Spec sheet · Ferraz Shawmut
Ferraz Shawmut UltraSafe US3J and US6J Class J Fuse Holders Spec Sheet
Spec sheet2 pagesPDF 206 KB
Both pages are below, each with its text.
Filed with · 1 model
Also filed with these models on the old site
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Ferraz Shawmut data sheet for the Ultrasafe US3J (30A) and US6J (60A) 600 volt modular fuse holders for Class J fuses. It gives features, ratings, approvals, recommended fuses, catalog numbers, dimensions and wiring data. The US3J21 designation is not printed in it.
- Type
- US3J: 600 volt Ultrasafe modular fuse holder for 30A Class J fuses p. 1
- Fuses
- US3J: 30A Class J or 22 x 58 mm French Ferrule (not UL listed with ferrule fuses); recommended AJT, A4J, HSJ p. 1
- Ratings
- 600VAC, 30A (US3J) or 60A (US6J); short circuit current rating 200kA p. 1
- Poles
- 1, 2 or 3 pole units, with or without blown-fuse indicators; multi-pole assembly kits for field build-up p. 1
- Mounting
- Snaps onto 35 mm DIN rail; latch stays open for repositioning p. 1
- Wiring
- #2 to #14 solid/stranded Cu; pressure plate connector; Phillips/slot head terminal screws p. 2
- Screw torque
- 30A: 35 in-lbs.; 60A: 45 in-lbs. p. 2
- Indicator light
- Operates from min. 90VAC, 115VDC; less than 0.7 mA leakage current at 600V p. 1
- US3J catalog numbers
- US3J1, US3J2, US3J3, US3J1I, US3J2I, US3J3I, US3JN, US3J2PAK, US3J3PAK, US3J4PAK p. 2
- Disconnect
- Non-load disconnect, not load-break p. 1, 2
- Body
- Polyamide; lockable in the open position p. 1
- Approvals
- The data sheet states UL Listed (Guide IZLT, File E52283), CSA Certified (Class 6225, File 32169), IEC 269, and UL512 p. 1
What this sheet walks you through
- Choosing fuses for the holder p. 1
- Ordering by catalog number for 30A and 60A holders p. 2
- Holder dimensions p. 2
- Wiring and terminal screw torque p. 2
Good to know
- The holder is not a load-break disconnect. p. 2
- The holder is not UL listed with 22 x 58 mm French Ferrule fuses. p. 1
- Lock the holder open during fuse changeouts or equipment servicing. p. 1
Questions this sheet answers
What fuses fit the Ferraz Shawmut US3J holder?
30A Class J fuses (recommended AJT, A4J or HSJ) or 22 x 58 mm French Ferrule fuses, though the holder is not UL listed with the ferrule type. p. 1
What wire size does the US3J take?
#2 to #14 solid or stranded copper, with a pressure plate connector and 35 in-lbs. suggested torque for 30A. p. 2
What is the short circuit current rating of the US3J?
200kA. p. 1
Does the US3J mount on DIN rail?
Yes, it snaps onto 35 mm DIN rail. p. 1
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
US3J & US6J
600 VOLT/ULTRASAFE FUSE HOLDERS ULTRASAFE MODULAR FUSE HOLDERS FOR CLASS J FUSES Ferraz Shawmut ULTRASAFETM modular 600 volt Fuse Holders for Class J fuses introduce a new level of safety and ease for installing or replacing Class J fuses. ULTRASAFE holders qualify as “finger safe” to an IP20 grade of protection under IEC standards. The US3J accommodates 30A Class J or 22 x 58 mm French Ferrule* fuses. The US6J is for 60A Class J fuses. ULTRASAFE holders are available in compact 1, 2, or 3 pole units, with or without blown-fuse indicators in each pole. Multi-pole units can also be made up in the field by using the multiple-pole Assembly Kits. All units have provisions for locking in the open position for safety during fuse changeouts or equipment servicing. US3J and US6J holders can be snap-mounted to 35 mm DIN rail and they have a unique latch which will stay open to allow repositioning of the holder in the future. Ultrasafe body material is tough and durable polyamide. *Holder not UL listed with these fuses
HIGHLIGHTS:
- APPLICATIONS
- Ratings
Approvals➤ Finger Safe➤ 600 volt motors,➤ 600VAC: 30A & 60A
➤ Optional Indicator Lights
transformers, lighting, heating, control circuits, general loads ➤ Non-load disconnect
➤ All Ultrasafe Fuse Holders meet the requirements of UL512
➤ DIN Rail Mount ➤ Compact Footprint ➤ Quick, Easy Fuse Change
➤ Short Circuit Current Rating: 200kA ➤ Min. voltage to operate indicator light: 90VAC, 115VDC [Less than 0.7 mA leakage current at 600V]
➤ UL Listed Guide IZLT, File E52283 ➤ CSA Certified Class 6225 File 32169 ➤ IEC 269
RECOMMENDED FUSE USAGE US3J, US6J . . . . . . . . . . .use with AJT, A4J, HSJ
H4
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
US3J & US6J
600 VOLT/ULTRASAFE FUSE HOLDERS
Catalog Numbers & Descriptions – For use with 30A Class J Fuses CATALOG NO.
DESCRIPTION
US3J1 US3J2 US3J3 US3J1I US3J2I US3J3I US3JN US3J2PAK US3J3PAK US3J4PAK
1 Pole 2 Pole 3 Pole 1 Pole with Indicator 2 Pole with Indicators 3 Pole with Indicators 1 Pole - Neutral 2 Pole Assembling Kit 3 Pole Assembling Kit 4 Pole Assembling Kit
Catalog Numbers & Descriptions – For use with 60A Class J Fuses CATALOG NO.
DESCRIPTION
US6J1 US6J2 US6J3 US6J1I US6J2I US6J3I US6JN US6J2PAK US6J3PAK US6J4PAK
1 Pole 2 Pole 3 Pole 1 Pole with Indicator 2 Pole with Indicators 3 Pole with Indicators 1 Pole - Neutral 2 Pole Assembling Kit 3 Pole Assembling Kit 4 Pole Assembling Kit
Dimensions DIMENSION A B C E F G H I J
US3JHUS6JmmInmmIn
32.5 65 97.5 114 3 106 80 56 6.5
1.28 2.56 3.84 4.49 0.12 4.17 3.15 2.20 0.26
40 80 120 122 3 115 89 62 6.5
1.57 3.15 4.72 4.80 0.12 4.53 3.50 2.44 0.26
Terminal screws: Phillips/slot head Suggested screw torque: 30A - 35 in-lbs. 60A - 45 in-lbs. Connector type: Pressure plate Wire range: #2 to #14 (solid/stranded Cu) Load-break disconnect: No
H5
