This is a four-page Eaton Cutler-Hammer catalog section from July 2007 on AEGIS powerline filters, series surge and noise filters for critical electronic loads such as PLCs. It covers the AEGIS-HW hardwired filter that includes the AGSHWCH120N15XC, along with the AEGIS-VL, AEGIS+ and AEGIS-PR versions. It gives features, let-through voltages, a specification table and the catalog numbering systems.
- What it is
- AEGIS-HW hardwired series surge filter for critical loads, made in 3, 5, 10, 15 or 20 ampere models p. 1, 4
- Catalog number
- AGSHW CH, voltage code 120N, current capacity 15, X, option C = Form C contact for remote monitor p. 4
- Current rating
- 15 ampere model: 15 amperes UL/CSA, 16 amperes CE p. 4
- Input voltage
- AEGIS-HW: 120, 220, 240 Vac, single-phase, 50/60 Hz; this model has voltage code 120N p. 3, 4
- Protection modes
- L-N, L-G, N-G (normal and common mode) p. 2, 3
- Surge current
- 45.5 kA per phase (up to 45,500 amperes) p. 2, 3
- Noise attenuation
- 75 dB at 100 kHz; filter bandwidth 10 kHz to 100 MHz p. 2, 3
- MCOV
- AEGIS-HW: 150, 320 volts p. 3
- Response time
- Less than 1 nanosecond p. 3
- Operating temperature
- AEGIS-HW: -40 to +50 °C p. 3
- Let-through voltage
- AEGIS-HW, L-N: 6 V on A3 ringwave (600 V, 200 A); 9.6 V on B3 ringwave (600 V, 500 A); 70 V on B3/C1 combination wave (600 V, 300 A) p. 2
- Mounting
- AEGIS-HW: DIN-Rail, J-Rail or flange mounting p. 2
- Monitoring
- Status indicator lights; thermal cut-off protection (AEGIS-HW only); optional Form C relay contacts for remote monitoring p. 2, 3
- Approvals
- The catalog lists UL 1449, UL 1283 and CSA for AEGIS-HW p. 3
What this sheet walks you through
- Decoding AEGIS-HW, AEGIS-VL and AEGIS+ catalog numbers p. 4
- Comparing AEGIS-HW, AEGIS-VL and AEGIS+ specifications p. 3
- How the series hybrid filter design protects line, neutral and ground p. 2
- IEEE C62.41 test waveforms before and after filtering p. 3
- Which loads to protect with a powerline filter p. 1
Good to know
- In the catalog numbers, the 230 V code applies to 220 and 240 volt applications. p. 4
- The let-through voltage figures come from static testing. p. 2
Questions this sheet answers
What does the C at the end of AGSHWCH120N15XC mean?
In the AEGIS-HW catalog numbering, option C is a Form C contact for remote monitoring; S is standard. p. 4
What is the amp rating of the AGSHWCH120N15XC?
It is a 15 ampere model; the catalog notes the 15 ampere model is 15 amperes UL/CSA and 16 amperes CE. p. 4
How much surge current can the AEGIS-HW handle?
The specification table gives 45.5 kA per phase total peak surge current. p. 3
Can the AEGIS-HW filter mount on a DIN rail?
Yes, the AEGIS-HW offers DIN-Rail, J-Rail or flange mounting. p. 2
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-21 Critical Load Surge Filter July 2007
AEGIS Powerline Filters
AEGIS Powerline Filters
Application Description The AEGIS is the ideal protection solution for your critical loads and facilities.
Loads
- Programmable controllers (PLCs).
- Scanning devices.
- ATMs (Automatic Teller Machines).
- Cash registers.
AEGIS Solutions
- Alarm systems.
Lightning Protection for ac Powerline Applications (1-, 2-, 3-Phase Applications to 100 Amperes)
- Microprocessor-controlled
Product Description Eaton’s Cutler-Hammer AEGIS solutions are specifically designed to protect expensive electronics from the hazards that exist within a facility. This critical load protection is effective at reducing harmful surges and noise. Applying this high performance series powerline filter at your critical loads results in “clean” power entering the electronics and reduction of “soft” errors, operational malfunction, and damage to components.
Standards and Certifications Cutler-Hammer products are designed in accordance with ANSI/IEEE C62.41 (1991) recommended spectrum of transient waveforms. The AEGIS protects against all ringing and impulse disturbances.
OEM products.
- Robotics.
- CAD/CAM systems.
- Control equipment.
- Medical electronics and devices.
PLC manufacturers and service technicians recommend the use of surge suppressors and filters to prevent downtime and equipment damage due to surges and electrical line noise. One study shows failure to protect sensitive electronic loads costs American manufacturing, commercial and service industries over $39 billion per year in lost time and revenue. Preventing these losses is a major cost-saving opportunity.
AEGIS Powerline Filters Protect Against the Full Spectrum of Transient Disturbances AEGIS filters the entire sine wave and is effective against both frequently occurring low energy and occasional high energy transients. High energy transients can create immediate damage, while low energy transients cause microprocessor failure over time.
Hardwired Surge Filter that Protects Critical Loads (3, 5, 10, 15 or 20 Ampere Models)
CA08101001E
10
Why Should Sensitive Electronic Loads be Protected?
For more information visit: www.eaton.com
AEGIS VL Hardwired Critical Load Filter 1, 3 and 5 Ampere Modules Only
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Critical Load Surge Filter
10-22
July 2007
AEGIS Powerline Filters
Features, Benefits and Functions
Standards and Certifications
Table 10-14. AEGIS Powerline Filters Features and Benefits
Based on ANSI/IEEE C62.41, 1991 and C62.45, 1992.
Features
Benefits
Unique Series Hybrid Design (AEGIS-HW, AEGIS+)
- Protection against high and low energy transients and noise.
- The tracking filter reacts instantly to changes in frequency and voltage, regardless of phase angle, magnitude or polarity.
- Active at all times, providing more protection than a conventional surge suppressor.
- Extends the life of your microprocessors by eliminating degrading power disturbances.
High Performance Suppression Capabilities (AEGIS-HW, AEGIS+)
10
AEGIS-HW and AEGIS-PR have up to 45,500 amperes of surge current suppression and 75 dB of noise attenuation at 100 kHz. This guarantees a superior level of protection and reliability. AEGIS+ has additional protection up to 160 kA/phase.
Status Monitoring Lights (AEGIS-HW, AEGIS+)
No more testing or guessing whether your unit is working properly. Filter indicator lights expedite your troubleshooting efforts during downtime situations.
5-Year Downstream Equipment Warranty (AEGIS-HW only)
Eaton provides a 5-year Extended Warranty on the microprocessor power supply protected by AEGIS. No other manufacturer offers this level of assurance in backing up its claim of product performance, quality and reliability.
Value (AEGIS-HW, AEGIS+)
AEGIS provides superior value when considering the level of performance and benefits offered. It truly delivers the best “bang” for your dollar.
Optional Remote Monitoring Capabilities (AEGIS-HW, AEGIS VL, and AEGIS+ only)
Observe all your operations on a remote basis, including the power protection devices used to safeguard your critical and sensitive electronic loads.
Table 10-15. Let-Through Voltages (L-N) Description
AEGIS-HW (L-N Mode)
Category A3 Ringwave (600 V, 200 A)
Category B3 Ringwave (600 V, 500 A)
9.6 V
Category B3/C1 Combination 70 V (Impulse) Wave (600 V, 300 A) (206 V, dynamic at 90°) Static testing.
DIN-Rail, J-Rail or Flange Mounting Connections The DIN-Rail mountable enclosures greatly (AEGIS-HW only) reduce installation time, effort and cost. This unique container is the preferred choice among OEMs and contractors. Thermal Cut-Off Protection (TCO) (AEGIS-HW only)
Thermal fuse improves indication, monitor and control during fault conditions.
AEGIS Hybrid Series Powerline Filters Primary Transient Status High High Series Voltage Surge Suppression Frequency Blocking Performance Secondary Indicator Lights TVSS Tracking Filter Capacitor Inductors (TVSS) Power Input
LNormal ModeNormal ModeLED
Optional Form C Contacts Power Output Form C
N GL NCommon ModeCommon ModeG
Figure 10-13. 3-Wire Design has Normal and Common Mode Protection (L-N, L-G, N-G) Option for AEGIS and AEGIS+.
For more information visit: www.eaton.com
CA08101001E
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
TVSS, Power Conditioning, PF Capacitors & Harmonic Filters 10-23 Critical Load Surge Filter July 2007
AEGIS Powerline Filters
B3/C1 Combination (Impulse) Wave (6000 V, 3000 A)
8000 6000
0 -2000 -4000 -6000
400 300 200 100 0 -100 -200 -300 -400
2 Microseconds/Division
Volts2000VoltsVolts4000
7000 6000 5000 4000 3000 2000 1000 0 -1000 -2000 -3000 -4000
2 Microseconds/Division
Before
Volts
A3 Ringwave (Line-to-Neutral) (6000 V, 200 A)
700 600 500 400 300 200 100 0 -100 -200 -300 -400
20 Microseconds/ Division
After
Before
20 Microseconds/ Division
After
Figure 10-14. IEEE C62.41 (1991) Test Waveforms for AEGIS-HW and PR Versions
Product Specifications Table 10-16. Specifications Application
AEGIS-HW 2 W&G Grounded Systems
AEGIS-VL 2 W&G Grounded Systems
AEGIS+ 1-, 2- and 3-Pole Systems
Input Voltage Single-Phase
120, 220, 240 Vac, single-phase
120, 220, 240 Vac, single-phase
120, 208, 240, 400, 480, 600 Vac; Wye, Delta and International systems
Amperage
3, 5, 10, 15, 20 amperes
1, 3, 5 amperes
20, 30, 50, 70, 100 amperes
Frequency50/60 Hz50/60 Hz50/60 HzProtection ModesL-N, L-G, N-GL-N, L-G, N-G
L-N, L-G, and N-G modes (Wye system); L-L and L-G (Delta system)
MCOV150, 320 volts150, 320 volts
150, 320, 420 volts (Wye system) 300, 550, 680 volts (Delta system)
Noise Attenuation Normal Mode: Common Mode:
75 dB at 100 kHz 50 dB at 5 MHz
75 dB at 100 kHz 50 dB at 5 MHz
65 dB at 100 kHz 40 dB from 60 kHz to 5 MHz
Filter Bandwidth10 kHz to 100 MHz10 kHz to 100 MHz10 kHz to 100 MHz
Total Peak Surge Current
45.5 kA per phase
39 kA per phase
40, 80 or 160 kA per phase
Operating Temperature-40º to +50°C-40º to +50°C-40º to +40°CResponse TimeLess than 1 nanosecondLess than 1 nanosecondLess than 1 nanosecondOptionsForm C relay contactsN/A
Form C relay contacts; NEMA 3R/4X container; disconnect switch; 40 kA or 160 kA
Agency ApprovalsUL 1449, UL 1283, CSAUL 1449, UL 1283, CSA
CE, UL 1449 (20 to 70 amperes up to 480 volts)
Warranty
5 years plus downstream connected 5 years warranty
CA08101001E
For more information visit: www.eaton.com
5 years
10
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
10-24
TVSS, Power Conditioning, PF Capacitors & Harmonic Filters Critical Load Surge Filter July 2007
AEGIS Powerline Filters
Product Selection Table 10-17. AEGIS-HW (Hardwire Application) Catalog Numbering System
Table 10-19. AEGIS+ Catalog Numbering System
AGSHW CHXAGS+ CH Voltage CodeVoltage CodeCurrent Capacity120N 230L03 05 10 15 20
Options S = Standard C = Form C contact for Remote Monitor
Model rated at 15 amperes UL/CSA = 16 amperes CE.
Note: 230 V applies to 220 and 240 volt applications.
10
Table 10-18. AEGIS-VL (Hardwire Application) Catalog Numbering System
120N = 120 (1-Phase, 2W + G) 208Y = 208Y/120 (3-Phase, 4W + G) 240S = 240/120 (2-Phase, Delta 2W + G) 230L = 230 (1-Phase, 2W + G) 240D = 240D (3-Phase, Delta 3W + G) 400Y = 400Y/230 (3-Phase, 4W + G) 480Y = 480Y/277 (3-Phase, 4W + G) 480D = 480D (3-Phase, Delta 3W + G) 600Y = 600/347 (3-Phase, 4W + G) 600D = 600 (3-Phase, 3W + G)
AGSVLOperating CurrentVoltage CodeCurrent Capacity120N 230L1 3 5020 030 050070 100
Surge Current Rating/Phase 040 080 160 Enclosure R4X = NEMA 4X Container RSD = Disconnect Switch (with NEMA 12 Container) Blank = Caseless Options (if required) CXX = Form C contacts (remote monitor)
400/230 valid for 380/220 and 415/240 per IEC. Contact factory for
resistive ground applications.
Note: 230 V applies to 220 and 240 volt applications.
Table 10-20. AEGIS Price List Catalog Number
Price U.S. $
AGSHWCH120N03XC AGSHWCH120N03XS AGSHWCH120N05XC AGSHWCH120N05XS AGSHWCH120N10XC AGSHWCH120N10XS AGSHWCH120N15XC AGSHWCH120N15XS AGSHWCH120N20XC AGSHWCH120N20XS AGSHWCH230L03XC AGSHWCH230L03XS AGSHWCH230L05XC AGSHWCH230L05XS AGSHWCH230L10XC AGSHWCH230L10XS AGSHWCH230L15XC AGSHWCH230L15XS AGSHWCH230L20XC AGSHWCH230L20XS AGSPRCH120N15HG AGSPRCH120N15HW AGSPRCH120N15XX AGSPRCH230L15HG AGSPRCH230L15HW AGSVL120N1 AGSVL120N3 AGSVL120N5 AGSVL230L1 AGSVL230L3 AGSVL230L5
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 22-CD For more information visit: www.eaton.com
CA08101001E