Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 9 of 60

PiC900 Hardware Manual, pages 59 to 66

Pages 59 to 66 of 508: A.4 - PiC90 - CSM/CPU (Document 108-31045-00); A.5 - RSM I/O - Remote Service Module I/O Driver

The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Giddings & Lewis 502-03550-02

Page 59

A.4 - PiC90 - CSM/CPU (Document 108-31045-00)

(This document is archived and available from Giddings & Lewis by requesting part number 108-31045-00.)

A.4 -1

Page 60

PiC90 - CSM/CPU (Document 108-31045-00)

NOTE

A.4 -2

Page 61

A.5 -

RSM I/O - Remote Service Module I/O Driver

Introduction

When a PiC90 3- or 5- slot rack is used as a remote or local expansion rack for a PiC900 master rack, an RSM I/O driver module is required in slot 1/2 of the PiC90 rack. (Each PiC90 used as an expansion rack must have an RSM I/O module.) The RSM I/O driver module converts AC power to regulated DC power. Through the bus, the RSM supplies this power to the modules in an expansion rack. Refer to Appendix N2 for information on I/O expansion connections. The DIAG LED turns on briefly while the diagnostic tests are running. Figure A5-1. RSM I/O - the Remote Service Module I/O Driver (for 3- or 5- Slot PiC90 Expansion Rack)

RSM I/O

Name of module

DIAG PWR/SCAN CONFIG DATA IN/OUT

LEDs

Run

(Key slot not used) Stop

ON

Power switch OFF

L / LINE1

Power connector

N / LINE2 E / GRND

I/O local expansion twisted pair out I/O local expansion twisted pair in Twisted pair shield

Door

In

Out

Fiber optic connections

A.5 -1

Page 62

RSM I/O - Remote Service Module I/O Driver

Connections

The RSM I/O driver module receives power through a 3-pin power connector. Figure A5-2 illustrates the connections as listed below. Module

AC Power Source

L / LINE 1 to Hot

N / LINE 2 to Common

E / GRND to Single Point Ground

Figure A5-2. AC power to the system CSM/RSM/RSM I/O Modules AC Power Source

ON OFF

Line 1 (HOT) Line 2 (COMMON)

L / LINE 1 N / LINE 2 E / GRND

GROUND SPG

AA22-4892

The pinout for the 6-pin I/O driver connector is shown in Figure A5-3. This connector is used for local I/O expansion using twisted pair wire. The top two connections are for the I/O expansion twisted pair out. The next two are for the I/O expansion twisted pair in. The fifth connection is a shield used with twisted pair wire. The sixth connection is not used. Remote I/O expansion uses fiber optic cable connected to the fiber optic connectors shown in Figure A5-1. NOTE: It is possible to combine local and remote expansion racks in the same system. Use twisted pair wiring to connect racks that are up to 40 feet apart and use fiber optic cable to connect racks that are up to 2000 feet apart.

EMC NOTE To ensure EMC compliance, use fiber optic cables only. In some applications using only local expansion racks, it may be possible to comply to EMC standards when using shielded twisted pair wires. Verification would have to be done on a system by system basis.

A.5 -2

Page 63

RSM I/O - Remote Service Module I/O Driver

Figure A5-3. Pinout for the I/O driver twisted pair connector

I/O expansion twisted pair out I/O expansion twisted pair in

+ + -

Shield - Used with twisted pair wire Not Used

CAUTION The system is polarity dependent. Always connect the positive (+) output of one module to the positive (+) input of the next and the negative (-) to the negative (-), etc. Always connect the positive (+) input of one module to the positive (+) output of the next and the negative (-) to the negative (-), etc. LEDs

The RSM I/O driver module has six LEDs to indicate status. They are shown in Figure A5-4. Figure A5-3. RSM I/O driver LEDs

DIAG PWR/SCAN CONFIG DATA IN/OUT

Diagnostic Power Scan This rack configured I/O expansion line activity out I/O expansion line activity in

A.5 -3

Page 64

RSM I/O - Remote Service Module I/O Driver

DIAG

PWR

SCAN

CONFIG

DATA IN

Diagnostic

Power

Scan

This rack configured

On

The DIAG LED goes on when power is on and testing is performed by the CPU in the master rack. NOTE: The processor in the CPU module automatically runs diagnostic tests on all modules in an I/O expansion loop at power up.

Off

It turns off when the module passes all the tests. During normal operation the DIAG LED should be off.

On

The PWR light should be on whenever power is on. It indicates that the + 5V supply is within tolerance. See the specification sheet at the end of the section. During normal operation the PWR LED should be on.

Off

No power on

On

The SCAN light indicates that the application program is being executed. During normal operation the SCAN LED should be on.

Off

If scan loss occurs the light will go off and there is an orderly shutdown procedure.

On

Communication established with this expansion rack connected in an I/O expansion loop.

Off

Communication not established

I/O expansion line Dull Indicates the line receiving in is active. activity in glow Off

DATA OUT

No activity in

I/O expansion line Dull Indicates the line transmitting out is active. activity out glow Off

No activity out

NOTE: The diagnostic LED on the CPU module flashes certain error codes connected with I/O expansion. These codes are listed in Appendix M.

A.5 -4

Page 65

RSM I/O - Remote Service Module I/O Driver

Theory of Operation

The RSM I/O driver module converts AC input power into DC power at voltages of + 5V, + 15 V, and - 15 V and supplies them to the logic side of the modules in the rack. External power supplies are used for the field side of the I/O modules. Such supplies are not routed through the RSM I/O driver module, but they should all have the same power cut-off switch as the PiC900. See the power distribution diagrams in the Hardware chapter..

CAUTION The on/off rocker switch on the face of the RSM I/O driver module does not control the I/O power supplies. Always shut off power at the main disconnect switch before you replace a module in the system rack. Specification Table Characteristic

RSM I/O driver specifications

Functions

Supplies regulated DC power to the hardware modules installed in the rack Allows additional racks of I/O modules to be connected to a PiC900 master rack

Part number

502-03876-02

AC power source

110-230 VAC, 47-63 Hz

Input connector

3-terminal plug connector, meets all specifications for touch safety in accordance with IEC 529 and DIN VDE 0470 part 1

Power output, total

40 W

Individual outputs

+ 5 V @ 5.0 A + 15 V @ 2.0 A -15 V @ .5 A

+ 5 V supply monitor

Trip points ± 5% ± .5%: 4.725 to 4.775V and 5.225 to 5.275 V PWR LED goes off and PiC900 shuts down

PiC9XX CPU module

Communication capabilities in the master rack

Logic side power requirements (typical)

510 mA @ +5V

A.5 -5

Page 66

RSM I/O - Remote Service Module I/O Driver

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

2.4" wide x 12" high x 8.4" deep (including latch) 61 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

A.5 -6