Spec sheet · Emerson
Power Supplies: SDN-C Performance DIN Rail Series
Spec sheet8 pagesPDF 1.1 MB
SolaHD catalog pages for the SDN-C Performance DIN rail power supplies: single and three phase specifications, dimensions, mounting.
What this file really is
The old site listed this file as a spec sheet for the Sola SDN 4-24-100, SDN 5-24-100 and 3 more models. The file is named for the SDN 4-24-100, but the document is catalog pages for the SDN-C Performance DIN Rail Series and does not list the SDN 4-24-100 or SDN 5-24-100 (without the C).
Names · 2 models
The models it names
Filed with · 3 models
Also filed with these models on the old site
Summary
What is in it
SolaHD catalog pages for the SDN-C Performance DIN Rail Series of power supplies for industrial automation, process control, hazardous locations and marine use. They list certifications and features, the LED status conditions, full specifications for the single phase models (SDN 5-24-100C, SDN 10-24-100C, SDN 16-12-100C, SDN 20-24-100C, SDN 40-24-100C) and three phase models (SDN 5-24-480C to SDN 40-24-480C), reliability figures, dimensions and DIN rail or panel mounting.
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Emerson data sheet for the SolaHD SDN-C Performance DIN Rail Series power supplies. It covers the single-phase SDN 5-24-100C, SDN 10-24-100C, SDN 16-12-100C, SDN 20-24-100C and SDN 40-24-100C and the three-phase SDN 5-24-480C, SDN 10-24-480C, SDN 20-24-480CD and SDN 40-24-480C; the SDN 4-24-100 is not named. It gives input and output ratings, protection, status signals, environmental limits, dimensions and DIN rail or panel mounting.
- Device
- SDN-C DIN rail power supplies with 24 V or 12 V dc output, single-phase and three-phase models p. 1, 3, 5
- Input, single-phase
- 100 - 240 Vac (85-264 Vac), 43 - 67 Hz, or DC input p. 3
- Output, 24 V models
- 24 V, adjustable 23.5-28.5 Vdc, set at 24.5 V ± 1% p. 3
- DC OK relay
- N.O. contact rated 200mA/50 Vdc; active when Vout > 18.5 Vdc +/-5% p. 4
- Operating temperature
- -40°C to +60°C full power, derated linearly to 75% power from +60°C to 70°C p. 3, 5
- Mounting
- Snap-on to DIN TS35/7.5 or TS35/15 rail; optional panel mount bracket kits SDN-PMBRK3 and SDN-PMBRK2 p. 4, 8
- SDN 10-24-100C size
- SDN 10-24-100C: 4.85 x 2.36 x 4.36 in (H x W x D) p. 7
- Status LEDs
- 3 status LEDs: Input, Output, Alarm p. 4
- PowerBoost peak
- 1.5 x nominal current for more than 4 seconds minimum p. 3
- Protection
- Continuous short circuit, overload and open circuit; overtemperature alarm and shutdown with auto-recovery p. 3
- Parallel operation
- Single or parallel selected by a front switch; only the 40A models use active paralleling p. 3
- Input, three-phase
- Three-phase models: 380 - 480 Vac (320 - 540 Vac) or 600 Vdc (+/- 50Vdc) p. 5
- Case
- Fully enclosed metal housing, IP 20 touch proof; no internal fan p. 2, 4
- Storage temperature
- -40°C to +85°C p. 3
What this sheet walks you through
- Reading the Input, Output and Alarm LED status conditions p. 2
- Comparing single-phase model ratings p. 3, 4
- Comparing three-phase model ratings p. 5, 6
- Checking dimensions of each model p. 7
- Mounting on DIN rail or a panel with bracket kits p. 8
Good to know
- The input branch fuse or circuit breaker is to be provided by the installer. p. 4
- Use only one copper wire per screw terminal. p. 4
- Mounted sideways or front side up, operation is limited to 50% load. p. 3
- The manual states that installation requirements for use in hazardous locations are in the user manual. p. 1
- Redundant operation needs an external Redundancy module. p. 3
Questions this sheet answers
What input voltage does the SDN 10-24-100C take?
It is a single-phase SDN-C model; these take 100 - 240 Vac (85-264 Vac) at 43 - 67 Hz. p. 3
Can the output voltage of an SDN-C 24 V supply be adjusted?
Yes, the 24 V models adjust from 23.5 to 28.5 Vdc. p. 3
What is the DC OK relay rating on SDN-C power supplies?
A normally open contact rated 200mA/50 Vdc. p. 4
Can two SDN-C power supplies be run in parallel?
Yes, single or parallel operation is set with a front switch; redundant operation needs an external Redundancy module. p. 3
The whole text · 1 part
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file