The text of a manual · part 1 of 10

Modular electrical terminal CPX-P, pages 1 to 10

Pages 1 to 10 of 99

The original document is the PDF (3.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Festo CPX-AB-8-KL

Page 1 read from a scan by OCR; it may hold reading errors

Modular electrical terminal CPX-P

FESTO

Page 2

Terminal CPX-P Key features

Key features Installation concept

Electrical components

Assembly

Operation

Economical from the smallest configuration up to the maximum number of modules Up to 9 electrical input/output modules plus bus nodes and pneumatic interface/electronics modules for valves Extensive range of functions and connection options for the electrical modules Choice of connection technology for technically and economically optimised connections Can be used as a dedicated remote I/O module

High operating voltage tolerance (±25%) Open to all fieldbus protocols and Ethernet IT services and TCP/IP such as remote maintenance, remote diagnostics, web server, text message and e-mail alert Digital inputs and outputs, 4-/8-/16-way, optionally available with individual channel diagnostics Analogue inputs and outputs, 2-/4-way Analogue inputs and outputs with HART protocol Input modules for connecting NAMUR sensors IP65 or IP20

Wall or H-rail mounting, also on mobile units Conversions/extensions are possible at any time, individual linking Modular system offering a range of configuration options Fully assembled and tested unit Lower selection, ordering, assembly and commissioning costs thanks to the central CPX-P terminal Choice of pneumatic components for optimised control loop system design

Fast troubleshooting thanks to an extensive selection of LEDs (some of which are multi-coloured) on the bus node and on all I/O modules Supports module and channeloriented diagnostics On-the-spot diagnostics in plain text via operator unit (CPX-MMI) Fieldbus/Ethernet remote diagnostics Innovative diagnostic support with integrated web server/web monitor or maintenance tool (CPX-FMT) with USB adapter (NEFC) for PC Optimised commissioning thanks to parameterisable functions Reliability of service with connec­ tion blocks and modules that are quick to replace without changing the wiring

2

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 3

Terminal CPX-P Key features Variants for controlling the CPX-P terminal (with bus node, without preprocessing) Bus node Different bus nodes are used to integrate the terminal in the control systems of various manufacturers. The CPX-P terminal can therefore be operated on commonly used fieldbus systems: PROFIBUS DP PROFINET DeviceNet

Integration in universal networks based on Ethernet opens up new possibilities. Faster data transmis­ sion, real-time capability and above all additional IT services such as file transfer, web server, web monitor as integrated website in the CPX-P

Bus node terminal, text message/e-mail alerts, etc. open up a wide range of synergies. These include standardised and universal communication technology across all areas, including operating level, management level and field level in the production environment, with protection to IP65. The following protocols are supported: EtherNet/IP Modbus/TCP PROFINET

Industrial Ethernet bus node PLC

PLC

Industrial Ethernet

Fieldbus

IT services: Web E-mail File transfer

Communication with higher-order controller via fieldbus No preprocessing

Fieldbus protocol dependent on CPX bus node used Up to 90 I/Os, depending on the bus node used

Connection to a higher-order controller directly via EtherNet/IP, Modbus/TCP or PROFINET No preprocessing

Monitoring via Ethernet and web applications Up to 300 I/Os

-H- Note Every electrical connection can be combined with an appropriate number of I/O modules and/or pneumatic components, depending on its address capacity.

2018/04 – Subject to change

Likewise, every pneumatic variant of the CPX-P terminal can be operated with every electrical connection variant.

è Internet: www.festo.com/catalogue/...

3

Page 4

Terminal CPX-P Key features Connection of inputs and outputs to the CPX-P terminal Digital and analogue CPX I/O modules

Electrical connection The connection technology for sensors and additional actuators offers a wide range of digital and analogue input and output modules and is freely selectable – as appropriate to your standard or application. The input/output modules can be combined as required with the connection blocks:

CPX modules for NAMUR sensors

M12, 5-pin M12, 5-pin, with quick lock and metal thread M8, 3-pin M8, 4-pin Sub-D, 25-pin Harax®, 4-pin CageClamp® (with cover also to IP65/67) Screw terminal and spring-loaded terminal

Electrical connection The electronics modules for NAMUR sensors can only be combined with certain connection blocks. The input modules can be combined as required with the connection blocks:

M12, 4-pin Screw terminal and spring-loaded terminal

1 Higher-order controller 2 Non-ATEX zone; non-intrinsic­ ally safe circuits are permitted 3 ATEX zone; only intrinsically safe circuits are permitted 4 CPX input module for NAMUR sensors, non-intrinsically safe design 5 CPX input module for NAMUR sensors, intrinsically safe design 6 Actuator/machine component with NAMUR sensors

CPX-P modules are suitable for con­ figuring intrinsically safe or non-in­ trinsically safe circuits depending on the design selected. This enables components from both safe and hazardous zones to be connected to the CPX-P terminal. The components for the intrinsically safe zone are marked in blue or entirely coloured blue to distinguish them visually.

CPX modules for NAMUR sensors, intrinsically safe circuits for ATEX applications

1

PLC

Fieldbus 5 2

4

-H- Note 6

6

4

3

è Internet: www.festo.com/catalogue/...

Intrinsically safe circuits are circuits which release so little energy during operation, or in the event of certain faults under specified test condi­ tions, that no ignition can occur in a particular potentially explosive atmosphere.

Subject to change – 2018/04

Page 5

Terminal CPX-P Key features Pneumatic variants of the CPX-P terminal With valve terminal MPA-S – centralised The electrical CPX-P terminal is a modular peripheral system for valve terminals. The system is specifically designed so that the valve terminal can be adapted to suit different applications.

The modular system design lets you configure the number of valves, inputs and additional outputs to suit the application.

The electrical peripherals type CPX-P can also be configured without a valve terminal and can be used on a fieldbus. For this order, only the order code for the electrical peripherals is required.

The order lists for the pneumatic components can be found on è Internet: mpa-s (valve terminal MPA-S)

Ordering The CPX-P terminal with valve terminal is fully assembled according to your order specifications and individually tested. The finished valve terminal consists of the electrical peripherals including the desired actuation and the selected components from the MPA-S modular system.

2018/04 – Subject to change

The CPX-P terminal with valve ter­ minal is ordered using two separate order codes. One order code defines the electrical peripherals type CPX-P, while the other specifies the pneumatic components of the valve terminal.

è Internet: www.festo.com/catalogue/...

5

Page 6

Terminal CPX-P Peripherals overview Complete overview of modules

End plate

Bus node

Control block

Input/output modules

Mounting holes for wall mounting Functional earth connection

Fieldbus/Industrial Ethernet connection using various types of connection technology Setting of fieldbus parameters via DIL switch Display of fieldbus and peripheral equipment status via LED

Remote unit CPX-CEC Connection via Ethernet TCP/IP or Sub-D programming interface Setting of operating modes via DIL switch and program selection via rotary switch

Combination of Interlinking block Electronics module Connection block

Operator unit Connection to bus nodes or control block Display and modification of parameter settings Plain-text display for texts, messages (e.g. individual channel diagnostics, condition monitoring), menus, etc.

6

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 7

Terminal CPX-P Peripherals overview Complete overview of modules

1 2

3 Input/output modules 1 Interlinking block Internal linking of the power supply and serial communication External power supply for the entire system Additional power supply for outputs Connection accessories for 7/8" Individual linking with M6 screws, individually expandable

2018/04 – Subject to change

Pneumatic interface 2 Electronics module

3 Connection block

Digital inputs for connecting the sensors Digital outputs for activating additional actuators Analogue inputs Analogue outputs

Choice of connection technology Protection class IP65 or IP20 Can be combined with the electronics modules Connection accessories for M8/M12/Sub-D/quick connector, etc. M8/M12/Sub-D, etc. connecting cables Modular system for connecting cables

è Internet: www.festo.com/catalogue/...

MPA-S

7

Page 8

Terminal CPX-P Peripherals overview Individual overview of modules Bus node

è 66 Bus node for PROFIBUS DP DeviceNet EtherNet/IP (integrated web server) PROFINET (integrated web server)

Plastic connection block

Metal connection block Direct machine mounting (connection block to IP65/IP67) M8-3POL M8-4POL M12-5POL M12-5POL quick lock, metal thread screened Sub-D Quick connector Spring-loaded terminal with cover

Direct machine mounting (connection block to IP65/IP67) M12-5POL

Protected fitting space (protection class IP20) Spring-loaded terminal Screening concept Optional screening plate for con­ nection block with M12 connection technology Digital electronics module for inputs/outputs

è 62

Digital inputs 8 digital inputs 16 digital inputs Digital outputs 4 digital outputs (1 A per channel, individual channel diagnostics) 8 digital outputs (0.5 A per chan­ nel, individual channel diagnostics)

8

è Internet: www.festo.com/catalogue/...

Analogue electronics module for inputs/outputs

è 66

Analogue inputs 4 analogue inputs (1 … 5 V, 0 … 10 V, –5 … +5 V, –10 … +10 V, 0 … 20 mA, 4 … 20 mA, –20 … +20 mA) 4 analogue inputs with HART protocol Analogue outputs 2 analogue outputs (0 … 10 V DC, 0 … 20 mA, 4 … 20 mA) 4 analogue outputs with HART protocol

Subject to change – 2018/04

Page 9

Terminal CPX-P Peripherals overview Individual overview of modules Connection block for NAMUR sensors and HART input/output module

Digital electronics module for NAMUR sensors

Direct machine mounting (connection block to IP65) M12-4POL Protected fitting space (connection block to IP20) Screw terminal Spring-loaded terminal

è 86

Metal interlinking block – Individual linking System linking Different voltage values for supplying the modules Serial communication between the modules

Pneumatic interface MPA-S

In addition to system linking, power supply for the electronics plus sensors (8 A) valves plus actuators (8 A)

System supply 7/8", 5-pin

Additional power supply In addition to system linking, power supply for the actuators (8 A per supply)

è 92

End plate

Valve terminal MPA1 (360 l/min) MPA2 (700 l/min) Up to 128 solenoid coils Up to 16 modules can be configured

2018/04 – Subject to change

è 53

Digital inputs 8 digital inputs for NAMUR sensors or wired mechanical contacts Intrinsically safe design with additional protection measures in the event of failure

Expandability Can be expanded as required by up to 10 interlinking blocks

-H- Note The 7/8" supply is subject to the following restriction due to the available accessories: 5-pin 8 A

End plate Left-hand Right-hand (for use without valves)

è Internet: www.festo.com/catalogue/...

9

Page 10

-V- New CPX-4AE-4AA-H Terminal CPX-P Peripherals overview General basic data and guidelines Max. 11 modules in total: One bus node and/or one control block Up to 9 additional input/output modules In addition a pneumatic interface – Always positioned as the last module on the right-hand side – 16 MPA modules can be configured

Address capacity max. 512 inputs and 512 outputs, depending on bus node or control block One interlinking block with system supply Multiple interlinking blocks with additional power supply, always positioned to the right of the inter­ linking block with system supply

Combination of connection blocks and electronics modules for inputs and outputs Digital electronics modules For inputs CPX-8DE CPX-8NDE CPX-16DE

For outputs CPX-4DA

CPX-8DA

The connection blocks can, with a few exceptions, be combined with the electronics modules for inputs/ outputs (è table below) The electronics modules for inputs/ outputs can be combined with various interlinking blocks

For NAMUR sensors CPX-P-8DE-N CPX-P-8DE-N-IS

Connection blocks, plastic design CPX-AB-8-M8-3POL CPX-AB-8-M8X2-4POL CPX-AB-4-M12x2-5POL CPX-AB-4-M12x2-5POL-R CPX-P-AB-4XM12-4POL CPX-P-AB-4XM12-4POL-8DE-N-IS CPX-AB-8-KL-4POL CPX-P-AB-2XKL-8POL CPX-P-AB-2XKL-8POL-8DE-N-IS CPX-AB-1-SUB-BU-25POL CPX-AB-4-HAR-4POL n – n n – – n – – n n n – n n – – n – – n n

– n – – – – n – – n – n n n n – – n – – n n n n n n – – n – – n n

– – – – n – – n – – –

– – – – – n – – n – –

Connection blocks, metal design CPX-M-AB-4-M12X2-5POL n n

– n n

–

–

Combination of connection blocks and electronics modules for inputs and outputs Analogue electronics modules CPX-4AE-U-I CPX-2AA-U-I

-V-

CPX-4AE-4AA-H

Connection blocks, plastic design CPX-AB-4-M12x2-5POL CPX-AB-4-M12x2-5POL-R CPX-AB-8-KL-4POL CPX-AB-1-SUB-BU-25POL CPX-P-AB-4XM12-4POL CPX-P-AB-2XKL-8POL n n n n – – n n n n – –

– – – – n n

Connection blocks, metal design CPX-M-AB-4-M12X2-5POL n n

–

10

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04