Ferraz Shawmut data sheet for the Ultrasafe US3J (30A) and US6J (60A) 600 volt modular fuse holders for Class J fuses. It gives features, ratings, approvals, recommended fuses, catalog numbers, dimensions and wiring data. The US3J21 designation is not printed in it.

Type
US3J: 600 volt Ultrasafe modular fuse holder for 30A Class J fuses p. 1
Fuses
US3J: 30A Class J or 22 x 58 mm French Ferrule (not UL listed with ferrule fuses); recommended AJT, A4J, HSJ p. 1
Ratings
600VAC, 30A (US3J) or 60A (US6J); short circuit current rating 200kA p. 1
Poles
1, 2 or 3 pole units, with or without blown-fuse indicators; multi-pole assembly kits for field build-up p. 1
Mounting
Snaps onto 35 mm DIN rail; latch stays open for repositioning p. 1
Wiring
#2 to #14 solid/stranded Cu; pressure plate connector; Phillips/slot head terminal screws p. 2
Screw torque
30A: 35 in-lbs.; 60A: 45 in-lbs. p. 2
Indicator light
Operates from min. 90VAC, 115VDC; less than 0.7 mA leakage current at 600V p. 1
US3J catalog numbers
US3J1, US3J2, US3J3, US3J1I, US3J2I, US3J3I, US3JN, US3J2PAK, US3J3PAK, US3J4PAK p. 2
Disconnect
Non-load disconnect, not load-break p. 1, 2
Body
Polyamide; lockable in the open position p. 1
Approvals
The data sheet states UL Listed (Guide IZLT, File E52283), CSA Certified (Class 6225, File 32169), IEC 269, and UL512 p. 1

What this sheet walks you through

  • Choosing fuses for the holder p. 1
  • Ordering by catalog number for 30A and 60A holders p. 2
  • Holder dimensions p. 2
  • Wiring and terminal screw torque p. 2

Good to know

  • The holder is not a load-break disconnect. p. 2
  • The holder is not UL listed with 22 x 58 mm French Ferrule fuses. p. 1
  • Lock the holder open during fuse changeouts or equipment servicing. p. 1

Questions this sheet answers

What fuses fit the Ferraz Shawmut US3J holder?

30A Class J fuses (recommended AJT, A4J or HSJ) or 22 x 58 mm French Ferrule fuses, though the holder is not UL listed with the ferrule type. p. 1

Can the US3J fuse holder be opened under load?

No, it is a non-load disconnect. p. 1, 2

What wire size does the US3J take?

#2 to #14 solid or stranded copper, with a pressure plate connector and 35 in-lbs. suggested torque for 30A. p. 2

What is the short circuit current rating of the US3J?

200kA. p. 1

Does the US3J mount on DIN rail?

Yes, it snaps onto 35 mm DIN rail. p. 1

The file

Size and text

Pages2
PDF206 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Ferraz Shawmut UltraSafe US3J and US6J Class J Fuse Holders Spec Sheet

The text of page 1, from the PDF itself

US3J & US6J

600 VOLT/ULTRASAFE FUSE HOLDERS ULTRASAFE MODULAR FUSE HOLDERS FOR CLASS J FUSES Ferraz Shawmut ULTRASAFETM modular 600 volt Fuse Holders for Class J fuses introduce a new level of safety and ease for installing or replacing Class J fuses. ULTRASAFE holders qualify as “finger safe” to an IP20 grade of protection under IEC standards. The US3J accommodates 30A Class J or 22 x 58 mm French Ferrule* fuses. The US6J is for 60A Class J fuses. ULTRASAFE holders are available in compact 1, 2, or 3 pole units, with or without blown-fuse indicators in each pole. Multi-pole units can also be made up in the field by using the multiple-pole Assembly Kits. All units have provisions for locking in the open position for safety during fuse changeouts or equipment servicing. US3J and US6J holders can be snap-mounted to 35 mm DIN rail and they have a unique latch which will stay open to allow repositioning of the holder in the future. Ultrasafe body material is tough and durable polyamide. *Holder not UL listed with these fuses

HIGHLIGHTS:

APPLICATIONS
Ratings

Approvals➤ Finger Safe➤ 600 volt motors,➤ 600VAC: 30A & 60A

➤ Optional Indicator Lights

transformers, lighting, heating, control circuits, general loads ➤ Non-load disconnect

➤ All Ultrasafe Fuse Holders meet the requirements of UL512

➤ DIN Rail Mount ➤ Compact Footprint ➤ Quick, Easy Fuse Change

➤ Short Circuit Current Rating: 200kA ➤ Min. voltage to operate indicator light: 90VAC, 115VDC [Less than 0.7 mA leakage current at 600V]

➤ UL Listed Guide IZLT, File E52283 ➤ CSA Certified Class 6225 File 32169 ➤ IEC 269

RECOMMENDED FUSE USAGE US3J, US6J . . . . . . . . . . .use with AJT, A4J, HSJ

H4

Page 2 of Ferraz Shawmut UltraSafe US3J and US6J Class J Fuse Holders Spec Sheet

The text of page 2, from the PDF itself

US3J & US6J

600 VOLT/ULTRASAFE FUSE HOLDERS

Catalog Numbers & Descriptions – For use with 30A Class J Fuses CATALOG NO.

DESCRIPTION

US3J1 US3J2 US3J3 US3J1I US3J2I US3J3I US3JN US3J2PAK US3J3PAK US3J4PAK

1 Pole 2 Pole 3 Pole 1 Pole with Indicator 2 Pole with Indicators 3 Pole with Indicators 1 Pole - Neutral 2 Pole Assembling Kit 3 Pole Assembling Kit 4 Pole Assembling Kit

Catalog Numbers & Descriptions – For use with 60A Class J Fuses CATALOG NO.

DESCRIPTION

US6J1 US6J2 US6J3 US6J1I US6J2I US6J3I US6JN US6J2PAK US6J3PAK US6J4PAK

1 Pole 2 Pole 3 Pole 1 Pole with Indicator 2 Pole with Indicators 3 Pole with Indicators 1 Pole - Neutral 2 Pole Assembling Kit 3 Pole Assembling Kit 4 Pole Assembling Kit

Dimensions DIMENSION A B C E F G H I J

US3JHUS6JmmInmmIn

32.5 65 97.5 114 3 106 80 56 6.5

1.28 2.56 3.84 4.49 0.12 4.17 3.15 2.20 0.26

40 80 120 122 3 115 89 62 6.5

1.57 3.15 4.72 4.80 0.12 4.53 3.50 2.44 0.26

Terminal screws: Phillips/slot head Suggested screw torque: 30A - 35 in-lbs. 60A - 45 in-lbs. Connector type: Pressure plate Wire range: #2 to #14 (solid/stranded Cu) Load-break disconnect: No

H5