GE Series Six data sheet GEK-83506B (January 1984) for the I/O Control module, catalog number IC600CB503A. It describes what the module does in the Series Six CPU, its specifications, faceplate connectors and status lights, the user selection jumpers, installation and ordering.
- What it is
- Series Six CPU I/O Control module: links the CPU to the primary I/O chain and handles transfers with the PDT and DPU p. 1
- Compatible CPUs
- Series Six Models 60, 600 and 6000 p. 1
- Connectors
- Two 37-pin D type: "I/O" to an I/O Receiver module up to 50 feet away, "PP/DPU" for the DPU or PDT p. 1
- Status LEDs
- CHAIN OK, PARITY, ENABLED, DPU p. 1, 2
- Power
- 5 Vdc, 1.0 A, from the CPU power supply p. 1
- I/O cable
- IC600WDXXXA, where XXX is a three-digit length code; total I/O cable 50 feet (15 meters) max p. 3
- Slot
- Immediately left of the CPU power supply p. 3
- Circuit board size
- 8.15 x 11.0 in (208 x 280 mm) p. 1
- Temperature
- 0 to 60°C operating; 0 to 70°C storage p. 1
- Humidity
- 5% - 95% (non-condensing) p. 1
- Jumper options
- Select whether a DPU or CCM window failure puts the CPU in STOP mode p. 1
- Catalog numbers
- IC600CB503A, IC600FP509A p. 4
What this sheet walks you through
- Reading the CHAIN OK, PARITY, ENABLED and DPU lights p. 2
- Setting the user selection jumpers before installation p. 3
- Installing the module in a Model 60, 600 or 6000 CPU p. 3
- Connecting the I/O cable to the nearest I/O Receiver p. 3
- Ordering the board and faceplate p. 4
Good to know
- The total I/O cable length in the I/O station, including the link to this module, cannot exceed 50 feet (15 meters). p. 3
- The LEDs work only when the module is in a properly powered CPU rack. p. 1
- Alarm No. 1 puts the CPU in STOP mode; Alarm No. 2 is advisory only. p. 3
Questions this sheet answers
Which Series Six CPUs use the IC600CB503 I/O Control module?
The Model 60, 600 and 6000 CPUs. p. 1
Where does the I/O Control module go in the CPU rack?
In the slot immediately to the left of the CPU power supply, secured with the faceplate thumbscrews. p. 3
What does it mean when the CHAIN OK light is off?
A continuity or power problem or an output-data parity error exists at one or more primary-chain I/O stations. p. 2
What does the ENABLED light show?
On means the outputs are enabled and the CPU is in RUN ENABLED mode; off means outputs are disabled (RUN DISABLED or STOP). p. 2
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
SERIES SIX PROGRAMMABLE
I
GEK-83506B DPU, PDT and User I/O interfaces
CONTROLLERS
I/O CONTROL MODULE
GENERAL DESCRIPTION The I/O (Input/Output) Control module is utilized in the Series Six Central Processing Unit (CPU) to provide an interface between the CPU and the primary I/O chain; it also controls data transfers between the CPU and peripheral devices such as the Program Development Terminal (PDT) and the Data Processor Unit (DPU). The features and benefits of this module are summarized in Table 1.
an I/O Receiver module up to 50 feet away; the other connector, marked “PP/DPU”, can be used to connect a cable from the DPU or the PDT. The user has the option of selecting (by jumper) whether the CPU enters the STOP mode (and Alarm No. 1 and No. 2 are activated) if there is a Data Processor Window failure and/or a Communications Window failure (between the I/O Control and the Communications Control Module (CCM)), in the course of an execution sequence by the CPU. If these options are not selected, the CPU closes the window to the DPU and/or CCM at the occurrence of a window failure, and an Alarm Condition No. 2 prevails.
The module provides four Light-Emitting Diodes (LED’s), visible through a lens on the faceplate, which indicate I/O-chain parity and continuity conditions, whether user I/O are enabled, and problems with the DPU interface. The LEDs operate only when the module is installed in a properly powered CPU rack.
Refer to Figure 1 (next page) for I/O Control module specifications.
Two, 37-pin “D” type connectors are available for cable connections. One, marked “I/O”, can be used for linking
TABLE 1. FEATURES
r-
FEATURES AND BENEFITS BENEFITS
I
Contains I/O and Communication Interfaces.
I
Centralized control of CPU Interface operations.
Four LED indicators: CHAINOK PARITY ENABLED DPU
Simplifies
troubleshooting.
Can be used in Models 60,600 and 6000 CPUs.
Reduced spare-parts inventory.
- - Dimensions
- - Power Requirements: 5 Vdc, 1.0 A (Supplied by CPU power supply)
Circuit Board: 8.15 x 11.0 (inches) 208 x 280 (mm)
-
- Storage Temperature
- 0o t o 70oC
Faceplate:
- - Operating Temperature
- Oo to 60°C
12.46 x 1.175 (inches) 317 x 30 (mm)
- Humidity: FIGURE I. SPECIFICATIONS
5% - 95% (non-condensing)
I I
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
I/O Control ModuleGEK-83506:mcl LaDF ‘PlDPlHnlN K ARlTY NnaLE PU
-‘:0.-.. ::::.’. :‘*. 1
(????L!??
0 D-Type 37-Pin Connector to PDT or DPU
02 D-Type 37-Pin
Connector to Primary I/O Chain Connects to I/O Receiver module in nearest I/O rack in primary chain.
0 User Selection Jumpers See the “Installation” section of this Data Sheet.
04 CHAIN OK Light On:
- off
- Continuity, power, and output-data parity are OK at all I/O stations in the primary chain.
PARITY Light On: Input-data parity is OK at the I/O Control module. Off: Input-data parity error exists. @ ENABLED Light On: The outputs are enabled. CPU is operating in the RUN ENABLED mode. Off: The outputs are disabled. CPU is in the RUN DISABLED or the STOP mode.
- 07 DPU Light On: Off
- A continuity or power problem or output data parity error exists at one or more primary-chain I/O stations.
Data Processor is OK. A continuity error or other type of problem exists with the DPU.
FIGURE 2. USER ITEMS 2
Ref. PC-S6-84-0158
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
GEK-83506
I/O Control Module
INSTALLATION Before installing the I/O Control module in either the Model 60, 600 or 6000 CPU, refer to Table 2 and determine if the User Selection jumpers are in the appropriate positions. A further discussion of these jumper selections is provided in the General Description section of this data sheet. Install this module to the immediate left of the CPU power supply. Use the extraction/insertion tool supplied with the CPU to insert (or remove) this module in the appropriate card slot. Secure the faceplate to the rack using the thumbscrews at the top and bottom.
*TABLE 2.
Connect an I/O cable (Part No. IC600WDXXXA, where “XXX” is a three-digit number corresponding to the cable length) between the l/O Receiver module in the nearest I/O rack in the primary chain and the faceplate connector on this module; secure the connector using the furnished screws. NOTE The total length of I/O cable interconnetting the I/O racks in the I/O station, including the cable connecting t h i s m o d u l e t o t h e n e a r e s t I/O receiver, can not exceed 50 feet (15 meters),
USER SELECTION JUMPERS I
- NOTE
- JUMPER
POSITION
B B E E H H
A-B B-C D-E E-F G-H H-I
FUNCTION DPU present DPU not present DPU fault causes Alarms No. 1 and 2 DPU fault causes Alarm No. 2 CCM fault causes Alarms No. 1 and 2 CCM fault causes Alarm No. 1
Alarm No. 1 results in the CPU entering the STOP mode; Alarm No. 2 is an advisory condition.
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
GEK-83506
I/O Control Module
ORDERING INFORMATION Circuit Board and Faceplate
FaceplateIC600CB503AIC600FP509ACATALOGNUMBERREVISIONSUFFIX
The equipment listed above having the catalog numbers shown and the same equipment having a higher alpha suffix is designed for listing by UL for use as auxiliary control devices. The equipment is a direct replacement for equipment having the same catalog number but a lower alpha suffix.
The UL symbol on the nameplate means the product is listed by Underwriters Laboratories Inc. (UL Standard No. 508, Industrial Control Equipment, subsection Electronic Power Conversion Equipment.) For further information, contact your local GE Fanuc sales office.
JANU A R Y ,
1984