Spec sheet · Barber-Colman
MA Series Temperature Controllers
Spec sheet10 pagesPDF 103 KB
Barber-Colman catalog pages for MA, MAP, MAQ6-6 and MB series temperature controllers, with ordering codes and parts.
What this file really is
The old site listed this file as a spec sheet for the Barber-Colman MCD-41. The file is named for the MCD-41, but the document is Barber-Colman catalog pages for MA, MAP, MAQ6-6 and MB series temperature controllers and does not mention the MCD-41.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Catalog pages from Barber-Colman Company covering its MA Series single zone temperature controllers (MAQ quarter DIN and MAE eighth DIN), MAP programmer/controllers, MAQ6-6 controllers and MB Series (MBQ and MBE) temperature controllers. Each product has a features page and an ordering information page that decodes the model number fields (size, outputs, inputs, communications, options and alarms), followed by a list of MA/MB series parts and accessories.
Its parts
- MA Series Temperature Controllers
- MAP Programmer/Controllers
- MAQ6-6 Controllers
- MB Series Temperature Controllers
- MA/MB Series Parts & Accessories
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Barber-Colman catalog pages (1250-DB-100-0-01) for the MA Series temperature controllers (MAQ quarter DIN and MAE eighth DIN), the MAP programmer/controller, the MAQ6-6 actuator positioning controller and the MB Series (MBQ and MBE). They give features, ordering codes and a parts and accessories list. The MCD-41 is not named in these pages.
- Type
- MA Series: microprocessor based single zone temperature controllers with Touch-Tune automatic tuning p. 1
- Sizes
- MAQ quarter DIN (96 mm square); MAE eighth DIN (48 mm W x 96 mm H) p. 2
- MA inputs
- Thermocouple types K, J, R, S, B, T, PL II and C; PLT 100 DIN RTD; 4 to 20 mAdc; 0 to 5, 1 to 5 and 0 to 10 Vdc p. 2
- MA outputs
- Relay contact, non-contact voltage (for SSR), 4 to 20 mAdc, 2 to 12 mAdc or triac; optional second output or alarm 2 p. 2
- Communications
- Optional RS-485 (MAE versions for 120 Vac or 240 Vac only) p. 2
- Insta-Set memory
- Optional memory for 8 sets of setting values, called by external switch; MACS unit links up to 32 controllers p. 1, 2
- Heater burnout
- MA option calibrated 5, 10, 20, 30, 40 or 50 Amps p. 2
- MA alarm 1
- High or low deviation, deviation band, deviation range band, process alarm, with or without standby p. 2
- MAQ options
- MAQ only: auto/manual, remote setpoint (4 to 20 mA or 1 to 5 Vdc), process variable output (4 to 20 mA) p. 2
- Depth
- MA Series less than 3-1/2 in. deep p. 1
- MAP programmer
- 10 patterns of 10 steps, linkable to 100 steps; step time 0 to 99 hours 59 minutes p. 3
- MAP outputs
- Optional 7 open collector time signal outputs (user supplied 50 mA 24 Vdc max.); RS-485 at 1200 to 9600 bps p. 4
- MAQ6-6
- Quarter DIN controller with electric actuator slidewire feedback; accepts 100 to 1.2K Ω feedback pot p. 5
- MB Series
- Low cost autotuning MBQ and MBE controllers for input ranges up to 999; accuracy ±0.3% +1 digit p. 7
What this sheet walks you through
- Ordering an MA Series controller by model code p. 2
- MAP programmer/controller features and ordering p. 3, 4
- Ordering the MAQ6-6 actuator positioning controller p. 5, 6
- MB Series features and ordering p. 7, 8
- Parts and accessories for MA and MB controllers p. 9, 10
Good to know
- MA heater burnout needs output 1 option 1, 2 or T. p. 2
- The 4 to 20 mAdc and 2 to 12 mAdc second outputs are not available on the MAE. p. 2
- MB heater burnout calibration does not apply with current output 1 or the output 2 and alarm 2 option. p. 8
- MB Series controllers are meant for input ranges that do not exceed 999. p. 7
Questions this sheet answers
What sizes do Barber-Colman MA controllers come in?
MAQ is quarter DIN (96 mm square) and MAE is eighth DIN (48 mm wide by 96 mm high). p. 2
Which sensors can a Barber-Colman MA controller read?
Thermocouple types K, J, R, S, B, T, PL II and C, a PLT 100 DIN RTD, 4 to 20 mAdc current, or 0 to 5, 1 to 5 or 0 to 10 Vdc voltage. p. 2
How many MA controllers can a MACS switch unit connect?
As many as 32 separate controllers. p. 1
How many program steps does the Barber-Colman MAP hold?
Up to 10 patterns of 10 steps each, or patterns linked up to 100 steps. p. 3
Is RS-485 available on the MA Series?
Yes, as an ordering option; on the MAE it is ordered for 120 Vac or 240 Vac only. p. 2