Spec sheet · Andover Controls
Andover Controls EMX150 Spec Sheet
Spec sheet4 pagesPDF 54 KB
All 4 pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Andover Controls data sheet for the Infinity EMX 150, EMX 151, EMX 155, EMX 156 and EMX 160 expansion modules, which add input and output points to Andover Infinet controllers. It describes each module, how the modules are powered, installed and programmed, and gives the electrical, mechanical and per-module specifications, with a dimension drawing of the EMX 150.
- Module type
- EMX 150: expansion module with 2 analog outputs, each 0-20 mA or 0-20 VDC, for Infinet controllers p. 1, 3
- Load impedance
- EMX 150: 0-20 mA into 750 ohms maximum; 0-20 VDC into 4,000 ohms minimum p. 3
- Resolution
- EMX 150: 0.1 mA or 0.1 VDC p. 3
- Overrides
- EMX 150: 2-position switch plus potentiometer on each output, no software feedback p. 1, 3
- Power consumption
- EMX 150: 55 mA p. 3
- Dimensions
- EMX 150: 6.13"W x 4.88"H x 1.52"D (155W x 124H x 39D)mm p. 3
- Power
- Up to two modules powered from the Infinet controller (only 1 EMX 151); more need an external 24 VDC supply p. 3
- Controllers
- SCX 920, LCX 810, TCX 850, TCX (IDX) 851, TCX 853, TCX 855, ACX 700 p. 1
- Operating environment
- 32 to 120°F (0 to 49°C), 10 to 95% RH non-condensing p. 3
- Enclosure
- UL open class sheet metal, IP 10; panel mounted with two sheet metal screws p. 2, 3
- Connections
- 2-position external power connector; removable two-piece terminal blocks (EMX 156 has screw terminals) p. 3
- Communication
- Through the expansion serial port of the local Infinet controller p. 3
- Other modules covered
- EMX 151: 2 12-bit analog outputs, 0-10 VDC or 0-20 mA; EMX 155: 2 Form C relays, 5A, 24 VAC / VDC; EMX 156: 2 solid state outputs, 120/240 VAC; EMX 160: 8 dry contact inputs, counters to 140 Hz p. 1, 2, 4
- Programming
- Points assigned in Andover's Plain English language and used like the controller's built-in I/O p. 2
What this sheet walks you through
- Plugging a module into the controller's expansion port and panel mounting it p. 2
- Programming expansion points in Plain English p. 2
- Checking the EMX 150 dimensions and terminal layout p. 2
- Comparing the specifications of the EMX 151, 155, 156 and 160 p. 3, 4
Good to know
- Only one EMX 151 can be powered from the Infinet controller. p. 3
- EMX 156: DC loads are not permitted. p. 4
- EMX 160: all inputs must be dry contacts. p. 4
- The size differs between the EMX modules. p. 2
- The spec sheet states agency listings UL/CUL 916, FCC and CE. p. 3
Questions this sheet answers
What output range does the EMX 150 have?
Two analog outputs, each 0-20 mA or 0-20 VDC, with 0.1 mA or 0.1 VDC resolution. p. 3
How many EMX modules can an Infinet controller power?
Up to two (only one EMX 151). Additional modules need an external 24 VDC supply. p. 3
Does the EMX 150 have a manual override?
Yes. Each output has an override switch and a potentiometer for local control, with no software feedback. p. 1, 3
What load can the EMX 150 outputs drive?
In current mode, 0-20 mA into at most 750 ohms; in voltage mode, 0-20 VDC into at least 4,000 ohms. p. 3
How much current does the EMX 150 draw?
The EMX 150 power consumption is 55 mA. p. 3
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
Infinity EMX 150, EMX 151, EMX 155, EMX 156, EMX 160 Expansion Modules
The Andover Controls Infinity family of expansion modules provides a convenient and cost effective
F E A T U R E S
means to add input and output points to Andover’s Infinet distributed application controllers.
- Cost Effective I/O Expansion to Meet Additional Point
Up to two modules can be powered directly from any of these Infinet controllers: the SCX 920, LCX
Count Needs
810, TCX 850, TCX (IDX) 851, TCX 853, TCX 855, and the ACX 700. Additional modules can be
- Additional Points Provide
added by providing power from an external 24 VDC supply. Consult the Infinity Expansion Module
Seamless Controller
Configuration Guide for more specific information on the use of expansion modules.
Performance
EMX150
The EMX 150 contains two analog outputs configurable for either 0 - 20 VDC or 0 - 20 mA operation. Each output contains an override switch and potentiometer for local control.
EMX151
The EMX 151 contains 2 high-resolution, 12-bit analog outputs configurable for either 0-10 VDC or 0-20 mA operation. No override switches are provided.
EMX155
The EMX 155 provides two Form C relay outputs rated for 24 VAC/VDC operation. Each relay can be used for on/off control of motors and lighting, or can be used for pulse width modulation control, with 0.1 second resolution. Each output contains an override switch for manual operation, with software feedback of the switch position.
EMX156
The EMX 156 provides 2 digital outputs rated for 120/240 VAC operation. Each output is a field replaceable, solid state device that can be used for control of motors and lighting, or can be used for pulse width modulation control, with 0.1 second resolution. Each output has 4000 V RMS isolation, and has a maximum surge current of 80 amps. Each output contains an override switch for manual operation, with software feedback of the switch position.
- Modular Design for Easy Plug-in Installation
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
I n f i n i t y E M X 1 5 0 , E M X 1 5 1 , E M X 1 5 5 , E M X 1 5 6 , E M X 1 6 0 Expansion Modules
EMX160
The EMX 160 contains 8 digital inputs designed for dry contact signals. In addition, each input can be configured to accept pulses up to 140 per second.
PROGRAMMING
Expansion module points are treated in the same manner as the built-in I/O of each Infinet controller. Once expansion points are assigned using Andover’s Plain English ™ programming language, they are automatically added to operator input and output summaries, and can be used unrestricted in programs, reports, and alarms.
INSTALLATION
Expansion modules are designed to be plugged into the expansion port found at the bottom of each Infinet controller. The expansion module enclosure is intended for panel mounting, using two sheet metal screws.
6.13" 156.0mm PLUG TO PREVIOUS EMX OR CONTROLLER
BOARD 1 2EMX150 OVERRIDE A AUTOOUTPUT ARET IMANVOUTPUT TERMINALSB4.88" 124.0mmAMANUAL ADJ POTSOUTPUT BRET I VB24vDC CLASS II+ -POWER SOCKETSUPPLY JUMPERMODULEDEPTH 1.52" (39mm)SOCKET FOR NEXT EMX
Note: Size differs for all EMX Modules
EMX 150 Dimensional Diagram
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
SPECIFICATIONS
- ELECTRICAL Power
- Up to two modules can be powered directly from the Infinet controller (Only 1 EMX 151). Additional modules can be powered with an external 24 VDC power supply.
MECHANICAL Operating Environment:
32 to 120°F (0 to 49°C), 10 to 95% RH (non-condensing)
- Enclosure Type
- UL open class sheet metal, IP 10
COMMUNICATIONS Communication Interface:
Through expansion serial port of the local Infinet controller.
CONNECTIONS
- External Power Connector
- 2-position connector
- I/O Connectors
- Removable two-piece terminal blocks. (EMX 156 has screw terminals).
GENERAL
EMX Modules/Infinet Controller:Consult the Infinity Expansion Module Configuration Guide for the maximum number of inputs/outputs allowed on each particular Infinet controller.
AGENCY LISTINGSUL/CUL 916, FCC,CE
- EMX 150 Points
- 2 analog outputs
- Range
- 0-20 mA or 0-20 VDC for each output
- Impedance
- 0-20 mA into maximum 750 ohms 0-20 VDC into minimum 4,000 ohms
- Resolution
- 0.1 mA or 0.1 VDC
- Overrides
- 2-position plus potentiometer, no software feedback
- Power Consumption
- 55 mA
- Dimensions
- 6.13"W x 4.88"H x 1.52"D (155W x 124H x 39D)mm
- EMX 151 Points
- 2 high-resolution analog outputs
- Range
- 0-20 mA or 0-10 VDC
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
S P E C I F I C A T I O N S (Cont'd)
- EMX 151 (Continued) Impedance
- 0-20 mA into maximum 1,000 ohms 0-10 VDC into minimum 4,000 ohms
- Resolution
- 4.88 µA or 2.44 mV
- Accuracy
- ± 0.1% of span
- Power Consumption
- 70mA
- Dimensions
- 6.13"W x 4.88"H x 1.52"D (155W x 124H x 39D)mm
- EMX 155 Points
- 2 digital outputs
- Type
- Form C relay
- Contact Rating
- 5A, 24 VAC / VDC
- Resolution
- 0.1 second
- Overrides
- Hand-off-auto switch with software feedback
- Power Consumption
- 46 mA
- Dimensions
- 6.13"W x 4.42"H x 1.82"D (155W x 112H x 46D)mm
- EMX 156 Points
- 2 high voltage digital outputs
- Type
- Form A solid state device, field replaceable
- Contact Rating
- 3A, 120/240 VAC @ 25°C, 2A, 120/240 VAC @ 50°C (DC loads not permitted).
- Minimum Load
- 12 VAC, 20 mA
- Single Cycle Surge Current
- 80A
- Contact Isolation
- 4,000 V RMS
- Allowable Power Factor
- EMX 156 provides switching for inductive loads with 0 .4 to 1.0 power factor.
- Resolution
- 0.1 second
- Overrides
- Hand-off-auto switch with software feedback
- Power Consumption
- 32 mA
- Dimensions
- 6.13"W x 4.42"H x 1.52"D (155W x 112H x 39D)mm
- EMX 160 Points
- 8 digital inputs. Any or all points can be assigned as counter inputs. All inputs must be dry contacts.
Maximum Counter Frequency: 140 Hz, 50% duty cycling, 3.57 ms minimum pulse width Reference Voltage:
5 VDC into 24k ohms
- Input Protection
- 24 VAC / VDC indefinitely on any single channel, 1500 volt transients
- Power Consumption
- 12 mA
- Dimensions
- 6.13"W x 5.72"H x 1.52"D (155W x 145H x 39D)mm
Andover Controls Corporation World Headquarters 300 Brickstone Square Andover, Massachusetts 01810 USA Tel: 508 470 0555 • Fax: 508 470 0946 http://www.andovercontrols.com Andover Controls Ltd. Smisby Road Ashby-de-la-Zouch Leicestershire LE65 2UG England Tel: 01530 417733 • Fax: 01530 415436 Andover Controls GmbH Am Seerhein 8 D-78467 Konstanz, Germany Tel: 07531 99370 • Fax: 07531 993710 Andover Controls S.A. 93 avenue de Fontainebleau 94270 Le Kremlin-Bicetre Tel: 1 49 606363 • Fax: 1 49 606271 Andover Controls Asia 707 Chinachem Golden Plaza 77 Mody Road, Tsimshatsui East Kowloon, Hong Kong Tel: 2739 5497 • Fax: 2739 7350 U.S. Patent #4591967 ©1998 Andover Controls Corporation. Data subject to change without notice. Consult Andover Product Installation Guides for exact installation instructions and specifications. #DS-EMX150-3.96