Page 323

Pico-Link and Point-to-Point Serial Connections

6-17

Establishing a Serial Interface connection to a Pico-Link station. Figure 6.6 Pico-Link operation and Serial Interface connections.

GFX-70

GFX-70

GFX-70

GFX-70

A Serial Interface connection can be established with a Pico-Link station. The same conditions apply here as with operation without Pico-Link.

Data accesses via Serial Interface The following data access operations are possible from the active station to the remote station:

Active station, read

Remote station

Inputs

1I01 to 1I16

I01 to I16

Inputs of local expansion unit

1R1 to 1R16

R01 to R16

Outputs

1Q01 to 1Q08

Q01 to Q08

Outputs of local expansion unit

1S01 to 1S08

S01 to S08

Pico-Link diagnostics bits

1ID01 to 1ID08

ID01 to ID08

Analog inputs

1IA01 to 1IA04

IA01 to IA04

Analog output

1QA01

QA01

Write/read accesses in the marker range Publication 1760-UM002B-EN-P - March 2005

Page 324

6-18

Pico-Link and Point-to-Point Serial Connections

Active station

Remote station

1 MD01

MD01

1 MW01 1 MB01

1MW02 1MB02

1MB03

MW01 1MB04

MB01

MW02 MB02

1 M01 to 1 M32

M01 to M32

1 MD02

MD02

1 MW03 1 MB05

MW03

1MW04 1 MB06

1 MB07

1 MB08

MB05

MB06

M33 to M64

1 MD03

MD03

1 MB09

1 MW06 1 MB10

1 MB11

MW05 1 MB12

MB09

MB10

M65 to M96

1 MD04

MD04 1 MW08

MB07

MB08

MW06

1 M65 to 1 M96 1 MW07

MB04

MW04

1 M33 to 1 M64 1 MW05

MB03

MW07

MB11

MB12

MW08

....

..... .... 1 MD20

MD20

1 MW39 1 MB77

MW39

1 MW40 1 MB78

1 MB79

1 MB80

MB77

MW40 MB78

MB79

MB80

The normal rules for addressing the markers apply.

IMPORTANT

Ensure a clear separation of the write range of the two stations. The active station should write different markers to the remote station. Otherwise the markers in the last write operation will be overwritten.

Configuration of the Serial Interface The active station must have the following settings in order for the Serial Interface connection to be functional: • Baud rate, • Serial Interface (active), • Remote marker range (data exchange range).

Publication 1760-UM002B-EN-P - March 2005

Page 325

Pico-Link and Point-to-Point Serial Connections

6-19

Baud rate Serial Interface The baud rate can be 9600 baud or 19200 baud.

BAUDRATE:19200B

IMPORTANT

Serial Interface REMOTE MARKER...

In normal applications, select the higher baud rate of 19200 baud. The baud rate of 9600 baud should only be selected if the connection is frequently faulty. Factory setting: 9600 baud

Activating Serial Interface Serial Interface must be activated in order for it to function. Factory setting: not active

BAUDRATE:19200B

The tick on the Serial Interface menu item indicates that Serial Interface is active.

Serial Interface ✓ REMOTE MARKER...

Remote markers, Serial Interface data exchange range

IMPORTANT

The REMOTE MARKER.. menu only opens if a tick is displayed next to Serial Interface.

Select the REMOTE MARKER... menu option. Here you can determine, select and modify the data exchange range. In the example the READ range was selected with the marker double words MD11 to MD15. READ: 1MD11 → 1MD015 WRITE:

The WRITE range consists of the marker double words MD16 to MD18.

1MD16 → 1MD18

The entire data exchange range available is the marker range MD01 to MD20 of the remote station. The active station accesses these markers with 1MD*. The * indicates the number of the marker concerned. The smallest possible unit for defining a marker range is an MD marker double word.

Publication 1760-UM002B-EN-P - March 2005

Page 326

6-20

Pico-Link and Point-to-Point Serial Connections

Example: The read range of the active station is 1MD02. The write range of the active station is 1MD03. The read range of the remote station is therefore MD03. The write range of the remote station is MD02.

Operating principle of the Serial Interface connection The active station at the Serial Interface must be in RUN mode. Data can only be exchanged with the active station in RUN mode. The remote station must be in RUN or STOP mode. The active station scans the remote station. The entire READ marker range is transferred as a string. The entire WRITE marker range is transferred as a string.

IMPORTANT

Data consistency The data is located in the image range (data range storing the marker states) of the active station (1MD..) as well as in the image range of the remote station (MD..) Each station writes data to its own image range asynchronously for data communication. As the serial interface transfers large data volumes slower than the devices overwrite the image ranges, the following applies: one marker double word 1MD.., MD.. is consistent. Within a program cycle, a marker double word that is overwritten via Serial Interface is not constant. The data via the Serial Interface is written to the status image over the course of the program cycle. This means that a different marker value can be present at the start of the program cycle to after the write operation via Serial Interface.

Sign of life detection Serial Interface, diagnostics contact ID09 To determine the proper functioning of the Serial Interface connection, the diagnostics contact ID09 is provided on the active station of the Serial Interface connection. Publication 1760-UM002B-EN-P - March 2005

Page 327

Pico-Link and Point-to-Point Serial Connections

Status of diagnostics contact ID09

Status of the connection

“0”

Serial Interface connection operating correctly or

6-21 no Serial Interface connection selected. “1”

Serial Interface connection not functioning, faulty

The time required to detect that the Serial Interface is not working properly depends on the baud rate selected and the event concerned.

Baud rate

Time required for detection of faulty Serial Interface connection. CRC error (data content incorrect)

No response, no hardware connection, remote station not in operation

9600 Baud

250 ms

1.5 s

19200 Baud

120 ms

0.8 s

ATTENTION

If the states of the inputs, outputs or data are required by a station without fail, the respective diagnostics contact should be evaluated and the information applied in accordance with its respective application. If the respective diagnostics contacts are not evaluated, it may cause faults in your application.

Publication 1760-UM002B-EN-P - March 2005

Page 328

6-22

Pico-Link and Point-to-Point Serial Connections

Publication 1760-UM002B-EN-P - March 2005