Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of NM Series Direct Coupled Actuator

Spec sheet · Andover Controls

NM Series Direct Coupled Actuator

Spec sheet17 pagesPDF 413 KB

Belimo catalog pages for the NM Series direct coupled damper actuators (NM24, NM24-SR, NM24-MFT, NMQ24-MFT) and accessories.

What this file really is

The old site listed this file as a spec sheet for the Andover Controls NM24-AV. These are Belimo NM Series actuator catalog pages; they do not name an Andover Controls NM24-AV.

Download the PDF413 KB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Catalog pages from Belimo Aircontrols for the NM Series non-spring return, direct coupled damper actuators used on HVAC dampers. An overview table compares the models, then each actuator (NM24 US on-off/floating point, NM24-SR US proportional, NM24-MFT US Multi-Function Technology and the fast acting NMQ24-MFT US) gets technical data, operation notes, dimensions, wiring diagrams and a typical specification. The SN1 and SN2 auxiliary switches, installation instructions, general wiring and start-up and checkout follow.

From the sheet

Key facts from this sheet

Each line names its page in the PDF.

Belimo product literature for the NM Series direct coupled damper actuators: NM24 US, NM24-SR US, NM24-MFT US and NMQ24-MFT US, plus the SN1 and SN2 auxiliary switches. It gives technical data, wiring diagrams, mounting and wiring instructions and an electrical checkout procedure. It does not name the NM24-AV designation the site files it under.

Read for this summary: pages 1 to 9, 11, 13 to 14 and 17 of 17.

Device
Non-spring return, direct coupled damper actuators for HVAC systems, 24 V p. 3, 5, 7
Torque
NM24 US, NM24-SR US and NM24-MFT US: min. 70 in-lb (8 Nm); NMQ24-MFT US: min. 35 in-lb (4 Nm) p. 3, 5, 7, 9
Damper area
NM24 US and NM24-SR US: air dampers up to 18 sq ft, figured at about 4 in-lb per sq ft p. 3, 5
Control signal
NM24 US: on-off or floating point (tri-state); NM24-SR US, NM24-MFT US and NMQ24-MFT US: 2 to 10 VDC, or 4 to 20 mA with a 500 Ω resistor p. 3, 4, 5, 7, 9
Power supply
NM24-MFT US: 24 VAC ± 20%, 50/60 Hz, or 24 VDC ±10%; NMQ24-MFT US: 24 VAC ± 5%, 50/60 Hz, or 24 VDC ± 5% p. 7, 9
Power consumption
NM24-MFT US: running 1.3 W, holding 0.5 W; NMQ24-MFT US: running 9 W, holding 1.2 W p. 7, 9
Feedback
NM24-SR US, NM24-MFT US and NMQ24-MFT US: 2 to 10 VDC position feedback (the two MFT models: 0.5 mA max) p. 5, 7, 9
Running time
NM24-SR US: 150 seconds for 35 to 95° of stroke; NM24-MFT US: 150 seconds constant; NMQ24-MFT US: 5.0 seconds for 95° p. 5, 7, 9
Rotation
0 to 95°, limited with adjustable mechanical stops p. 3, 7, 9
Connection
3 ft, 18 GA plenum cable with 1/2 in. conduit connector p. 3, 5, 7, 9
Temperature
NM24-MFT US and NMQ24-MFT US: ambient -4 to +122° F (-20 to +50° C); storage -40 to +176° F (-40 to +80° C) p. 7, 9
Weight and housing
NM24-MFT US and NMQ24-MFT US: 1.8 lbs (0.8 kg), NEMA 2, IP54 housing p. 7, 9
Accessories
NM24 US and NM24-SR US: AV 10-18 damper shaft extension, SN1 and SN2 auxiliary switches, ZG-H2 operator handle, ZG-NMSA-1 short shaft adaptor p. 3, 5
Auxiliary switches
SN1: one SPDT; SN2: two SPDT; 6 A (2.5 A) 250 VAC, adjustable over the full rotation p. 11

What this sheet walks you through

  • Mounting the actuator on the damper shaft and pre-loading it 5° from closed p. 13
  • Setting the adjustable end stops p. 13
  • Testing the installation without power p. 13
  • Wiring on-off and tri-state control of the NM24 US p. 4
  • Wiring 2 to 10 VDC and 4 to 20 mA control of the NM24-SR US p. 6
  • Wiring the NM24-MFT US, including override to min, mid and max positions p. 8
  • Mounting the SN1 and SN2 auxiliary switches p. 11
  • Powering several actuators from one or more transformers p. 14
  • Starting the NMQ24-MFT US adaptation after installation p. 9
  • Step-by-step electrical checkout of the NM24-SR US and NM24-MFT US p. 17

Good to know

  • The SN1 and SN2 switches will not mount on NM actuators made before May 1994. p. 11
  • Mount indoors in a dry, clean place; outdoors a protective enclosure is needed. p. 13
  • Power controllers from a separate transformer unless the controller supply uses half wave rectification; mixing them can damage the controller. p. 14
  • The enclosure cannot be opened in the field and has no replaceable or repairable parts. p. 14
  • When one wire run powers several actuators, divide the allowed wire length by the number of actuators. p. 14

Questions this sheet answers

What control signal does the NM24-SR US accept?

2 to 10 VDC, or 4 to 20 mA when a 500 Ω resistor converts it to 2 to 10 VDC. p. 5, 6

How do I start the adaptation on an NMQ24-MFT US?

After mounting and wiring, press the manual override button twice within four seconds. p. 9

Can an NM24 actuator be stalled without damage?

Yes. The document says the actuator can be stalled indefinitely in any position without harm. p. 13

What minimum supply voltage does the NM24-SR US or NM24-MFT US checkout call for?

The checkout gives a minimum of 19.2 VAC or 21.6 VDC, with a supply rated at least the total actuator requirement. p. 17

Which wires carry the control signal on the NM24-SR US?

Control signal positive goes to wire No. 3 and negative to wire No. 1; the checkout says most control problems come from reversing them. p. 17

The whole text · 2 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 91-9
  2. Pages 10 to 1710-17

The file

Revision and size

RevisionG20492
PublisherBelimo Aircontrols (USA), Inc.
Pages17
PDF413 KB
TextText from the PDF itself.

The first pages · 4 of 17

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 17
Page 2
Page 2of 17
Page 3
Page 3of 17
Page 4