Spec sheet · B & R Automation
DO135
Spec sheet12 pagesPDF 452 KB
Data sheet for the B&R 2003 DO135 (7DO135.70) screw-in digital output module with 4 FET outputs, 12 to 24 VDC, 0.1 A.
Covers · 1 model
The models it covers
Summary
What is in it
The B&R 2003 modules manual section for the DO135 (model 7DO135.70), a screw-in digital output module with 4 FET outputs for the AF101 adapter module. It gives the technical data, general information, the normal, pulse width modulation and TPU operating modes, special functions, the output circuit diagram, TB712 terminal connections and a connection example, variable declaration, access using CAN IDs, and a description of the data and configuration words.
From the sheet · read page by page
Key facts from this sheet
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Section 8.6 of a B&R 2003 modules manual covering the DO135 (model number 7DO135.70), a 4-channel digital output screw-in module. It gives technical data, operating modes, connections and the data and configuration words used to program the outputs, including access over CAN IDs.
- Device
- B&R 2003 digital output screw-in module with 4 FET push/pull outputs p. 1
- Model number
- 7DO135.70 p. 1
- Output rating
- 12 to 24 VDC, 0.1 A per output p. 1
- Terminal block
- TB712, ordered separately p. 1, 5
- Fits
- AF101 adapter module or a slot of the CP interface p. 3, 8
- Supply
- 12 to 24 VDC, protected with a 1 A slow-blow fuse; valid range 10.5 VDC < Us < 30 VDC p. 3, 5
- Switching frequency
- Max. 100 kHz p. 1
- Residual voltage
- Max. 0.6 V at 0.1 A p. 1
- Capacitive load
- Max. 20 nF p. 1
- Power consumption
- Max. 0.2 W p. 1
- Isolation and cable
- No electrical isolation (output to PCC or output to output); shielded cable required p. 2
- Operating modes
- Set per output: normal, pulse width modulation (PWM) or TPU operation p. 3
- PWM timing
- Period time unit = 250 µs * factor; PWM resolution = 125 µs * factor; standard factor 4 (1 ms units) p. 10
- Module code
- $14 p. 11
What this sheet walks you through
- Setting each output's operating mode with configuration word 14 p. 12
- Writing output states and pulse width ratios with data words 0 to 3 p. 9
- Setting the PWM period time and factor (configuration words 8 and 9) p. 10, 11
- Reading module status and supply voltage faults from configuration word 12 p. 11
- Accessing the module over CAN identifiers p. 7, 8
- Declaring module variables in PG2000 p. 6
- Wiring the outputs, shields and supply on the terminal block p. 5
Good to know
- A supply above 35 VDC for more than 5 ms damages the outputs. p. 2
- Switching large capacitive loads triggers an overcurrent warning. p. 1
- Output data cannot be packed: one CAN object is sent per screw-in module. p. 8
- B&R 2000 users must swap the data so the high byte comes first (Motorola format). p. 8
Questions this sheet answers
What terminal block does the B&R DO135 use?
The TB712, which is ordered separately. p. 1
Can the DO135 do PWM?
Yes. Each output can be set to pulse width modulation; a data word value of 32767 ($7FFF) gives 100 %. p. 3, 9
How should the DO135 supply be fused?
The 12 to 24 VDC supply should be protected with a 1 A slow-blow fuse. p. 5
The whole text · 2 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file