Spec sheet · Crydom
Series 1 480 VAC
Spec sheet5 pagesPDF 735 KB
Datasheet for Crydom Series 1 480 VAC panel mount solid state relays, 12A to 90A, including the 50A AC-controlled A4850.
Covers · 1 model
The models it covers
Summary
What is in it
Crydom's datasheet for the Series 1 480 VAC panel mount solid state relays, with SCR outputs rated 12A to 90A at 80-530 VAC and DC (D prefix) or AC (A prefix) control, including the A4850 (50A, 90-280 VAC control). It gives product selection, output, input and general specifications, notes, wiring diagram, mechanical drawing, thermal derating, agency approvals, safety warnings and environmental information.
From the sheet · read page by page
Key facts from this sheet
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Crydom data sheet for the Series 1 480 VAC panel mount units with SCR output, in DC control (D prefix) and AC control (A prefix) models up to 90A. It gives product selection, output, input and general specifications, notes, agency approvals and safety warnings. Its selection table prints A4850 under both the 50A and the 75A columns, so the current rating of the A4850 is not stated here.
- Type
- Series 1 480 VAC panel mount unit with SCR output for heavy industrial loads p. 1, 4
- Load voltage
- 80-530 VAC p. 1
- Control input
- A prefix: AC control, 90-280 Vrms (60Hz); 2.0 mA @ 120 Vrms, 4.0 mA @ 240 Vrms p. 2
- Output switching
- Series offers zero-crossing (resistive loads) or random-fire (inductive loads) output p. 1
- Terminals
- Screw and saddle clamps furnished, unmounted; 6-32 screws 10 in/lbs, 8-32 and 10-32 screws 20 in. lbs. p. 2
- Weight
- 3 oz (86.5g) typical p. 2
- Encapsulation
- Thermally conductive epoxy p. 2
- Input circuit
- Active current limiter in the input circuitry p. 2
- Series models
- DC control: D4812, D4825, D4850, D4875, D4890; AC control: A4812, A4825, A4850, A4890 p. 1
- Agency approvals
- Files E116949, LR81689 and 10143 UG (not applicable to -B and 4D) p. 3
What this sheet walks you through
- Choosing a model by control voltage and current p. 1
- Output, input and general specifications p. 1, 2
- Safety warnings for installing and handling the unit p. 4
Good to know
- Heat sinking is required; derating curves are given on page 3 of the sheet. p. 2
- All parameters are at 25°C unless otherwise specified. p. 2
- The 50A model has double faston pairs, and both pairs must be connected. p. 2
- Disconnect all power before installing or working on the unit, and replace all covers before turning power on. p. 4
- The side panels may be hot; let the unit cool before touching it. p. 4
Questions this sheet answers
What control voltage does the Crydom A4850 need?
A prefix models are AC controlled with 90-280 Vrms (60Hz) on the input. p. 2
What load voltage can a Crydom Series 1 480 VAC unit switch?
80-530 VAC. p. 1
Does the Crydom A4850 need a heat sink?
Yes, the sheet says heat sinking is required and refers to its derating curves. p. 2
How tight should the Crydom Series 1 terminal screws be?
6-32 screws 10 in/lbs; 8-32 and 10-32 screws 20 in. lbs. p. 2