DL305 User Manual: Chapter 10: RLLPLUS Programming Basics, pages 224 to 233

Pages 224 to 233 of 359, from DL305 User Manual

The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D3-08TD2, AutomationDirect D3-16TD2, Konnect-It D3-08TD2, Koyo D3-08TD2, Konnect-It D3-16TD2 and Koyo D3-16TD2

Page 224

RLL PLUS Programming Basics

10--21

Here’s a flowchart that describes the two-station press. Please note we’ve changed some of the stage numbers, input numbers, and output numbers, so they won’t necessarily match the previous examples. Check for Stop Stage150

Reset all stages Jump to Start

Check for Parts in A&B Stage 10

Lock the clamp

Press the Part

Unlock clamp

Wait for Station B

Move Conveyor

Check Mode

A Stage 20

Stage 21

Stage 22

Stage 23

Stage 40

Stage 50

Station A Wait for Start Stage 0

No Part in A

Station B Lock the clamp

Press the Part

Unlock clamp

Station B Finished

B Stage 30

Stage 31

Stage 32

Stage 33

Program must converge into a single path again

No Part in B

One Cycle

Continuous

You’ve already seen how the basic sequence of operations was executed. so we’re only going to show the portions of the program that describe how the branches are joined together.

RLLPLUS Programming Basics

DL305 User Manual, Rev. D

Page 225

10--22

RLL PLUS Programming Basics

Using Stage Bits as Contacts

If you examine the flowchart you’ll notice once the part is unclamped in station B, the program transitions to Stage 33 which indicates Station B is complete. If you look at that portion of the program shown here, you’ll notice there are no other instructions or actions that take place in this stage. This is why we call it a “dummy” stage. We’re just going to use the status of the stage bit associated with this dummy stage as a contact elsewhere in the program to indicate station B is finished. You may be wondering how we can turn off this stage. Since it does not have any type of jump or power flow transition, the only other option is to Reset the stage. We’ll do this later in the program.

Station B SG

Lock the clamp

S030

Clamp SET 020 S31 JMP

Part Locked 023 SG

Press the part

S031

Press Down 021

Lower Limit

S32 JMP

024 SG

Unlock the clamp

S031 Top Limit

Clamp RST 020

025 Part Unlocked

S33 JMP

023 SG

S0033

Station B Finished

Check for Stop Stage 150

Reset all stages Jump to Start

Check for Parts in A&B Stage 10

Lock the clamp

Press the Part

Unlock clamp

Wait for Station B

Move Conveyor

Check Mode

A Stage 20

Stage 21

Stage 22

Stage 23

Stage 40

Stage 50

Station A Wait for Start Stage 0

No Part in A

RLLPLUS Programming Basics

Station B Lock the clamp

Press the Part

Unlock clamp

Station B Finished

B Stage 30

Stage 31

Stage 32

Stage 33

No Part in B One Cycle

Continuous

DL305 User Manual, Rev. D

Program must converge into a single path again

Page 226

RLL PLUS Programming Basics Stage Contact Example

Since each stage has a status bit that is either on or off, you can use this bit as a contact in the program. If you examine Stage 23 you’ll notice we’ve used a contact labeled S33. This contact reflects the status of Stage 33, which indicated Station B was finished. When S33 is on, the contact labeled S33 is also on and the program will transition to Stage 40. In Stage 40 we use a reset instruction to reset Stage 33 before we move the conveyor.

10--23

Only executes logic in stages that are active

Station A SG

Clamp the part

S020

Part Locked

Clamp SET 020 S21 JMP

002 SG

Press the part

S021

Press Down 021 Lower Limit

S22 JMP

004 SG

Unlock the clamp

S022 Top Limit

Clamp RST 020

005 Part Unlocked

S23 JMP

003 SG

Wait for Station B to finish

S023

B Finished

S40 JMP

S33 SG

Index the conveyor

S040

B Finished RST S33 Conveyor 022

Conveyor Moved

S50 JMP

006 SG

One cycle or automatic?

S050

One Cycle

S0 JMP

007 One Cycle

S10 JMP

007

RLLPLUS Programming Basics

DL305 User Manual, Rev. D

Page 227

10--24

RLL PLUS Programming Basics

Unusual Operations in Stages

Using the Same Output Multiple Times

Over the last few pages you’ve learned how the CPU executes the Stage instructions. However, there are a few unusual circumstances that may not work exactly as the appear. In the program shown it appears output 021 will be turned on at three separate SG times before the program jumps to the S0010 next stage. However, the only time the TMR T600 output actually comes on is when the final condition has been met. T600 K100 021 Why? Remember if you use multiple OUT outputs in a program, the last rung 021 T600 K200 T600 K500 containing the output controls the status OUT that will be written to the module. This is 021 T600 900 no different in a program that uses OUT PLUS RLL instructions. Finished S20 In this example, the last comparison rung JMP 001 says the output should be off until the timer value reaches 90 seconds.

RLLPLUS Programming Basics

In the previous example the same output was used multiple times in the same stage. The last use of the output controlled the status of the output. There may be occasions when you have the same output in different stages. Even though it’s not advisable to do this in normal RLL programs, this is perfectly acceptable with a program that uses RLL PLUS instructions. However, if both stages are active at the same time, then the logic in the last stage will control the status of the output. In the example shown, if both stages are active, then the logic in Stage 70 will control the output status.

DL305 User Manual, Rev. D

SG

S0010 021 OUT 001 S002 JMP 002

SG

S070 021 OUT 010

011 S002 JMP

006

Page 228

RLL PLUS Programming Basics

Using a Set Out Reset (SET OUT RST) Instruction

Output Placement

Many normal RLL programs use one-shot instructions. In the DL305 instruction set, this instruction is called a Set Out Reset (SET OUT RST). In the program shown, input 001 will trigger the SET OUT RST 160 instruction, which will in turn activate output 021 for one scan. However, what happens if 001 stays on and Stage 10 is activated, deactivated, and then activated again? At first glance it appears the one shot only gets executed one time since 001 stayed on while Stage 10 was turning on and off. It doesn’t work this way. The logic in an inactive stage is not executed. So even though the stage became active the SET OUT RST instruction did not see an off to on transition, so the instruction is not executed. The SET OUT RST instruction will work in an active stage as long as the input transitions from off to on while the stage is active.

Scan N SG

One Shot is executed

S010 001

160 SET OUT RST

160

021 OUT

Scan N + 10 SG

Stage off, One Shot is not executed

S0010 001

160 SET OUT RST

160

021 OUT

Scan N + 20 SG

S0010

One shot must see off to on 001

160 SET OUT RST

160

021 OUT

Incorrect Placement SG

S0010 001

CNT

C600

021 OUT 003

S11 JMP

Correct Placement SG

S0010 021 OUT 001

CNT

003

DL305 User Manual, Rev. D

C600

S11 JMP

RLLPLUS Programming Basics

As you’ve seen in some of the previous examples, we always place unconditional outputs immediately following the Stage Instructions. There’s a reason for doing this. If you look at the example stage shown here, the output is placed after a counter box. The DirectSOFT software and the Handheld Programmer will allow you to enter this as shown. However, the CPU will only turn on output 021 when the counter input 001 is turned on. This is because the CPU interprets the output as being tied to the counter input leg instead of the Stage power rail. You can easily avoid this problem by placing any unconditional actions at the very beginning of the stage. Then, the output will work the way you expect.

10--25

Page 229

10--26

RLL PLUS Programming Basics

Two Ways to View RLL PLUS Programs Throughout the example programs, we’ve consistently shown how the instructions appear in when viewed as ladder instructions. However, with DirectSOFT, you also have the capability to view the program as a flowchart. You can even view the program flowchart (in Stage View) and view the ladder program at the same time with a split screen feature. The DirectSOFT manual provides detailed information on how to view the programs in this manner. DirectSOFT Stage View ISG S0

J

J

SG

Stage

SG S1

SG S150

Reference to a Stage

DirectSOFT Ladder View

J

SG S2

S

SG S140

J

SG S6

J

SG S3

J

ISG S0

R

SG S140 Transition Logic

ISG

J

Wait for start

S000 Start

S1 JMP

000 SG

Check for a part

S001

Part Present

S2 JMP

001 Part Present

S5 JMP

001

RLLPLUS Programming Basics

SG

Lock the clamp

S002

Part Locked

Clamp SET 020 S4 JMP

002 SG

Press the part

S003

Press Down 021 Lower Limit 004

DL305 User Manual, Rev. D

S4 JMP

Jump

S

Set Stage

R

Reset Stage

Page 230

RLL PLUS Programming Basics

10--27

Designing a Program Using RLL PLUS Instructions As with most any application problem, a thorough understanding of the tasks combined with a good plan of execution often results in success. The RLL PLUS instructions provide an easy way to load the plan of execution directly into the CPU. The easiest way to make sure you understand the tasks is to make a flowchart. This is often the most critical part of creating a program that uses RLL PLUS instructions. There are a few simple steps you can follow to create a detailed flowchart. 1. Create a top-level flowchart. 2. Expand the flowchart by adding things that cause the transitions from step to step. 3. Add any actions that must occur in each step. 4. Add any conditions that control the actions. 5. Add any special monitoring or alarm steps that must be performed. 6. Assign numbers to the stages (steps). 7. Add the I/O instructions and addresses (input contacts, output coils, jump instructions, etc.) 8. Enter the program. Use DirectSOFT to The DirectSOFT programming package allows you to quickly and easily create programs with RLL PLUS instructions. The software has special features that allow Save Time you to create the flowcharts, add the transitions, actions, etc. Even if your programs are fairly small, DirectSOFT can make the job much easier.

RLLPLUS Programming Basics

DL305 User Manual, Rev. D

Page 231

10--28

RLL PLUS Programming Basics

Step 1: Design a Top-level Flowchart

There are many different ways to design a flowchart of the application problem, but there are a few guidelines that will make the job easier. 1. Start with a “top-level” flowchart that breaks the operation sequence into simple pieces. 2. Each piece of the top-level flowchart should only represent one action. Resist the temptation to group several operations into one part of the flowchart. 3. Don’t try to add input or output addresses to the flowchart. Only use words to describe the things that are taking place. 4. Don’t worry about special conditions, such as stop conditions, alarms, etc at this point. These will be added later when you fully understand how the main part of the operations sequence is organized. You can draw the flowchart horizontally or vertically at any point in the design process, the choice is yours. Here’s an example top level flowchart for our simple one-station press. The flowchart breaks the program into logical steps

Wait for Start

RLLPLUS Programming Basics

One Cycle

DL305 User Manual, Rev. D

Check for Part

Continuous Check Mode

Lock Clamp

Press Part

Unlock Clamp

Move Conveyor

Page 232

RLL PLUS Programming Basics Step 2: Add Flowchart Transitions

10--29

Once you have designed the basic operating sequence you should determine the events that cause a transition from step to step. During this phase you may find things need to be added to the flowchart. All you’re really doing is adding more detail to the top-level flowchart. Once again, don’t try to use addresses yet. Concentrate on using words to describe the events taking place. The following flowchart adds the transition conditions for our one-station press. Wait for Start

Transition Symbol Press Start Switch

Check for Part

Part in place

No Part

Lock the Clamp

Jump to Move Conveyor

Clamp Limit Switch

Press the Part

Press Lower Limit Switch Unlock the Clamp

Unclamp Limit Switch Move Conveyor

Conveyor Index Limit Switch

Check 1-cycle Switch ON Jump to Wait for Start

Check 1-cycle Switch OFF Jump to Check for Part

DL305 User Manual, Rev. D

RLLPLUS Programming Basics

Check Mode

Page 233

10--30

RLL PLUS Programming Basics

Step 3: Add Actions

After you determine the events that cause a transition from step to step you should add any actions that need to take place during the sequence. Again, don’t try to use addresses yet. Concentrate on using words to describe the actions taking place. The following flowchart adds the actions that take place during each part of the program. Wait for Start

Press Start Switch

Check for Part

Part in place

No Part Jump to Move Conveyor

Lock the Clamp Clamp On Clamp Limit Switch

Action Symbol

Press the Part Press Press Lower Limit Switch Unlock the Clamp Clamp Off Unclamp Limit Switch Move Conveyor Conveyor On Conveyor Index Limit Switch

RLLPLUS Programming Basics

Check Mode

Check 1-cycle Switch ON Jump to Wait for Start

DL305 User Manual, Rev. D

Check 1-cycle Switch OFF Jump to Check for Part