Specification sheet for the Eurotherm TE10S solid state relay, offered for 16, 25, 40 and 50 amp loads at 240 and 480 volt. It gives the electrical, control input and installation data, the ordering code, and the part numbers of spare fuses and fuse holders.

Device type
Self-powered solid state relay with no moving parts, a replacement for mechanical contactors, with DIN rail mounting p. 1
Current ratings
16A, 25A, 40A and 50A at 45°C p. 2
Load voltage
48 to 240 Vac or 96 to 500 Vac (+10%, -15%); 47 to 63 Hz p. 2
Control inputs
LGC 8 to 32Vdc, LAC 32 to 48Vac or HAC 100 to 240Vac; polarity insensitive; green LED shows the command signal p. 2
Firing mode
Logic firing (ON/OFF) with zero voltage switching p. 2
Loads and wiring
Constant resistance or shortwave infrared elements; single phase with 1 unit, three phase with 2 or 3 units p. 1, 2
Ordering options
Input LGC, LAC, HAC, PDS1 or PDS2; voltage 120V, 240V, 480V or 500V; fuse FUSE, MSFU or NONE p. 3
Partial load failure
Option PLF (relay open in alarm) or IPF (relay closed in alarm); discrimination 1 element in 6 for single phase load p. 2, 3
Surge withstand
500V/μs and 100A/μs; at least 400A for 10ms p. 1
Dimensions
115H x 93D mm; width 35 (16A), 53 (25A), 88 (40A) or 105 mm (50A), wider with PLF/IPF p. 2
Weight
16A 320g, 25A 500g, 40A 770g, 50A 880g p. 2
Temperature
Operating 0°C to 45°C (up to 60° with derating); storage -10°C to 70°C; natural convection cooling p. 2
Fuse and holder parts
FU1038/16A/00, FU1038/25A/00, FU1451/40A/00, FU2258/50A/00; with microswitch MSFU1451/16A, MSFU1451/25A, MSFU1451/40A, MSFU2258/50A p. 3
Leakage current
Less than 30mA p. 2

What this sheet walks you through

  • Building the ordering code: current, input, voltage, language, partial load failure and fuse p. 3
  • Wiring single phase and three phase loads p. 1, 2
  • Derating the maximum current with ambient temperature p. 3
  • Choosing a spare fuse and holder for each current rating p. 3
  • Using PDS to control the relay and read back heater break or load current alarms p. 3

Good to know

  • Replacement fuses are marked with a higher current rating than the thyristors; this does not mean a higher current is allowed. p. 3
  • High speed fuses are not recommended for shortwave infrared (SWIR) loads. p. 3
  • Not suitable above 2000m or in corrosive or explosive atmospheres without further protection. p. 2
  • Electrically conductive pollution must be kept out of the cabinet the unit is mounted in. p. 2
  • PDS inputs are not available together with the PLF or IPF partial load failure option. p. 3

Questions this sheet answers

Can the TE10S control a three phase heater?

Yes. Three wire star or delta loads use two units on two limbs; four wire star with neutral or six wire open delta loads use three units. p. 2

What control signal does the TE10S accept?

LGC 8 to 32Vdc, LAC 32 to 48Vac or HAC 100 to 240Vac, depending on the input ordered. The input is polarity insensitive. p. 2

Does the TE10S need a separate supply for its electronics?

No. It is self powered, so there is no wiring for an electronics supply. p. 1

Can the TE10S detect a broken heater element?

With the partial load failure option it detects a rise in load impedance when part of the heating load fails or disconnects, down to 1 element in 6 on a single phase load. p. 2

Can the TE10S run above 45°C?

It operates from 0°C to 45°C, and up to 60° with derating; the sheet's derating chart shows maximum current against ambient temperature. p. 2, 3

The file

Size and text

Pages4
PDF200 KB
TextText from the PDF itself.

Every page · 4

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Eurotherm TE10S Spec Sheet

The text of page 1, from the PDF itself

TE10S MODEL

Solid State Relay Specification Sheet

Rated up to 50A at 45°C

A compact, low cost, 240 and 480 volt solid state relay for 16, 25, 40 and 50 amps, rated at 45°C.

240V and 480V options

Easy replacement for mechanical contactors

AC and DC logic input

Partial load failure detection

Simple installation and maintenance

Mechanical contactors in heating applications may operate three million times per year. The lifetime of such contactors is 1 to 3 years, so they need to be replaced several times during the life of an industrial machine. Alternatively the TE10S from Eurotherm® has no moving parts and will not wear out. Its wiring is similar to contactors and it has simple DIN rail mounting. It takes a broad range of AC and DC inputs with a front face LED to show the control signal to help commissioning and diagnostics.

Extend the life of your heaters Tests performed by a well known heater supplier have shown that heaters can last up to 7 times longer when driven by a solid state relay. Faster on/off cycle times cause less thermal expansion and contraction of the heaters to reduce breakage due to fatigue and thermo-mechanical stress. Your savings include the cost of the heaters, installation costs, scrap reduction and lost production. The TE10S is able to detect element failures to heaters with multiple elements in parallel.

Why choose a fully assembled unit from Eurotherm? In short, it gives you a well designed, tested and compact solution. The TE10S is assembled in an ISO9001:2000 registered factory, follows international safety regulations and comes with a 2 year warranty. The alternative would be to take a solid state device, heatsink, thermal transfer compound, load and control terminals, protection covers mounting hardware, design regulations and then find the labour to put them all together. Self assembled installations tend to use more panel space, whether they are mounted directly on the cubicle metal work or on oversized heatsinks. Detailed thermal analysis allows Eurotherm to supply the most compact unit for a given current.

Tough enough for infrared applications The TE10S uses two thyristors so it can withstand fast voltage and current changes (500V/μs and 100A/μs) and momentary over-current (at least 400A for 10ms). The TE10S is tough enough to handle the current surges that arise when you burst fire short-wave infrared elements.

Simple wiring for single and three phase loads No wiring for electronics supply (self powered). Can be used for single phase loads (1 x TE10S), three phase loads (3 x TE10S) firing independently.

  • EUROTHERM® FLEXIBLE SOLUTIONS•
Page 2 of Eurotherm TE10S Spec Sheet

The text of page 2, from the PDF itself

CE marking TE10S Units are CE marked to show that they meet the essential requirements of the European Low Voltage Directive. No exposed parts are at a dangerous voltage. Eurotherm certificates that the TE10S units have successfully passed the EMC tests and enable the system which incorporates them to comply with the EMC Directive as far as the TE10S is concerned. An EMC installation guide (part no. HA025464) is available on request.

SPECIFICATION Current
16A, 25A, 40A and 50A at 45°C. Under certain conditions e.g. lower ambient temperature these units may be run at slightly higher currents. Consult your local Eurotherm engineer
Voltage
48 to 240 Vac (+10%, -15%) or 96 to 500 Vac (+10%, -15%)
Supply frequency
47 to 63 Hz
Environmental Humidity
IP20 (IEC 529)
Isolation
All distances comply with IEC 644 Control signals isolated from power, tested to 3600Vac. Isolation to earth tested to 2000Vac

Electrical protection:

Load Load type
Constant resistance or shortwave infrared elements

Single phase connection: Three phase connection:

Line-to-line or line-to-neutral Three wire star or delta - two units control two limbs of the load Four wire star with neutral or six wire open delta - three units together

Firing mode
Logic firing (ON/OFF) with zero voltage switching
Leakage current
Less than 30mA
Storage temperature
-10°C to 70°C
Cooling
Natural convection
Operating temperature
0°C to 45°C (up to 60° with derating)
Safety standards
EN61010, installation category 3 (voltage transients must not exceed 4.0KV)
Atmospheres
Electrically conductive pollution must be excluded from the cabinet in which this controller is mounted. This product is not suitable for use above 2000m or in corrosive or explosive atmospheres without further protection

Polarity insensitive + and - can be crossed Command signal indication by green LED LGC 8 to 32Vdc (ON>8V, OFF<2V) LAC 32 to 48Vac, (ON>30V, OFF<5V) HAC 100 to 240Vac (ON>85V, OFF<10V) Current:

LGC 9mA dc (self limiting). (ON>9mA, OFF<0.5mA)

European directives Electromagnetic compatibility Immunity test standards: EN61000-4, EN61000-4-4, PrEN 61000-4-3 Emission test standard: EN55011, EN50081-2 without external filter (optional parallel filters must be fitted for 2 phase control pf 3 phase loads)

Option Partial load failure detection:

Detects an increase in load impedance due to failure or disconnection of part of the heating load

Safety
Complies with Low Directive 73/23/EEC dated 19/2/73 amended by Directive 93/68/EEC dated 22/7/93 (product installed and used in compliance with its user manual)
CE marking
TE10S products carry the CE mark in compliance with the European Low Voltage Directive. A CE declaration of conformity is available on request

Discrimination: 1 element in 6 for single phase load Installation Dimensions (mm):

Mounting: Inter-unit spacing: Internal bus bar: Power terminals: Control terminals: Weight:

16A 115H x 35W x 93D (53W with PLF/IPF); 25A 115H x 53W x 93D (70W with PLF/IPF); 40A 115H x 88W x 93D (105W with PLF/IPF); 50A 115H x 105W x 93D (123W with PLF/IPF) Vertical on DIN rail 10mm for full current operation 8mm2 copper bars Cable sizes 1.5 to 16mm2. Tightening torque 1.2Nm Cable size 0.5 to 1.5mm2. Terminals are removable for easy maintenance 16A 320g, 25A 500g, 40A 770g, 50A 880g

RC snubber network External high speed fuse (to be ordered separately)

Input

Voltage
5 to 95% non condensing

Enclosure protection:

Page 3 of Eurotherm TE10S Spec Sheet

The text of page 3, from the PDF itself

Ordering code 123546TE10SCurrent116A 25A 40A 50A004

LGC Universal DC LAC 48 VAC input HAC 100-240 VAC PDS1 PDS (1) Heater Break Detect PDS2 PDS (1) Current Monitoring

16 amps 25 amps 40 amps 50 amps

2Input3VoltageLanguage

ENG English FRA French GER German

Partial load failure 00 None PLF Relay open in alarm IPF Relay closed in alarm

Fuse

6

(1) PDS (not available with PLF/IPF) uses the same two wires to control the switching of the TE10S and to feedback load status. PDS Heater Break Detect will transmit the power demand signal to a TE10S typically from a 2200 Series controller and read back a heater break alarm. Similarly, PDS Current Monitoring will transmit the power demand signal to a TE10S and read back load current, open and short circuit alarms.

120V 120 volts 240V 240 volts 480V 480 volts 500V 500 volts

Option

5

FUSE Fuse without microswitch MSFU Fuse with microswitch NONE No fuse *

  • High speed fuses are not recommended for SWIR loads

Please note that replacement fuses are marked with a higher current rating than the thyristors. This allows correct operation at elevated temperatures and does not imply that higher current is permissible.

SPARE FUSE AND HOLDER Current rating amps 16 25 40 50

SPARE FUSE

Fuse and holder assembly FU1038/16A/00 FU1038/25A/00 FU1451/40A/00 FU2258/50A/00

Fuse and Holder with Microswitch MSFU1451/16A MSFU1451/25A MSFU1451/40A MSFU2258/50A

Current rating amps 16 25 40 50

Fuse holder dimensions

Fuse rating amps 20 32 50 63

Fuse number CH260024 CH260034 CH330054 CS173087U063

Fuse Trip with Indicator CS176513U020 CS176513U032 CS176513U050 CS176461U063

Current derating IN - Nominal current of TE10S at 45°C

60dIN = 50A 50HabLI(A) Maximum CurrentIN = 40Ac P40 30IN = 25A20IN = 16A10Dimensions (mm)FU1038Fuse-holder FU1451FU2258Height (H)8195124Width (L)17.52635Depth (P)688690 4a-2b7.57.5-c384554d36.540.5420 202530354045

T(°C) - Ambient temperature

505560

Page 4 of Eurotherm TE10S Spec Sheet

The text of page 4, from the PDF itself

Eurotherm: International sales and service Understanding and providing local support is a key part of Eurotherm's business. Complementing worldwide Eurotherm offices are a whole range of partners and a comprehensive technical support team… to ensure you get a service you will want to go back to. AUSTRALIA Sydney Eurotherm Pty. Ltd. T (+61 2) 9838 0099 F (+61 2) 9838 9288 E info.au@eurotherm.com

FRANCE Lyon Eurotherm Automation SA T (+33 478) 664500 F (+33 478) 352490 E info.fr@eurotherm.com

IRELAND Dublin Eurotherm Ireland Limited T (+353 1) 4691800 F (+353 1) 4691300 E info.ie@eurotherm.com

SPAIN Madrid Eurotherm España SA T (+34 91) 6616001 F (+34 91) 6619093 E info.es@eurotherm.com

AUSTRIA Vienna Eurotherm GmbH T (+43 1) 7987601 F (+43 1) 7987605 E info.at@eurotherm.com

GERMANY Limburg Eurotherm Deutschland GmbH T (+49 6431) 2980 F (+49 6431) 298119 E info.de@eurotherm.com

ITALY Como Eurotherm S.r.l T (+39 31) 975111 F (+39 31) 977512 E info.it@eurotherm.com

SWEDEN Malmo Eurotherm AB T (+46 40) 384500 F (+46 40) 384545 E info.se@eurotherm.com

BELGIUM & LUXEMBOURG Moha Eurotherm S.A/N.V. T (+32) 85 274080 F (+32) 85 274081 E info.be@eurotherm.com

HONG KONG & CHINA Eurotherm Limited North Point T (+85 2) 28733826 F (+85 2) 28700148 E info.hk@eurotherm.com Guangzhou Office T (+86 20) 8755 5099 F (+86 20) 8755 5831 E info.cn@eurotherm.com Beijing Office T (+86 10) 6567 8506 F (+86 10) 6567 8509 E info.cn@eurotherm.com Shanghai Office T (+86 21) 6145 1188 F (+86 21) 6145 1187 E info.cn@eurotherm.com

KOREA Seoul Eurotherm Korea Limited T (+82 31) 2738507 F (+82 31) 2738508 E info.kr@eurotherm.com

SWITZERLAND Wollerau Eurotherm Produkte (Schweiz) AG T (+41 44) 7871040 F (+41 44) 7871044 E info.ch@eurotherm.com

NETHERLANDS Alphen a/d Rijn Eurotherm B.V. T (+31 172) 411752 F (+31 172) 417260 E info.nl@eurotherm.com

UNITED KINGDOM Worthing Eurotherm Limited T (+44 1903) 268500 F (+44 1903) 265982 E info.uk@eurotherm.com www.eurotherm.co.uk

BRAZIL Campinas-SP Eurotherm Ltda. T (+5519) 3707 5333 F (+5519) 3707 5345 E info.br@eurotherm.com DENMARK Copenhagen Eurotherm Danmark AS T (+45 70) 234670 F (+45 70) 234660 E info.dk@eurotherm.com FINLAND Abo Eurotherm Finland T (+358) 22506030 F (+358) 22503201 E info.fi@eurotherm.com

INDIA Chennai Eurotherm India Limited T (+91 44) 24961129 F (+91 44) 24961831 E info.in@eurotherm.com

NORWAY Oslo Eurotherm A/S T (+47 67) 592170 F (+47 67) 118301 E info.no@eurotherm.com POLAND Katowice Invensys Eurotherm Sp z o.o. T (+48 32) 2185100 F (+48 32) 2177171 E info.pl@eurotherm.com

U.S.A. Leesburg VA Eurotherm Inc. T (+1 703) 443 0000 F (+1 703) 669 1300 E info.us@eurotherm.com www.eurotherm.com ED53

© Copyright Eurotherm Limited 2007 Invensys, Eurotherm, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris and Wonderware are trademarks of Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners. All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior written permission of Eurotherm limited. Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice. The information in this document is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.

Part No. HA023806 Issue 5