Page 449

M.1 - Diagnostic LED Error Codes Error Codes

While the PiC900 is running, the DIAG LED on the CPU module will flash a three digit code signal if there is an error. For example, if there is a long pause-flashpause-flash-flash-pause-flash-flash-flash-long pause, the code is 123. The errors are described below. Code Error

Description

122

No math coprocessor

Attempted to perform floating point operation with no math coprocessor installed on the CPU.

123

Scan too long

A ladder scan loss has occurred because the CPU takes more than 200 ms to scan the application program. Whenever the scan light is out, the discrete outputs go to the OFF state and the analog outputs are zeroed.

124

Excessive overhead

The system overhead update time is excessive.

125

Insufficient memory

There is insufficient memory on the CPU to run the current program.

126

No hardware bit memory

There is no bit memory installed on the CPU and the program requires it.

127

No software bit memory

There is no bit memory capability via software and the program requires it.

222

Driver error

No driver support on the CPU for the I/O module. Update your system EPROMs.

22_

Master rack error

The I/O modules in the master rack do not match what was declared in the hardware master declaration table. The number of flashes in the third digit (_) identifies the slot number that is in error.

232*

Communications error

A failure has occurred in remote I/O communications.

233*

Number of racks error

The number of expansion racks in the system does not match the number of expansion racks declared in the expansion hardware declaration table.

M.1 -3

Page 450

Diagnostic LED Error Codes

3_ _* Expansion rack error

The I/O modules in the expansion rack(s) or the block I/O modules do not match what was declared in the expansion hardware declaration table. For rack expansion: The number of flashes in the second digit indicates the remote rack (1 through 8). The number of flashes in the third digit indicates the slot number. For block I/O modules: The number of flashes in the second and third digits indicates the block I/O module (01 through 77). The second digit will flash a 1 - 7, 10 for 0. The third digit will flash a 1 - 9, 10 for 0. For example, if the second digit flashes 3 times and the third digit flashes 10 times, the module is 30.

*Errors connected with I/O expansion. Refer to the I/O Driver Module write-up in the Hardware Manual for more information.