Manual · Apollo Actuation
Apollo Rack & Pinion Pneumatic Actuators Installation, Operation and Maintenance Manual
Manual10 pagesPDF 450 KB
Installation, operation and maintenance manual for Apollo rack and pinion pneumatic actuators, sizes A0025 to A4000.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Apollo's installation, operation and maintenance manual for its rack and pinion pneumatic valve actuators, double acting and spring return, in sizes A0025 to A4000. It explains the part numbering system, exploded views and parts lists, installation on ball, butterfly and plug valves, single and dual stroke adjustment, a tool and torque chart, recommended tubing sizes, and step-by-step disassembly and reassembly with the repair kit.
Its parts
- Introduction
- Exploded View & Parts List
- Installation
- Disassembly
- Reassembly
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation, operation and maintenance manual (IOM #I941900, Rev B, March 1, 2011) for Apollo rack and pinion pneumatic actuators, double acting and spring return, in sizes A0025 through A4000. It covers the part number system, exploded views and parts lists, mounting on a valve, stroke adjustment, disassembly and reassembly. The A0025U designation the site files it under is not printed; size A0025 is covered with the A0025 to A1600 group.
- Device
- Rack and pinion pneumatic actuators, double acting or spring return, for 90 degree valves such as ball, butterfly and plug valves p. 1, 2, 5
- Sizes
- 0025, 0040, 0065, 0100, 0150, 0200, 0350, 0600, 0950, 1600, 2500, 4000 p. 2
- Action codes
- D = double acting, S = spring return, K = kit; add suffix F for fail open units p. 2
- Seals and temperature
- N Nitrile: -4° to 175° F; H Fluorocarbon: -4° to 250° F; L Silicone: -40° to 175° F p. 2
- Limit stops
- Single adjustable stops on the end caps on all actuators; dual adjustable limit stops on sizes 0025 thru 1600 only p. 2, 6
- Air ports
- Pressure at port A drives to full CCW; port B to full CW p. 5
- Repair kit
- Part numbers like AK0350N (Nitrile seals); bearings, piston and heel guides, o-rings, spring clip and thrust washer p. 8
- Lubricant
- Dow 111 grease, included with each kit p. 9
- End cap screws, 0025
- AD/AS0025: M5 socket-head cap screws, 4mm allen key p. 7
- Touch-up paint
- Rust-oleum Sunburst Yellow Gloss Protective Enamel: spray #7747830, ½ pint #7747730, quart #7747502 p. 10
- Mounting
- In-line with the piping by default, clockwise to close; perpendicular mounting allowed for space limits p. 5
What this manual walks you through
- Mounting a double acting actuator on a valve p. 5, 6
- Installing spring return actuators for fail closed or fail open, in-line or perpendicular p. 6
- Setting the single (outward) stroke stops p. 6
- Setting the inward stop on dual stop models p. 7
- Identifying parts from the exploded views and parts lists p. 3, 4
- Removing end caps, pistons, pinion and insert p. 8
- Reassembling the pinion, pistons, springs and end caps p. 9, 10
- Checking a rebuilt unit for air leaks with soapsuds p. 10
Good to know
- Do not work on valves or actuators under pressure; ball and plug valves can trap pressure in the body cavity. p. 5
- On spring return models, loosen the end cap fasteners evenly in a criss-cross pattern, two to three turns at a time, until spring pre-load is relieved. p. 8
- Failing to adjust both outbound limit stops may damage the actuator pistons. p. 7
- Fail open actuators need special factory preparation; the model number must end in F. p. 6
- Keep the very small port o-rings for reuse when removing the end caps. p. 8
Questions this manual answers
How do I tell if an Apollo spring return actuator is set up for fail open?
Fail open units get special factory preparation and their model number ends in the letter F. p. 2, 6
Which repair kit fits an Apollo rack and pinion actuator?
Kit part numbers look like AK0350N, the example given for a kit with buna-n (Nitrile) seals; each kit includes assembly lubricant. p. 8, 9
What grease is used when rebuilding the actuator?
A light film of Dow 111 grease on the o-rings, bearings, heel guides and pinion teeth. p. 9
How do I set the open position on the actuator?
Back out both end cap limit stop bolts 4 turns, turn the shaft to the desired position, then turn the bolts in until they meet resistance and lock the nuts. p. 6
The whole text · 1 part
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file