Spec sheet · B & R Automation
B & R Automation IF311 and IF321 Spec Sheet
Spec sheet2 pagesPDF 272 KB
Both pages are below, each with its text.
Covers · 2 models
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
This two-page B&R 2003 Modules data sheet covers two screw-in interface modules: the IF311 with one RS232 port and the IF321 with one isolated RS485/RS422 port. It gives technical data, the pin assignments of both 9 pin connectors and the IF321 bus termination switch.
- What it is
- IF311: B&R 2003 screw-in module with 1 RS232 port; IF321: 1 RS485/RS422 port, electrically isolated, network capable p. 1
- Model numbers
- IF311: 7IF311.7; IF321: 7IF321.7 p. 1
- Slot
- CP interface, slots 1, 2 and 3 p. 1
- Connector
- IF311: 9 pin D-type plug; IF321: 9 pin D-type socket p. 2
- Baud rate
- Max. 115.2 kBaud, set in software p. 1
- Distance
- IF311: 15 m at 19200 Baud; IF321: 1200 m without repeater p. 1
- Panel supply
- IF311: +5 VDC, max. 500 mA on pin 4 for simple PANELWARE controllers such as the P120 p. 1, 2
- Power consumption
- IF311: max. 0.5 W, max. 1.6 W with P120 / P121; IF321: max. 1.4 W p. 1
- Handshake lines
- IF311: RTS (pin 7) and CTS (pin 8) p. 1, 2
- Bus termination
- IF321: built-in termination resistor switched on and off p. 2
- Remote bus connector
- IF321: remote bus connector 0G1000.00-090 can be used p. 2
What this sheet walks you through
- IF311 RS232 pin assignment p. 2
- IF321 RS485 and RS422 pin assignment p. 2
- Switching the IF321 bus termination resistor p. 2
Good to know
- Wiring remote I/O networks is described in another chapter of the B&R 2003 manual, not on this sheet. p. 2
Questions this sheet answers
What is the difference between the B&R IF311 and IF321?
The IF311 has one RS232 port; the IF321 has one electrically isolated, network capable RS485/RS422 port. p. 1
How long can the cable be on an IF321?
Up to 1200 m without a repeater; the IF311 RS232 port reaches 15 m at 19200 Baud. p. 1
What is the IF311 RS232 pinout?
Pin 2 RXD, pin 3 TXD, pin 4 +5 VDC panel supply, pin 5 GND, pin 7 RTS, pin 8 CTS; pins 1, 6 and 9 are not connected. p. 2
Does the IF321 have a termination resistor?
Yes, a built-in bus termination resistor turned on and off with a switch. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
14.2 IF311 / IF321 14.2.1 Technical Data
Module IDIF311IF321
General Information Model Number
7IF311.77IF321.7Short Description
2003 interface module, 1 RS232 interface, screw-in module
2003 interface module, 1 RS485/RS422 interface, electrically isolated, network capable, screw-in module
C-UL-US ListedYesYesB&R ID Code$18
Module Type Slot Power Consumption
$16 B&R 2003 screw-in module CP Interface, slots 1, 2 and 3
Max. 0.5 W max. 1.6 W with P120 / P121 1)
Max. 1.4 WRS232RS485/RS42 2)
Standard Communication Interface Interface Type Electrical Isolation Interface - PCC Design Handshake Lines
NoYes9 pin D-type plug9 pin D-type socket
RTS, CTS, - Baudrate 2)
Max. 115.2 kBaudMax. 115.2 kBaudDistance15 m at 19200 Baud
1200 m (without repeater)
No
Yes
5 to 8 yes / no / even / odd 1/2
7/8 yes / no / even / odd 1/2
Network Capable Data Formats Data Bits Parity Stop Bits Mechanical Characteristics Dimensions 1) 2)
B&R 2003 screw-in module
Integrated power supply on pin 4 of the RS232 interface for simple PANELWARE controllers, e.g. P120. Can be configured using software.
416IF311 / IF321Chapter 3
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
14.2.2 Pin Assignments IF311
Assignment9 pin D-type plug 6915PinRS2321NCReserved2RXDReceive Signal3TXDTransmit Signal4+5 VDC /max. 500 mAPanel Supply5GNDGround6NCReserved7RTSRequest To Send8CTSClear To Send9NCReservedPinRS485RS4221NCNC2NCTXD3DATARXD4NCNC5GNDGND6+5 VDC / 50 mA+5 VDC / 50 mA7NCn_TXD8n_DATAn_RXD9NCNC
Chapter 3 B&R 2003 Modules
14.2.3 Pin Assignments IF321 Assignment
9 pin D-type socket 9651
14.2.4 Bus Termination Resistance IF321 The IF321 is equipped with a bus termination resistor. The resistance is turned on and off with a switch.
Using the remote bus connector 0G1000.00-090 is possible. Wiring remote I/O networks is described in Chapter 2 "Project Planning and Installation", section "Remote I/O Bus".
B&R 2003 ModulesIF311 / IF321417