Spec sheet · Gems Sensors
Gems Sensors ST-28196 Spec Sheet
Spec sheet2 pagesPDF 1.6 MB
Both pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
A two-page Gems Sensors catalog sheet for its solid-state LOAD-PAK, SPDT-PAK and FLIP-PAK switching units, which boost the load a sensor can switch. The site files it under part 28196, a FLIP-PAK that the sheet lists alongside 28244. It gives ratings, an ordering table, dimension drawings and typical wiring, including pump and motor start-stop control.
- Device
- FLIP-PAK, a solid-state start-stop (on-off) switching unit driven by low-current contacts p. 1
- Part numbers
- FLIP-PAK: 28196 or 28244 p. 2
- FLIP-PAK ratings
- 120 VAC and 240 VAC models; loads to 5 amps p. 1
- OFF override
- FLIP-PAK: a closed OFF input makes the ON input ineffective p. 2
- Low-voltage protection
- FLIP-PAK: built in p. 1
- Housing
- Compact, totally encapsulated polysulfone body p. 1
- Family
- LOAD-PAK 5 A AC, 10 A AC and 2 A DC; SPDT-PAK 5 A AC; FLIP-PAK 5 A AC p. 2
- LOAD-PAK 25763
- Controls loads up to 2 amps DC from a dry contact sensor p. 2
- SPDT-PAK
- One sensor controls two loads up to 5 amps each, N.O. for one and N.C. for the other p. 1
What this sheet walks you through
- Wiring a FLIP-PAK for pump up/down control p. 2
- Starting and stopping a motor with two push buttons and a FLIP-PAK p. 2
- Choosing a part number from the ordering table p. 2
- Wiring a LOAD-PAK to a dry contact sensor p. 2
- Adding transient protection to an SPDT-PAK p. 2
Good to know
- The DC LOAD-PAK must be wired to the polarity shown; reversed polarity destroys it. p. 1
- The SPDT-PAK needs loads of at least 10 watts on both outputs for correct SPDT switching. p. 1
- The AC and DC LOAD-PAKs include transient protection; the SPDT-PAK does not. p. 1
- Sensor switch wires to LOAD-PAKs should not share raceways or conduits with high voltage lines. p. 2
- All AC voltage and current figures are RMS values unless stated otherwise. p. 2
Questions this sheet answers
What is Gems part number 28196?
It is a FLIP-PAK, a solid-state unit for start-stop or on-off switching from low-current contacts. The sheet lists it together with 28244. p. 1, 2
What load can a FLIP-PAK switch?
The sheet says its 120 VAC and 240 VAC models handle loads to 5 amps. p. 1
How is a FLIP-PAK wired for pump refill control?
Low level lets switch S2 close and start the refill pump; rising level closes S1 on the OFF input to stop it. Swapping the ON and OFF connections gives pump-down control. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
Non-Intrinsically Safe Relays Boost Your Sensor’s Load Handling Ability SPST, N.O. Operation AC or DC models Amplify current handling capability of sensors for controlling high power loads Compact, polysulfone bodies are totally encapsulated Impervious to shock or vibration Solid-state reliability
LOAD-PAK®, 5 AMP, AC
GEMS solid-state switching units perform the functions of electro-mechanical relays, with the added reliability and advantages inherent in solid-state. Compact, totally encapsulated, and impervious to shock or vibration, these units mount anywhere… even directly on working machinery. 2-3/4˝ (69.8 mm) MTNG. CTRS. 7/32˝ LOAD-PAKS: integrated, solid-state switches that amplify current handling capabilities (5.5 mm) of sensors for controlling high power loads. SPST, N.O. operation, AC and DC DIA.models. 2 HOLES. 1-9/16˝ SPDT-PAKS: enable one low-current sensor to(39.6 control two independent loads up to 5 mm) amps each. Switching is N.O. for one load and N.C. for the other. 2-3/8˝ for industrial FLIP-PAKS: provide low-current, “Start-stop” or “on-off” switching (60.3 mm) motor, liquid level and other control systems. Units hold operational state up to THD. 1/2 second during momentary power loss to cut nuisance shutdowns; low6-32voltage protection is inherent. 120 VAC and 240 VAC models handle loads to 5 amps.
LOAD-PAK®, 10 AMP, AC1˝ (25.4 mm)Dimensions
LOAD-PAK, 10 Amp, A.C. LOAD-PAK, 2 Amp, D.C. SPDT-PAK, FLIP-PAK
LOAD-PAK, 5 Amp. A.C.
2-3/4˝ (69.8 mm) MTNG. CTRS.
1-9/16˝ (39.6 mm)
2-3/4˝ (69.8 mm) MTNG. CTRS. 7/32˝ (5.5 mm) DIA. 2 HOLES.
7/32˝ (5.5 mm) DIA. 2 HOLES.
2-3/8˝ (60.3 mm) 2-3/8˝ (60.3 mm)
2-3/8˝ (60.3 mm)
6-32 THD.
Intrinsically Safe LOAD-PAK®, 2 AMP, DC Certified intrinsically safe under MSHA Certification No. 1951 for use on permissible equipment, for Group D use only.
6-32 THD.FLIP-PAK1˝ (25.4 mm)1-3/8˝ (34.9 mm)2-3/4˝ (69.8 mm)
MTNG. CTRS. Electrical Information
ELECTRONIC PRODUCTS L-12
DC LOAD-PAK: Switching is by means 7/32˝ of B+ closure. . .the DC LOAD-PAK must be (5.5 mm) wired to the polarity shown. REVERSING DIA. 2 HOLES. POLARITY WILL DESTROY THIS UNIT. 2-3/8˝ SPDT-PAK: This unit is designed to operate with a load connected to each of the two (60.3 mm) outputs. These loads must be 10 watts, minimum, for correct SPDT switching. One load used alone must be connected to the N.O. terminal. With this load, which may be less than 10 watts,2-3/8˝ the unit will operate the same as an SPST unit. (60.3 mm) THD.transients will not normally harm LOAD-PAKS, Line Transients: While random6-32line they may pass current to some loads for up to 1/2 cycle duration*. AC LOAD-PAKS and the DC LOAD-PAK include transient protection. . .the SPDT-PAK does not. If load transients 1-3/8˝ are a problem, the external protective circuit, a properly-sized metal oxide (34.9 mm) varistor, may be used.
SPDT-PAK
- Mechanical holding or latching contacts (contactors) may cause some loads to latch under transient conditions.
Visit www.GemsSensors.com for most current information.
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
load-pak / spdt-pak / flip-pak Surge Current Ratings of LOAD-PAKS. Non-repetitive. Overload Time
Switch or Sensor Wiring: Wires connecting external sensor switches to LOAD-PAKS should not be placed in raceways or conduits containing high voltage lines. Voltages induced from these lines trigger the low-power, solid-state triac, causing it to turn “on” momentarily.
20173
26392
Part Number Operating & Load Voltage Range
1.0 Sec.10 Sec.5 Amps, AC30201010 Amps, AC503015
*Mechanical holding or latching contacts (contactors) may be cause some loads to latch under transient conditions.
Specify Part Number based on the specifications tabulated below. LOAD-PAK 10 AMP, AC
.010 Sec.
Overload, Amps
How To Order LOAD-PAK 5 AMP, AC
LOAD-PAK RatingLOAD-PAK 2 AMP, DC24 to 260 VACSPDT-PAK 5 AMP, ACFLIP-PAK 5 AMP, AC257632215528196282446 to 48 VDC100 to 130 VAC100 to 130 VAC200 to 250 VACVoltage Loss2 VAC2 VDC3 VAC2 VACSensor Current, Max.20 mA35 mA20 mA20 mA
Allowable Resistance in Sensor Circuit to Turn “ON” (Max.)
4 kΩ at Nom. Volt.
0 to 4 kΩ
4 kΩ at Nom. Volt., Leakage Current Thru Load Term.
12 mA @ 240 VAC2 mA20 mA12 mA @ 240 VACSPST, N.O. & N.C.SPST, N.O.Switching ModeSPST, N.O.Operating Temperature
32°F to 120°F (0°C to 48.9°C)
0°F to 120°F (-17.8°C to 48.9°C)
0°F to 120°F (-17.8°C to 48.9°C)
Note: All AC voltage and current specifications are RMS values unless otherwise stated. – Stock Items
Typical Wiring
STEEL TERM. (COMMON)LOAD-PAK LOAD-PAK STEEL TERM. (COMMON) (TOP VIEW)(TOP VIEW)
BRASS TERM. LOAD-PAK LOAD-PAK BRASS TERM. (TOP VIEW)(TOP VIEW) SW. LOAD SW. LOAD LOAD
SENSOR SENSOR SWITCH SWITCH
B+VDCVDCB-B-LOADLOADLOAD B-B-COM. B+
N.O. SENSOR SENSOR SWITCH SWITCH
LOAD LOADLOADVAC NEUTRALB+N.C. SW.N.O.
SW. LOAD-PAK LOAD-PAK (TOP VIEW)(TOP VIEW)
SW.C1R1R1C1COM.N.C.
SPDT-PAK LOAD TERMINALS
“OFF” S2N.C.SENSOR SWITCH“ON” S1
SPDT-PAK, actuated by a single sensor to control two separate loads. R1
C1
R1
R = 100 OHM, 1/4 WATT RESISTOR N.O.
VAC NEUTRALSW.SENSOR SWITCH
LOAD-PAK, Part Number 25763, actuated by dry contact sensor to control load up to 2 amps, DC.
HOTLOADCOM.
COM. N.C. = .05N.O. MICROFARAD, 500 V, CAPACITOR SPDT-PAK LOAD TERMINALS
TRANSIENT PROTECTION FOR THE SPDT-PAK, The circuit shown or a properly-sized metal oxide varistor may be used.
NEUTRAL NEUTRAL VACCOM. ONLOADHOTVACVACHOT PUMP MOTOR
BRASS TERM. BRASS TERM.
LOADHOTLOAD ACS2 LOW LEVEL N.C. DRY
LOAD-PAK, Part Numbers 20173 and 26392 actuated by dry contact sensor to control load up to 10 amps, AC. B+
LOAD OFF
FLIP-PAK, providing pump up/down control. Refill: Low level permits S2 to close, starting refill FLIP-PAK, P/N 28196 OR 28244 pump. S1 Rising level allows S2 to open, and eventually HIGH OFF closes LEVEL S1 to actuate the FLIP-PAK “OFF” circuit and AC N.O. DRY 28196 OR 28244COM. stop the pump FLIP-PAK, motor.P/NThe FLIP-PAK “OFF” override assuresS2 pump shut-down evenONif S2LOAD failed to open. OFF LOW S3 AC VAC LEVEL PUMP of MOTOR Pump-Down: With “ON” and “OFF” connections S1 N.C. DRY COM. and S2 transposed at theLOAD FLIP-PAK, the pump is started by S1 and stopped ON by S2 at low level. The same “OFF” MOTOR STARTER override prevails. OR MOTOR
“OFF” S2
VAC
FLIP-PAK, P/N 28196 OR 28244 S3
OFF ACVACCOM.
C1 R = 100 OHM, 1/4 WATT RESISTOR = .05 MICROFARAD, 500 V, CAPACITOR
“ON” S1
ON
LOAD MOTOR STARTER OR MOTOR
With two normally open, momentary contact push buttons (S1 and S2), the FLIP-PAK provides solid-state control of the motor starter or the motor itself… if load requirements are within FLIP-PAK ratings. S3 provides a safety shut-down. With S3 closed, the “ON” push button (S1) is rendered ineffective by the “OFF” override feature of the FLIP-PAK.
Visit www.GemsSensors.com for most current information.
ELECTRONIC PRODUCTS
SENSOR SENSOR SWITCH SWITCH
HOT HOT VAC VAC LOADNEUTRAL NEUTRAL
FLIP-PAK, P/N 28196 OR 28244
S1 HIGH LEVEL N.O. DRY
L-13