The text of a manual · part 41 of 42

DL305 User Manual, pages 342 to 353

Pages 342 to 353 of 359: Appendix B: DL305 Error Codes; Appendix C: Instruction Execution Times

The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D3-08TD2, AutomationDirect D3-16TD2, Konnect-It D3-08TD2, Koyo D3-08TD2, Konnect-It D3-16TD2 and Koyo D3-16TD2

Page 342

DL305 Error Codes

In This Appendix. . . ., Error Code Table

1B

Page 343

Appendix B DL305 Error Codes

Appendix A DL305 Error Codes

B--2

DL305 Error Codes

DL305 Error Code

Description

E01 Invalid Keystrokes

Invalid keystroke or series of keystrokes entered into the handheld programmer. Refer to the DL305 Handheld Programmer manual for assistance in the operation you are trying to perform.

E02 An I/O point dedicated to an input module has been used as an output in the Input Point Programmed application program. Change the I/O reference number in the program which is as Output causing the error. E03 Stack Overflow

The maximum number of instructions utilizing the internal stack has exceeded eight. These instructions can be a combination of AND STRs, OR STRs and MCS/MCR groups. Reduce the number of these instructions which are pushed onto the stack at one time.

E05 (NON Stage) Duplicate Coil Reference

Two or more output coils have the same data type and number. Change the duplicate coil to correct the error. Duplicate coil references are valid with the SET instruction. E05 will be generated at the address of the second duplicated output.

E05 (Stage) Duplicate Stage Reference

Two or more Stages have the same reference number. Change the duplicate Stage number to correct the error. E05 will be generated at the address of the second duplicated stage number.

E06 MCR/MCS Mismatch

The number of MCR instructions do not match the number of MCS instructions. Each MCR must have an accompanying MCS.

E07 Missing CNT or SR Contact

A required input contact is missing from a CNT (example, RESET input) or a SR instruction.

E08 Invalid Data Values

The required data values for a TMR, CNT or SR are missing or incorrect. Refer to the DL305 Programming Manual Set for details on these instructions.

E09 Incomplete Program Rung

The rung does not terminate with an output as required. Program an output to terminate the rung properly.

E11 Program Full

There is no available program addresses in memory. Reduce the size of the program.

E21 Program Memory Parity Error

A parity error has occurred in the program memory of the CPU. Clear the memory and reload the program. If the error reoccurs replace the CPU. Severe electrical noise will cause this problem.

E22 Password Error

The password stored in the CPU is invalid. Press the “CLR” key twice on the handheld programmer and the password will be reset to 0000. Re-enter the password if required.

E25 A mismatch was found when a compare was performed on the program in CPU Tape/Program Mismatch memory and the program stored on tape. E28 Volume Incorrect On Tape Device.

The volume is incorrect on the tape player being used to load the program to the CPU. Adjust the volume and retry the operation. Refer to the DL305 Handheld Programmer manual for details on tape operation.

E31 RAM Limit Exceeded

The application program required more RAM for execution than is available. Reduce the length of the program.

E377 EEPROM Write Error

Write of EEPROM failed because EEPROM is write protected (remove write protect jumper), the EEPROM is bad (replace EEPROM), or UVPROM is installed instead of EEPROM (install EEPROM).

E99 Instruction Not Found

A search was performed and the specified instruction was not found in the application program.

DL305 User Manual, Rev. D

Page 344

Instruction Execution Times In This Appendix. . . ., Introduction, DL330 Instruction Execution Times, DL330P Instruction Execution Times, DL340 Instruction Execution Times

1C

Page 345

Instruction Execution Times

Introduction This appendix contains several tables that provide the instruction execution times for the DL330, DL330P, and DL340 CPUs. One thing you will notice is that many of the execution times depend on the type of data being used with the instruction. For example, some of the instructions have different execution times if you use a regular data register instead of a constant. You’ll also notice that some of the data instructions (such as DSTR) require differing amounts of execution time depending on the type of data. There are generally three options. S Data Registers S I/O Data Registers S Constants The following paragraphs may help you understand the differences between the register types. Data Registers

Appendix D Inst. Execution Times

Appendix C Inst. Execution Times

Appendix B DL405 Error Codes

Appendix A DL405 Error Codes

C--2

Some data registers are primarily used to hold variable data and are considered true data registers. For example, the registers that store the timer or counter current values, or just regular variable data would be considered as a data register. Don’t think that you cannot load a bit pattern into these types of registers, you can. It’s just that their primary use is as a data register. The following locations are considered as data registers. Type of Data

I/O Data Registers

DL330

DL330P

DL340

Timer / Counter Current Values

R600 -- R677

R600 -- R677

R600 -- R677

User Data Words

R400 -- R563

R400 -- R563

R400 -- R563 R700 -- R767

You may recall that the I/O points are automatically mapped into data register locations. The following locations that contain this data are considered I/O registers and will take longer to execute with most instructions. Type of Data I/O Points

DL330 R000 -- R016* R070 -- R 076

DL330P R000 -- R016* R070 -- R076

DL340 R000 -- R017* R070 -- R076

NOTE: 160 -- 167 can be used as I/O in a DL330 or DL330P CPU under certain conditions. 160 -- 177 can be used as I/O in a DL340 CPU under certain conditions. You should consult Chapter 4 to determine which configurations allow the use of these points. These points are normally used as control relays. You cannot use them as both control relays and as I/O points. Also, if you use these points as I/O, you cannot access these I/O points as a Data Register reference.

DL305 User Manual, Rev. D

Page 346

Instruction Execution Times

Some of the instructions can have more than one parameter so the table shows execution times that depend on the amount and type of parameters. For example, the when you use the SET instruction to set a range of stages in a DL330P CPU, the execution time depends on how many stages are being set by the instruction.

X0

X1

Two Locations Available

S10 -- S17 SET

Appendix A DL405 Error Codes

How to Read the Tables

C--3

C0

Stage Instruction

Stage Instruction not activated by a Jump instruction (ex. power flow)

SET SG

26.3 + 13.1μs x (n--1)

18.8 μs

Does not apply

RST SG

26.3 + 13.1μs x (n--1)

18.8 μs

Does not apply

Appendix C Inst. Execution Times

Execution depends on numbers of locations and types of data used

Appendix B DL405 Error Codes

Instruction

Appendix D Inst. Execution Times

DL305 User Manual, Rev. D

Page 347

Instruction Execution Times

DL330 Instruction Execution Times Basic Input Instructions

Appendix D Inst. Execution Times

Appendix C Inst. Execution Times

Appendix B DL405 Error Codes

Appendix A DL405 Error Codes

C--4

Output Type Instructions

Instruction

Execute

Disabled by MCR

STR

6.6 μs

N/A

STR NOT

9.1 μs

N/A

AND

5.3 μs

N/A

AND NOT

8.4 μs

N/A

OR

6.6 μs

N/A

OR NOT

9.1 μs

N/A

STR T/C

10.3 μs

N/A

STR NOT T/C

12.8 μs

N/A

AND T/C

5.3 μs

N/A

AND NOT T/C

8.4 μs

N/A

OR T/C

6.6 μs

N/A

OR NOT T/C

9.1 μs

N/A

STR (Comparative Contact)

50.9 μs

N/A

STR NOT (Comparative Contact)

61.5 μs

N/A

AND (Comparative Contact)

59.1 μs

6.2 μs

AND NOT (Comparative Contact)

60.3 μs

6.2 μs

OR (Comparative Contact)

60.3 μs

6.2 μs

OR NOT (Comparative Contact)

62.5 μs

6.2 μs

AND STR

3.8 μs

N/A

OR STR

3.8 μs

N/A

MCR

5.0 μs

N/A

MCS

3.0 μs

N/A

Instruction

Execute

Not Executed

OUT

7.5 μs

7.5 μs

SET OUT

10.0 μs

10.0 μs

SET

17.5 μs

17.5 μs

RST

9.3 μs

9.3 μs

SET OUT RST

19.3 μs

19.3 μs

DL305 User Manual, Rev. D

Page 348

Instruction Execution Times

Execute w/ Constant

Instruction

Execute w/ Data Register

Execute w/ I/O Register

Not Executed

TMR

90.9 μs

458.8 μs

700.0 μs

27.1 μs

CNT

92.9 μs

465.6 μs

706.8 μs

27.1 μs

SR

64.1 μs+16.6 μs times ( # of shifts)

Data Operations

Execute w/ Data Register

Instruction

53.1 μs

Execute w/ I/O Register

Execute w/ Constant

Appendix A DL405 Error Codes

Timer, Counters, and Shift Registers

C--5

Not Executed

321.9 μs

14.3 μs

6.3 μs

DSTR1

F51

63.8 μs

140.9 μs

N/A

6.3 μs

DSTR2

F52

95.0 μs

172.2 μs

N/A

6.3 μs

DSTR3

F53

96.6 μs

173.8 μs

N/A

6.3 μs

DSTR5

F55

N/A

326.2 μs

N/A

6.3 μs

DOUT

F60

52.6 μs

329.4 μs

N/A

6.3 μs

DOUT1

F61

39.1 μs

160.1 μs

N/A

6.3 μs

DOUT2

F62

39.8 μs

116.0 μs

N/A

6.3 μs

DOUT3

F63

55.0 μs

108.1 μs

N/A

6.3 μs

DOUT5

F65

N/A

358.3 μs

N/A

6.3 μs

CMP<=>

F70

112.8 μs

354.0 μs

57.0 μs

6.3 μs

ADD

F71

456.8 μs

698.0 μs

262.0 μs

6.3 μs

SUB

F72

315.8 μs

557.0 μs

275.0 μs

6.3 μs

MUL

F73

290--2664 μs

497--2851 μs

223--2576 μs

6.3 μs

DIV

F74

742--2645 μs

1218--2851μs

720--2557 μs

6.3 μs

DAND

F75

103.7 μs

345.0 μs

55.6 μs

6.3 μs

DOR

F76

103.7 μs

345.0 μs

55.6 μs

6.3 μs

SHFR

F80

216 μs+13.4 μs times ( # of shifts)

6.3 μs

SHFL

F81

220 μs+13.4 μs times ( # of shifts)

6.3 μs

DECO

F82

56.3 μs

N/A

N/A

6.3 μs

ENCO

F83

282.0 μs

N/A

N/A

6.3 μs

INV

F84

30.0 μs

N/A

N/A

6.3 μs

BIN

F85

412.2 μs

N/A

N/A

6.3 μs

BCD

F86

746.0 μs

N/A

N/A

6.3 μs

FAULT

F20

114.0 μs

355.3 μs

72.2 μs

6.3 μs

DL305 User Manual, Rev. D

Appendix D Inst. Execution Times

80.7 μs

Appendix C Inst. Execution Times

F50

Appendix B DL405 Error Codes

DSTR

Page 349

Instruction Execution Times

DL330P Instruction Execution Times Basic Input Instructions

Appendix C Inst. Execution Times Appendix D Inst. Execution Times

I/O, Control Relay

Instruction

Executed *

Appendix B DL405 Error Codes

Appendix A DL405 Error Codes

C--6

**

Timer, Counters, and Shift Registers

Not Executed *

Not Executed

Executed

**

*

Timer / Counter

**

*

Not Executed

Executed

**

*

**

*

STR

28.4 / 31.4μs

21.3 μs

25.6 / 30.9μs

22.2 μs

121.3/117.8μs

28.4 μs

STR NOT

28.4 / 31.4μs

21.3 μs

25.6 / 30.9μs

22.2 μs

121.3/117.8μs

28.4 μs

AND

13.4 / 20.0μs

13.4 / 20.0μs

13.4 / 20.0μs

13.4 / 20.0μs

123.1/119.6μs

20.3 μs

AND NOT

18.1 / 21.6μs

10.3 μs

18.1 / 21.6μs

10.3 μs

123.1/119.6μs

20.3 μs

OR

21.8 / 25.3μs

14.7 μs

21.8 / 25.3μs

14.7 μs

123.1/119.6μs

20.3 μs

OR NOT

20.6 / 24.1μs

14.7 μs

20.6 / 24.1μs

14.7 μs

123.1/119.6μs

20.3 μs

*

Execution time when data type is ON. For example, STR 000 takes 28.4 μs if point 000 is on.

**

Execution time when data type is OFF. For example, STR 000 takes 31.4 μs if point 000 is off. Instruction

Output Type Instructions

Stage

Executed

Not Executed

AND STR

25.9 μs

22.8 μs

OR STR

25.9 μs

22.8 μs

Instruction

Execute

Not Executed

OUT

20.6 μs

20.6 μs

SET OUT

24.3 μs

16.6 μs

SET

24.3 μs

16.6 μs

RST

24.3 μs

16.6 μs

SET OUT RST

33.8 μs

29.4 μs

Instruction

Execute

Not Executed

TMR

92.8 μs

50.9 μs

CNT

97.5 μs

46.3 μs

RST CNT

25.9 μs

16.6 μs

SR

75.9 +11.5μs x (# of shifts)

41.9 μs

DL305 User Manual, Rev. D

**

Page 350

Instruction Execution Times

Stage Instruction not activated by a Jump instruction (ex. power flow)

Stage Instruction

Instruction

Executed

Not Executed

Executed

Not Executed

35.3 μs

20.0 μs

50.9 μs

30.6 μs

SG

35.3 μs

20.0 μs

50.9 μs

30.6 μs

JMP

28.4 μs

16.6 μs

Does not apply

NJMP

40.3 μs

28.4 μs

Does not apply

SET SG

26.3 + 13.1μs x (n--1)

18.8 μs

Does not apply

RST SG

26.3 + 13.1μs x (n--1)

18.8 μs

Does not apply

Data Operation Instructions

Execute w/ Data Register

Instruction

Execute w/ I/O Register

Execute w/ Constant

Not Executed

80.7 μs

321.9 μs

14.3 μs

6.3 μs

DSTR1

F51

63.8 μs

140.9 μs

N/A

6.3 μs

DSTR2

F52

95.0 μs

172.2 μs

N/A

6.3 μs

DSTR3

F53

96.6 μs

173.8 μs

N/A

6.3 μs

DSTR5

F55

N/A

326.2 μs

N/A

6.3 μs

DOUT

F60

52.6 μs

329.4 μs

N/A

6.3 μs

DOUT1

F61

39.1 μs

160.1 μs

N/A

6.3 μs

DOUT2

F62

39.8 μs

116.0 μs

N/A

6.3 μs

DOUT3

F63

55.0 μs

108.1 μs

N/A

6.3 μs

DOUT5

F65

N/A

358.3 μs

N/A

6.3 μs

CMP<=>

F70

112.8 μs

354.0 μs

57.0 μs

6.3 μs

ADD

F71

456.8 μs

698.0 μs

262.0 μs

6.3 μs

SUB

F72

315.8 μs

557.0 μs

275.0 μs

6.3 μs

MUL

F73

290--2664 μs

497--2851 μs

223--2576 μs

6.3 μs

DIV

F74

742--2645 μs

1218--2851μs

720--2557 μs

6.3 μs

DAND

F75

103.7 μs

345.0 μs

55.6 μs

6.3 μs

DOR

F76

103.7 μs

345.0 μs

55.6 μs

6.3 μs

SHFR

F80

216 μs+13.4 μs times ( # of shifts)

6.3 μs

SHFL

F81

220 μs+13.4 μs times ( # of shifts)

6.3 μs

DECO

F82

56.3 μs

N/A

N/A

6.3 μs

ENCO

F83

282.0 μs

N/A

N/A

6.3 μs

INV

F84

30.0 μs

N/A

N/A

6.3 μs

BIN

F85

412.2 μs

N/A

N/A

6.3 μs

BCD

F86

746.0 μs

N/A

N/A

6.3 μs

FAULT

F20

114.0 μs

355.3 μs

72.2 μs

6.3 μs

DL305 User Manual, Rev. D

Appendix D Inst. Execution Times

F50

Appendix C Inst. Execution Times

DSTR

Appendix B DL405 Error Codes

ISG

Appendix A DL405 Error Codes

Stage Instructions

C--7

Page 351

Instruction Execution Times

DL340 Instruction Execution Times Basic Input Instructions

Appendix D Inst. Execution Times

Appendix C Inst. Execution Times

Appendix B DL405 Error Codes

Appendix A DL405 Error Codes

C--8

Instruction

Disabled by MCR

STR

0.875 μs

N/A

STR NOT

1.750 μs

N/A

AND

0.625 μs

N/A

AND NOT

1.5 μs

N/A

OR

1.125 μs

N/A

OR NOT

1.75 μs

N/A

STR T/C

0.875 μs

N/A

STR NOT T/C

1.75 μs

N/A

AND T/C

0.625 μs

N/A

AND NOT T/C

1.5 μs

N/A

OR T/C

1.125 μs

N/A

OR NOT T/C

1.75 μs

N/A

AND STR

0.75 μs

N/A

OR STR

0.75 μs

N/A

MCR

0.75 μs

N/A

MCS

1.125 μs

N/A

Comparative Contacts

Output Type Instructions

Execute

Instructions

Execute w/ Data Register

Execute w/ I/O Register

Execute w/ Constant RAM

EE / UV

Not Executed

STR

56.8 μs

95.0 μs

15.6 μs

15.6 μs

N/ A

STR NOT

56.8 μs

96.5 μs

15.6 μs

15.6 μs

N/A

AND

56.8 μs

95.0 μs

15.0 μs

15.0 μs

1.4 μs

AND NOT

56.8 μs

96.5 μs

15.6 μs

15.6 μs

1.4 μs

OR

56.8 μs

94.0 μs

15.6 μs

15.6 μs

1.4 μs

OR NOT

56.8 μs

94.0 μs

16.2 μs

16.2 μs

1.4 μs

Instruction

Execute

Not Executed

OUT

1.188 μs

1.188 μs

SET OUT

1.563 μs

1.563 μs

SET

1.625 μs

1.4 μs

RST

1.625 μs

1.4 μs

SET OUT RST

7.5 μs

7.125 μs

DL305 User Manual, Rev. D

Page 352

Instruction Execution Times

Execute w/ Data Register

Instructions

Execute w/ I/O Register

Execute w/ Constant RAM

EE / UV

Not Executed

TMR

68.1 μs

113.8 μs

22.5 μs

22.5 μs

15.7 μs

CNT

67.3 μs

97.9 μs

22.5 μs

22.5 μs

25.6 μs

SR

21.8 μs+3.8 μs times ( # of shifts)

Data Operation Instructions

Execute w/ Data Register

Instruction

Execute w/ I/O Register

8.3 μs

Execute w/ Constant

Appendix A DL405 Error Codes

Timer, Counters, and Shift Registers

C--9

Not Executed

60.6 μs

10.6 μs

1.4 μs

DSTR1

F51

24.3 μs

39.4 μs

N/A

1.4 μs

DSTR2

F52

25.0 μs

40.6 μs

N/A

1.4 μs

DSTR3

F53

96.6 μs

39.4 μs

N/A

1.4 μs

DSTR5

F55

N/A

76.8 μs

N/A

1.4 μs

DOUT

F60

18.8 μs

53.8 μs

N/A

1.4 μs

DOUT1

F61

13.1 μs

33.1 μs

N/A

1.4 μs

DOUT2

F62

16.3 μs

23.1 μs

N/A

1.4 μs

DOUT3

F63

15.6 μs

23.1 μs

N/A

1.4 μs

DOUT5

F65

N/A

59.3 μs

N/A

1.4 μs

CMP<=>

F70

30.0 μs

61.8 μs

15.6 μs

1.4 μs

ADD

F71

77.5 μs

108.0 μs

63.0 μs

1.4 μs

SUB

F72

70.6 μs

101.8 μs

57.0 μs

1.4 μs

MUL

F73

71.8 -- 540.0 μs

102.5 -- 571.2 μs

58.7 -- 526.8 μs

1.4 μs

DIV

F74

73.7 -- 568.1 μs

104.3 -- 598.7 μs

58.7 -- 553.1 μs

1.4 μs

DAND

F75

29.3 μs

60.0 μs

15.6 μs

1.4 μs

DOR

F76

31.2 μs

62.5 μs

15.6 μs

1.4 μs

SHFR

F80

18.1 μs+2.5 μs times ( # of shifts)

SHFL

F81

18.1 μs+2.5 μs times ( # of shifts)

DECO

F82

ENCO

F83

INV BIN BCD FAULT

1.4 μs 1.4 μs

15.6 μs

N/A

N/A

1.4 μs

47.5 μs

N/A

N/A

1.4 μs

F84

6.8 μs

N/A

N/A

1.4 μs

F85

48.1 μs

N/A

N/A

1.4 μs

F86

88.7 -- 326.0 μs

N/A

N/A

1.4 μs

F20

28.8 μs

60.1 μs

15.0 μs

1.4 μs

DL305 User Manual, Rev. D

Appendix D Inst. Execution Times

29.4 μs

Appendix C Inst. Execution Times

F50

Appendix B DL405 Error Codes

DSTR

Page 353

This page is a scan with no text; see it in the PDF.