dispose of the lithium battery in the general trash. Cut the battery leads and recycle at a battery disposal center. Table 1 Display Indicators
Figure 1 Nomenclature _ Operating indicator”
Reset indicator @ \
Present value
\
\
\
\ Allen-Bradley r ” \ ” \ Mode indicator ’
Displaya 1
Signal input indicator@ h Key protection W / r indicator I/ //
/
700-HX Output@ indicator
Required set time@RESET key 1 SELECT key
1
Power supply@ indicator Increment keys
- (A, B, C, D) ) See Table 1 for further description. 3 Required set time is the time setting in seconds; min. : sec.; hours : min.; or hours.
RUN RST
Reset Indicator
Reset key operated or pin 3 connected to pin 1
SIG
Signal Input Indicator
Signal applied with pin 4 connected to pin 1
OUT
Output Indicator
Output relay energized, form C contact @
Key Protection Indicator
Key program protection enabled @
Power Supply Indicator
Power applied, pin 2 & 7 rated voltage
KP
T
POW
1
Description
Location Operating Indicator
Digital timer program operating
@ The LCD is backlit when power is applied. @ Form C contact:
pin 8 (corn) to 5 normally closed pin 8 (corn) to 6 normally open
@ The timing mode and range cannot be changed. The time can be changed at any time.
Publication
700-5.7
Page 2
2
Digital Timing Relay
General Specifications
Specification
Rating l
Setting or repeat accuracy tolerances Minimum reset time requirements Allowable voltage range l
&0.03% of the setting or +50 ms, whichever is greater (started by a power supply) f0.03% of the setting or +20 ms, whichever is greater (started by a signal input)
0 Power source input is 500 ms minimum. 0 Signal source input is 20 ms (minimum) all ranges except 0.050 sec. scale which is 1 ms (minimum). 1 . 85 to 110%
Allowable operatinq temperature 1 l -10 to t55” C (avoid icing) Allowable storage temperature 1l -25 to t65” C (avoid icing) Allowable humiditv 1 l 35 to 85% (non-condensing) l AC model - Approx. 1.5 VA (at 240V 50 Hz.) l DC model - Approx. 0.8 W (at 24V DC) Power consumption l Allowable ripple DC - full wave Output
Maximum switching current/volts Contact ratina Minimum switch current Mechanical life of relav Electrical life Insulation resistance Dielectric strength Noise resistance Surge resistance malfunction durability Vibration mechanical durability Shock Weight
Installation Instructions malfunction durability mechanical durability
1 l SPDT (1 form C contact) l 5 Amps/240 VAC, 5 Amps/24 VDC l C300 pilot duty 1 l 10ma at 5 VDC I 0 10,000,000 operations
1 l 100.000 operations (5 A at 250 VAC res., 1800/hr) I l 100 M ohms min., 500V DC meqqer I l 2,000 VAC for 1 min. (between terminals to ground) l 2,000 VAC for 1 min. (between output contacts and control circuit) l 1,000 VAC for 1 min. (between open contacts) I l k2000V by noise simulator l +45OOV (1.2X50 us wave) l f500V:24 VDC voltage l l
10 to 55 Hz double amplitude 0.5 mm (0.02”) 10 to 55 Hz double amplitude 0.75 mm (0.03”)
l
100 m/s2 (about 1 OG) 500 m/s2 (about 50G)
l
Approx. 120 grams (4.2 oz.)
l
The Bulletin 700-HX is recommended for installation through a 45 mm2 (1.77 in2) square cutout in the enclosure door or operator’s station. Use the 700-HN130 panel adapter that is included with each device. Follow the procedure below to install the timing relay. 1. Place the 700-HX timing relay through the hole and slip the panel adapter over the back of the timer. 2. Push the timer and adapter together to get a snug fit, and tighten screws as necessary for a tighter fit. 3. Guide the wires through the optional 700-HN108 connector cover and solder wires to the proper socket tabs. See wiring recommendations on page 3. 4. Screw the cover of the optional 700-HN108 over the wires. The 700-HN132, optional protective cover, is clear for easy visibility and protects the buttons from accidental operation.
Publication 700-5.7
Page 3
Digital
Timing
Relay
Figure 2 Outline Dimensions and Insulation Optional 700-HN132 Clear Shield Protective Cover
Optional 700-HNl OO 700-HN125 8 pin sockets
700-HN130 Panel Adaptor (included) /
700-HX Digital Timer
3
1 1.26 I321
I
Optional 700-HN108 liv s/ Panel w
Wiring Recommendation Use three-wire shielded cable, 3-50 ft. (l-l 5 meters): Signal (pin 4). Reset (pin 3) and Grout Id (pin 1). Maximum length is 50 ft. (15 meters).
A t 0
Use stranded power wires: pins 2 & 7 Relay Output 6 (N.O.), 5 (N.C.), 8 (Corn.)
ATTENTION: l l l l l
Do not remove timer from housing. Such action invalidates product warranty. Remove power before changing the mode. Time setting can be changed with power on. (Use clear shield 700-HN132 to prevent tampering). The AC/DC type timer uses a transformerless supply. When two or more timers are connected together, use pin 1 as ground. Figure 3 Typical Wiring Diagrams International
U.S./Canada Mode1,3,5,7
Mode 1,3,5,7
/
/ 12 0
7
1
Mode 2
7
22 0
24 0
8
]
Mode4.8
1
14 0
Mode 2
1
1
8
Key
(I) Input Power (terminals 2 (Al) and 7 (A2) )
(TC) Timed Contacts SPDT
Power to terminals 2 (Al) and 7 (A2) must be applied continuously. (Time delay and output contact can reset immediately.)
(1 form C contact) (terminals 5 (22) N.C., 6 (24) N.O., and 8 (21) Corn.)
l l
Mode 6 power interruption. (Continues timing when returned.)
Note: International Socket Terminal Numbers are shown in ( ).
A l
(S) Start Signal (terminals 4 (12) and 1 (11) ) l
This signal can be either momentary or maintained.
(R) Reset Signal (terminals 3 (14) and1 (11) ) l l l
Reset signal not required for normal operations. This is used to reset the timer without the loss of power. Reset signal will override the start signal.
ATTENTION: Do not connect inductive loads or voltages higher than 30V to the start or reset gate inputs pins 3 or 4.
Publication 700-5.7
Page 4
Digital Timing Relay
4
Contact Signal Input Connection
Solid-state Signal Input Connection
Solid-state Circuit Connection
For reliability use external contacts or reeds that are designed for SVDC low power switching. (700-HC54,700-R, or 700-CPR). The SVDC is provided internally by the Timing Relay.
Use an open collector transistor with maximum leakage current 25 I-LA. A residual voltage of 2V maximum with transistor on is considered low. 3V or higher is considered a high signal.
A 2V maximum voltage, on the gate pin 4 (12) or reset pin 3 (14) is low. With 3V or higher, the signal is high (or “On”) signal.
I
,
7to30 I VDC In 1
Publication 700-5.7
Page 5
I
I
I
5
Digital Timing Relay
A
Programming Instructions t 0
ATTENTION: Program timer only after removing it from socket or with no power applied to the 700-HX (pins 2 (Al) & 7 (A2)).
To program the Bulletin 700-HX Digital Timing Relay, follow the procedure below. 1. Disable Key Protect If Key Protect (KP) is displayed the function is enabled. Press Select and any increment key together to disable the key protection feature. 2. Mode Selection Press the Select key until the mode indicator (1-8) is flashing (on the LCD display). Press any increment key (A, B, C, or D) and observe the mode number using the following code: 1 - Power-up on-delay 2 - Signaled off-delay 3 - One shot (interval delay) 4 - Flicker (repeat cycle) CL = Lff)
l l l l l l l l
5 - Signaled on-delay 6 - On-delay (electronic reset) 7 - On-delay (integration) 8 - Unequal repeat cycle CL
# Lff)
Press the Select key for the next selection. 3. Range Selection Press any increment key to select the range. Range selection includes: 0.050-9.999 sec. 0.05-99.99 sec. 0.1-999.9 set l-9999 sec.
l l l l l l l l
O:Ol-99:99 min.:sec. O:Ol-99:99 hrs.:min. l-9999 hrs. Press the Select key for the next selection.
4. Timing Direction Selection For Direction, toggle any increment key and observe the “Up” or “Down” counting direction on the LCD. The “Up” direction displays the time elapsed by starting at zero and then increasing to the time set. The “Down” direction displays the time remaining by starting at the set time and decreasing to zero. Press the Select key to set the direction required and for the next selection. 5. Key Protection
Selection
For Key Protection (tamper lockout) toggle this feature On or Off by pressing any increment key A, B, C, or D. “KP” in the display indicates that the feature is activated. Press the Select key for the next selection. 6. Time Setting Set the Time value. To do this, press the four increment keys (A, B, C, and D). The key farthest right (D) controls the least significant digit on the LCD display. 7. End Programming Press Reset key. The timer is now programmed.
A
ATTENTION: Do not use this timing relay in direct sunlight. the LCD to dim and shorten the timer’s useful life.
High temperatures will cause
T 0
Publication 700-5.7
Page 6
Digital
6
Timing
Table 2 Programming Quick Reference:
Relay
Bulletin 7WHX
Operational Overview
To program timing relay, the device must be de-energized or removed from the socket. To disable Key Protection “KP” to begin programmina, press Select and anv increment key simultaneously Exolanation
Setting Timer To Set Mode Mode l-7 1 - Power On 2 - Sig. Off 3 - One Shot 4 - Flicker
.
5 - Sig. On 6 - Rst. On 7 - Integration 8 - See Table 3.
Press Select until the mode indicating number flashes. Press any increment key (A, 6, C, or D) until the mode number needed is displayed. )
Mode 2 . .. .. .. . +
Mode 1 -
Mode81
Press Select. “Range” will appear and digits below will flash. Press any increment key (A, B, C, or D) to obtain the needed range.
To Set Range 0.000s to 9999h o.ooosoo.oos000.0s 0000s OOOOh r+ 00min:OOs ----) OOh:OOminTo Set Display of Time Elapsed “Down” or time remaining or “Up” time elapsed.
Press Select to observe Down or Up. Press any increment key (A, B, C, or D) to toggle. Up Down ~ Press Select to Key Protection and observe. KP On or Off will flash. Press any increment key (A, B, C, or D) to toggle.
To Set Key Protection On or Off
-On--,
-
Press Select, and the set time will appear. Press the four increment keys (A, B, C, and D) to set the “required time setting” on the display. Key A is the most significant, and Key D is the least significant. Press Reset.
To Set the Time To Complete Setting Table 3 Programming Quick Reference:
Off
Bulletin 700-HX Operational Overview for Unequal Repeat Cycle (Mode 8)
To program timing relay, the device must be de-energized or removed from the socket. To disable Key Protection “KP” to begin programming, press Select and any increment key simultaneously . Explanation
Setting Timer Mode 8
Press Select until the mode indicating number flashes. Press any increment key (A, B, C, or D) until the mode number is on 8. Mode87 Mode 1 Mode 2 . .. . . ... -
To Set “Off” Time Range
Press Select “Off ,” and “Range” will appear and digits below will flash. Press any increment key (A, B, C, or D) to obtain the needed range.
To Set Mode
- o.ooos00min:OOs - oo.oosooo.os0000s 00h:OOmin --) OOOOh
To Set “Off” Time Preset Mode
Press Select. Set time by pressing each increment key (A, B, C, or D). g I_ 0 1 2 . . .. .. .. -
To Set “On” Time Range
Press Select “On,” and “Range” will appear and digits below will flash. Press any increment key (A, B, C, or D) to obtain the needed range. o.ooosoo.oos000.0s 0000s 00min:OOs ---) 00h:OOmin --) OOOOh
To Set “On” Time Preset Mode
To Set Display to “Down” or “Up”
/
Press Select. Set time by pressing each increment key (A, B, C, or D) to set “On” time. 0 1 2 . . .. ..*. g Press Select. Press any increment key (A, B, C, or D).
-+
Up -
Down ~
To Set Key Protect Selection Mode
Press Select. Press any increment key (A, B, C, or D) . -+ OnOff __
To Complete Setting
Press Reset key.
To operate output contacts, energize or insert timer into the socket.
Publication 700-5.7
Page 7
Digital
D
Timing
7
Relay
Timing Charts I No.
Mode
Input/Output
1
Power On-delay
Power
(2-7)
Start signal (gate) (l-4) Reset (l-3) output
Explanation
Time Chart
Power On-delay (Mode 1). Input power starts the time delay. l l
Start signal - Holds time event until released. Reset signal - Resets display when applied. Timing starts when released.
(6-N
Set timer J up Display @ \ 2
D
Signal Off -delay
0
Set timer Down o
Power
(2-7)
Start signal (start) (f-4 Reset (l-3) output
Signal Off-delay (Mode 2). Input power must be applied continuously. l
(6-S)
Set timer J up Display @ l
0
Start signal - Application operates the output relay. Release (off) starts the timing event. Input again, operates relay (if timed out) and release (off) starts the timing event again. Reset signal - Resets display when applied. Release has no effect. Start signal (off) needed for timing event.
Set timer Down o
P I*
3
Interval (One Shot)
Power
(2-7)
Start signal (start) (l-4 Reset (l-3) output
One Shot (Mode 3). Input power must be applied continuously. l
(6-B)
l
Set timer 1 up Display @
0
Start signal - Momentary input, operates output relay and also start timing event. Release has no effect. Reset signal - Resets display and releases output relay (if energized) when applied. Release has no effect.
Set timer Down o b 4
Flicker (Repeat Cycle)
Power
(2-7)
Start signal (gate) (f-4) Reset (l-3) output
Flicker (Mode 4). Input power starts the equal On and Off cycling. l l
(6-3)
Set timer 5 up 0 Display @
Start signal - Holds either time event until released. Reset signal - Resets display and releases output relay (if energized) when applied. The equal On and Off cycling begins with the output relay de-energized when released.
Set timer Down o @ Display shows either time elapsed (referred to here as “set timer up”) or time remaining (“set timer down”).
Publication 700-5.7
Page 8
a
Digital
Timing
Relay
Timing Charts (cont.) No.
Mode
Input/Output
5
Signal On-delay
‘ower
Signal On-delay (Mode 5). Input power must be applied continuously.
(2-7)
Start signal start) (f-4) Reset (l-3) output
Explanation
Time Chart l
(6-8)
l
Set timer : up Display @ ! 6
On-delay (Electrical Reset)
0
Reset On-delay (Mode 6). Power is applied continuously. However, if there is a loss of power, time is held until power is reapplied.
(2-7)
Start signal [gate) (f-4) Reset (l-3) output l
(6-8)
l
Set timer J up 0 Display o
On-delay (Integration)
Reset signal - Resets the display and the output relay (if energized) when power is applied. Start signal needed to start timing event.
Set timer Down o
Power
!
Start signal - Momentary input, starts the timing event. Release has no effect. Relay operates at end of the event.
Start signal - Holds timed event until released. Reset signal - Resets the display and the relay (if energized) when applied. Starts timing event when released.
Set timer Down o
Power (2-7) Start signal (Integration) (l-4 Reset (l-3) output
Integration (Mode 7). Input power must be applied continuously. l
(6-8)
Set timer J up Display @ l
0
Start signal - Input starts time delay but continues only as long as the signal is maintained. Release does not reset. Delay continues (integrates) with input. Reset signal -Resets the display and the relay (if energized) when applied. Start signal needed to begin integration.
Set timer Down o Repeat (Unequal)
Power
(2-7)
Start signal (gate) (f-4) Reset (l-3) output
Unequal Repeat Cycle (Mode 8). Input power starts unequal cycling. l l
(6-8)
Set timer J up 0 Display @
Start signal - Holds On or Off cycling event until released. Reset signal - Resets the display and the relay (if energized) when applied. Unequal cycling begins again with the output relay de-energized when released.
Set timer Down o o
!!!!!
Display shows either time elapsed (referred to here as “set timer up”) or time remaining (“set timer down”).
RN#~wMI
Automation
41052-086-02(C)