Page 211

Wiring with Pico GFX-70

4-101

Scan time Tc Scan time Tc determines the duration of the interval in which the function block is called by the operating system for processing. The value range is between 0 and 6553.5 s. If the value 0 is set, the cycle time of the device is the pause time between the function block calls.

IMPORTANT

IMPORTANT

The device cycle time varies according to the length of the program. With a scan time of 0 s, this may cause an irregular control response.

Use the Set cycle time function block (see Set Cycle Time on page 4-137) to keep the cycle time of the device constant.

Manual Mode of the PID Controller A value must be present at the >MV input to set the manipulated variable directly. If the coil DC..SE is activated, the value at >MV is transferred as manipulated variable QV>. This value is present for as long as the DC..SE coil is activated or the value at the >MV input is changed. If coil DC..SE is deactivated, the control algorithm is reactivated. IMPORTANT

IMPORTANT

Extreme changes in the manipulated variable can occur when the manual manipulated variable is transferred or deactivated.

If the function block is running in UNI (unipolar) mode, a negative signed manipulated variable value will be output.

Signal Smoothing Filter Pico GFX-70 provides 32 signal smoothing filters FT01 to FT32. The function block allows you to smooth noisy input signals.

Wiring a Signal Smoothing Filter You can integrate a signal smoothing filter into your circuit as a coil.

Publication 1760-UM002B-EN-P - March 2005

Page 212

4-102

Wiring with Pico GFX-70

Figure 4.42 Pico GFX-70 circuit diagram with smoothing function block M 48----------------------------[ FT17EN

Parameter Display and Parameter Set for the FT Function Block FT17

+

>I1 >TG >KP QV>

FT17

FT PT1 signal smoothing filter function block, number 17

+

Appears in the parameter display

>I1

Input value

>TG

Recovery time

>KP

Proportional gain

QV>

Output value, smoothed

IMPORTANT

The recovery time Tg is the time in which the output value is calculated. The recovery time Tg must be set so that it is an integer multiple of the cycle time or controller scan time Tc.

Inputs The function block inputs >I1, >I2 and >KP can have the following operands: • Constants • Markers MD, MW, MB • Analog inputs IA01 to IA04 – IA01: terminal I7 – IA02: terminal I8 – IA03: terminal I11 – IA04: terminal I12 • Analog output QA01 • Actual value … QV> of another function block

Output The function block output QV> can be assigned the following operands: • Markers MD, MW, MB • Analog output QA01

Publication 1760-UM002B-EN-P - March 2005

Page 213

Wiring with Pico GFX-70

4-103

Value Range for Inputs and Outputs

Value range

Resolution/unit

>I1

Input value of the function block

-32 768 to +32767

>TG

Recovery time Tg

0 to 65535 in 100/ms

>KP

Proportional gain Kp

0 to 65535 in -- /%

QV>

Output value

-32 768 to +32767

Example:

Value at input

Value processed in the function block.

>TG

Recovery time Tg

250

25 s

>KP

Proportional gain Kp

1500

15

Displaying the Parameter Set in the PARAMETERS Menu • + Access enabled • - Access disabled

Coil FT01EN to FT32EN, function block enable

Memory Requirement of the FT Function Block The FT function block requires 56 bytes of memory plus 4 bytes per constant on the function block input.

Function of the Signal Smoothing Filter Function Block

IMPORTANT

The signal smoothing filter must be enabled so that it can work. Coil FT..EN is active. If coil FT..EN is not active, the entire function block is deactivated and reset. The output value is set to zero.

If the function block is called for the first time, the output value is initialized with the input value when the device is started or after a reset. This speeds up the startup behavior of the function block.

Publication 1760-UM002B-EN-P - March 2005

Page 214

4-104

Wiring with Pico GFX-70

IMPORTANT

The function block updates the output value every time recovery time Tg expires.

The function block operates according to the following equation: Y(t) = [Ta/Tg] x [Kp x x(t) - Y(t-1)] Y(t) = calculated output value for scan time t = Scan time Ta Tg = Recovery time Kp = proportional gain x(t) = Actual value with scan time t Y(t-1) = Output value with scan time t - 1

Scan time: Scan time Ta depends on the set recovery time value.

Recovery time Tg

Scan time Ta

0.1 s to 1 s

10 ms

1 s to 6553 s

Tg x 0.01

GET, Fetch a Value from the Network The function block allows you to selectively read (get) a 32-bit value from the network. The GET function block fetches data which another station has made available on the Pico-Link network with a PUT function block.

Publication 1760-UM002B-EN-P - March 2005

Page 215

Wiring with Pico GFX-70

4-105

Figure 4.43 Pico GFX-70 circuit diagram with GET function block GT01Q1---------------------------[ DB16T

Parameter display and parameter set for the GET function block: GT01 02 20

+

QV>

GT01

GET function block (fetch a value from the network), number 01

02

Station number from which the value is sent. Possible station number: 01 to 08

20

Send function block (PT 20) of the sending station. Possible function block number: 01 to 32

+

Appears in the parameter display

QV>

Actual value from the network

Output The function block output QV> can be assigned the following operands: • Markers MD, MW, MB • Analog output QA01

Contacts GT01Q1 to GT32Q1 Contact (make contact) GT..Q1 switches to status 1 if a new value transferred on the Pico-Link network is present.

Memory Requirement of the GET Function Block The GET function block requires 28 bytes of memory.

GET Diagnostics The GET function block only functions when the Pico-Link network is functioning correctly (see Signs of Life of the Individual Stations and Diagnostics on page 6-12).

Publication 1760-UM002B-EN-P - March 2005

Page 216

4-106

Wiring with Pico GFX-70

Function of the GET Function Block Figure 4.44 Signal diagram of the GET function block

1

2

1: GT..Q1 2: value on GT..QV>

IMPORTANT

The GET function blocks are assigned the value 0 when the power supply is switched on.

Seven-Day Time Switch Pico GFX-70 is equipped with a real-time clock which you can use in the circuit diagram as a 7-day time switch and a year time switch.

IMPORTANT

The procedure for setting the time is described under Setting Date, Time and Daylight Savings Time on page 7-11.

Pico GFX-70 provides 32 seven-day time switches HW01 to HW32 for a total of 128 switching times. Each time switch has four channels which you can use to set four on and off times. The channels are set via the parameter display. The time is backed up in the event of a power failure and continues to run, although the time switch relays will no longer switch. The contacts are kept open when de-energized. Refer to General on page A-1 for information on the buffer time.

Wiring of a 7-Day Time Switch A 7-day time switch is integrated into the circuit diagram as a contact.

Publication 1760-UM002B-EN-P - March 2005

Page 217

Wiring with Pico GFX-70

4-107

Figure 4.45 Pico GFX-70 circuit diagram with 7-day time switch HW14Q1---------------------------[ Q 01

Parameter display and parameter set for the 7-day time switch HW: HW14

A

+

>DY1 >DY2

HW14

7-day time switch function block number 14

A

Time switch channel A

+

Appears in the parameter display

>DY1

Day 1

>DY2

Day 2

>ON

On time

>OFF

Off time

>ON >OFF

Channels 4 channels are available per time switch, channels A, B, C and D. These channels all act on the contact of the 7-day time switch.

Day 1 and Day 2 Either the time period acts from day 1 to day 2, e.g. Monday to Friday, or for one day only. Monday = MO, Tuesday = TU, Wednesday = WE, Thursday = TH, Friday = FR, Saturday = SA, Sunday = SU,

Time 00:00 to 23:59

Displaying the Parameter Set in the PARAMETERS Menu • + Access enabled • - Access disabled

Contacts HW01Q1 to HW32Q1

Publication 1760-UM002B-EN-P - March 2005

Page 218

4-108

Wiring with Pico GFX-70

Memory Requirement of the 7-Day Time Switch The 7-day time switch function block requires 68 bytes of memory plus 4 bytes per channel used.

Function of the 7-Day Time Switch The switching points are defined according to the parameters entered. MO to FR: on the weekdays Mo, Tu, We, Th, Fr ON 10:00, OFF 18:00: on and off switching times for the individual days of the week. MO: every Monday ON 10:00: switch on time SA: every Saturday OFF 18:00: switch off time Switching on working days

Time switch HW01 switches on Monday to Friday between 6:30 and 9:30 and between 17:00 and 22:30.

HW01 A

HW01 B >DY1 MO

>DY2 FR

>DY2 FR

>ON

>ON

06:30

>OFF 09:30

Publication 1760-UM002B-EN-P - March 2005

+

>DY1 MO

17:00

>OFF 22:30

+

Page 219

Wiring with Pico GFX-70

4-109

Switching at the weekend

Time switch HW02 switches on at 16:00 on Friday and switches off at 6:00 on Monday.

HW02 A

+

HW02 B

>DY1 FR

>DY1 MO

>DY2

>DY2

>ON

16:00

+

>ON

>OFF

>OFF 06:00

Figure 4.46 Signal diagram of “weekend”

Overnight switching

Time switch HW03 switches on overnight at 22:00 Monday and switches off at 6:00 on Tuesday.

HW03 D

+

>DY1 MO >DY2 >ON

22:00

>OFF 06:00

Figure 4.47 Signal diagram for night switching

IMPORTANT

If the Off time is before the On time, Pico GFX-70 will switch off on the following day.

Publication 1760-UM002B-EN-P - March 2005

Page 220

4-110

Wiring with Pico GFX-70

Time overlaps

The time settings of a time switch overlap. The clock switches on at 16:00 on Monday, whereas on Tuesday and Wednesday it switches on at 10:00. On Monday to Wednesday the switching-off time is 22:00.

HW04 A

+

HW04 B

>DY1 MO

>DY1 TU

>DY2 WE

>DY2 WE

>ON

>ON

16:00

>OFF 22:00

+

10:00

>OFF 00:00

Figure 4.48 Signal diagram of overlaps

IMPORTANT

Switch-on and switch-off times are always based on the channel which switches first.

Response in the event of a power failure

The power is removed between 15:00 and 17:00. The relay drops out and remains off, even after the power returns, since the first switching-off time was at 16:00.

HW05 A

+

HW05 B

>DY1 MO

>DY1 MO

>DY2 SU

>DY2 SU

>OFF 16:00

>ON

+

12:00

>OFF 18:00

IMPORTANT

Publication 1760-UM002B-EN-P - March 2005

When switched on, Pico GFX-70 always updates the switching state on the basis of all the available switching time settings.