GE Fanuc Series Three IC630MDL375 115/230 VAC Output Module Specifications
Manual2 pagesPDF 686 KB
Both pages are below, each with its text.
Filed with · 3 models
Also filed with these models on the old site
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Two-page Series Three data sheet (GEK-25376) for the 115/230 Vac output module. The pages print the designation IC630MDL375A, not the IC630MDL375B the site files it under. It describes the 16 output circuits, their grouping and limits, and shows typical user wiring.
- What it is
- Series Three 115/230 Vac output module, IC630MDL375A, with 16 circuits for discrete ON/OFF loads p. 1
- Typical loads
- Relay coils, motor starters, solenoid valves and indicator lights p. 1
- Grouping
- Two groups of 8 circuits, each with its own common; each group can use a separate power source p. 1
- Switching capacity
- 2 amps maximum per output circuit p. 1
- Group protection
- Each group of 8 outputs protected at 5 amps p. 1
- Indicators
- 16 with LED Indicators p. 1
What this manual walks you through
- Wiring field loads and the user power source p. 2
Good to know
- Power for the field devices must come from the user. p. 1
Questions this manual answers
How many outputs does the Series Three 115/230 Vac output module have?
16 circuits, split into two groups of 8, each with its own common. p. 1
How much current can each output switch?
Up to 2 amps per output circuit. p. 1
What loads can the 115/230 Vac output module drive?
Discrete ON/OFF loads such as relay coils, motor starters, solenoid valves and indicator lights. p. 1
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
GEK-25376
Series Three
115/230 VAC OUTPUT (TRIAL) IC630MDL375A The 115/230 Vac Output module provides 16 circuits each capable of controlling Typical loads include relay coils, user supplied discrete (ON/OFF) loads. The 16 circuits are motor starters, solenoid valves and indicator lights. divided into two groups of 8 circuits, each having its own common. Each group can be supplied from a separate power source. Power to operate the field devices must be supplied by the user. Each group of 8 outputs is protected by a 5 amp fl Maximum switching capacity of the output circuits is 2 amps. Specifications for this module are listed below.
Output points User Supplied Voltage ON delay OFF delay Output Current (ON) Minimum Maximum Leakage (OFF)
16 with LED Indicators 97 - 265 Vac < 0.1 ms < 1/2 cycle 25 mA 2 A 2.7 mA (115V, 50 Hz) 3.3 mA (115V, 60 Hz) 5.5 mIl. (230V, 50 Hz) 6.6 mA (230V, 60 Hz) 20A for 1 cycle 5A for each 8 circuits 5 Vdc, 35 mA 12 Vdc, 20 mA + 17.5 mA/point
Inrush Current Fuse Rating Internal Power Consumption
aoc 1 8 CIRCUITS ON AT 1 AMP EACH
12 NUMBER OF CIRCUITS ON
S CRC LATS ON AT 2 AMPS EACH S CIRCUITS ON AT 1 AMP EACH
4
2 CIRCUITS ON AT 2 AMPS EACH I I 5 1 00 C 2 OOC C 30 I0 C 406 ' 00 C SOOC
AMBIENT TEMPERATURE PC) 1.1 0 POINTS VS. TEMPERATURE CHART
Ref. PC-S3-83-00286-8PC4M-e3.C.•
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
GEK-25376
Series Three
Figure 6.3 provides user wiring information for the 115/230 VAC output module.
OUTPUT MODULE CIRCUITRY
FIELD WIRING
TYPICAL REFERENCES 97-265 VAC
070071072073 ,Mk074075076077080081082083084085086087
OUTPUT SWITCHING DEVICE 0C - si4a.00n
USER LOAD0USER POWER SOURCE
Figure 6.1 115/230 VAC OUTPUT, TYPICAL USER CONNECTIONS
Ref. PC-S3-83-0020
6-9