Page 121
Resolver Module (4, 2 channel)
Indicator light, module
DIAG LED goes off when the module passes its diagnostic tests
Logic side power requirements (typical for 4 ch)
473 mA @ 5V 133 mA @+15V 20 mA @ -15V 14 mA per energized input @ +15V 14 mA per energized input @ -15V 12 mA per fast input
Logic side power requirements (typical for 2 ch)
296 mA @ 5V 105 mA @ +15V 16 mA @ -15V 14 mA per energized input @ +15V 14 mA per energized input @ -15V 13 mA per fast input
Field side power dissipation, worst case
4 ch
1.4 W
2 ch
.7 W
Recommended resolver
Part number M.1200.0399 (old # 501-98409-00) Harowe 11BRW 300-F-1/10
Other suggested resolvers
Clifton 11BHW-0IE/A004 Kearfott CR41095050
Operating temperature range
7°C to 55°C (45°F to 131°F)
Storage temperature range
-40°C to 85°C (-40°F to 185°F)
Humidity
5 to 95%, non-condensing
EMC Compliant Emissions Noise immunity
Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge e(4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
117
Page 122
Resolver Module (4, 2 channel)
NOTES
118
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 123
Multi-Channel Resolver Module (12 channel)
Multi-Channel Resolver Module (12 channel) The input multi-channel resolver module can interface to 12 independent resolvers (or equivalent transducers). Feedback information from the resolvers is used to update the on-board memory. The position of each resolver can be read at any time by the PiC. For each channel, the module sends out two sine waves 90° out of phase with each other and receives a signal whose phase represents the angular position of the resolver. The resolution of the angular position is 4000 counts per revolution or 0.09 degrees. The DIAG LED goes on briefly while the diagnostic tests are running.
INPUT RESOLVER (Multi-Channel) Module (12 CH)
INPUT RESOLVER
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
Giddings & Lewis
Name of Module Diagnostic LED
Screw terminal connector
Door
PiC900 Controls Motion Solutions Product Guide
119
Page 124
Multi-Channel Resolver Module (12 channel) Specification Table
Characteristic
Input Resolver (12 ch) Module Specifications
Function
Measures the position of a transducer that accepts a 2phase quadrature excitation, such as a resolver or potentiometer M.1016.9231 (old # 502-03722-02) 40 pin card edge connector, screw terminals 2-phase quadrature for control transformer type of resolver 4KHz
Part number Field side connector Excitation method Excitation frequency RPO and QPO outputs 15V P-P (5.3V RMS) Output voltage Current per output channel, 100 mA max. Resolver transformer ratio .5 to 1.0 Resolution, resolver 4000 Feedback Units (FUs) per electrical revolution Resolution, potentiometer 1000 Feedback Units (FUs) per electrical revolution Accuracy at constant temper- ± 12 arc minutes ature Accuracy over temperature ± 5.4 arc minutes /10°F range Velocity, max. 15000 electrical RPM (1M FU/Sec.) Cable length, max. 6 ft. from module to terminal block (18 AWG) 100 ft. from terminal block to resolvers (twisted pair) Stored position value range 0-3999 Indicator light, module DIAG LED goes off when the module passes its power-on diagnostic tests Logic side power requirements 200 mA @ +5V (typical) 60 mA @ +15V 60 mA @ -15V Recommended resolver Giddings & Lewis part number 501-98409-00 Harowe 11BRW 300-F-1/10 Other suggested resolvers Clifton 11BHW-0IE/A004 Kearfott CR410959 Operating temperature range 7° C to 55° C (45° F to 131° F) Storage temperature range -40° C to 85° C (-40° F to 185° F) Humidity 5 to 95%, non-condensing
120
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 125
Multi-Channel Resolver Module (12 channel) EMC Compliant Emissions Noise immunity
UL and C/UL Listed Physical size Vibration (per IEC 68-2-6) Shock (per IEC 68-2-27)
Giddings & Lewis
Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information. File No. E126417 NRAQ Programmable Controllers 1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm 10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g) Four shocks per axis (15g/11 msec)
PiC900 Controls Motion Solutions Product Guide
121
Page 126
Servo Encoder with Analog I/O Module
Servo Encoder with Analog I/O Module The servo encoder with analog I/O module provides: • • • •
Two analog output channels Four analog input channels Three encoder input channels Three fast inputs
An LED goes on when the fast input for each encoder channel is energized. The DIAG LED goes on briefly while the diagnostic tests are running.
Servo Module Encoder with Analog Inputs SERVO ENCODER
Name of Module Diagnostic LED Indicator LEDs for fast inputs
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
122
Screw terminal connector
Door
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 127
Servo Encoder with Analog I/O Module Specification Table
Characteristic Function
Servo Encoder module specifications Converts a 16-bit digital word into a ±11V analog output signal for each of two channels Converts an analog input signal into a 12-bit digital word for each of four channels. Counts pulses from up to three encoders Latches the counter value at an index or 24 VDC fast input event M.1016.9329 (old # 502-03839-04) 482 mA @ +5V 42 mA @ +15V 62 mA @ -15V
Part number Logic side power requirements (typical)
Analog Output 1 mA per energized output 11 mA per energized output 11 mA per energized output
@ @ @
+5V +15V -15V
Analog Input 120 mA 112 mA
@ +5V @ +15V
Encoder
Field side connection Field side power dissipation, worst case Indicator light, module Indicator light Operating temperature range Storage temperature range Humidity EMC Compliant Emissions Noise immunity
UL and C/UL Listed
Giddings & Lewis
21 mA per energized input @ +5V 12 mA per fast input @ +5V 40 pin card edge connector, screw terminals 7.4 W DIAG LED goes off after the module passes its diagnostic tests LED is lit when current flows into the fast input 7°C to 55°C (45°F to 131°F) -40°C to 85°C (-40°F to 185°F) 5 to 95%, non-condensing Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information. File No. E126417 NRAQ Programmable Controllers
PiC900 Controls Motion Solutions Product Guide
123
Page 128
Servo Encoder with Analog I/O Module Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g) Four shocks per axis (15g/11 msec)
Shock (per IEC 68-2-27) Analog Output section (2 ch) Output channels Resolution Output voltage characteristics Nominal voltage range Voltage accuracy @ 11 V Output current, max. @ ±10V Output update time increment Output voltage after power up Response to scan loss
2 16 bits, or 65536 steps over the full output range ± 11V DC ± 5% ± 10 mA 32 µsec 0V ± 20 mV
Output ripple
All outputs reset to 0V ± 20 mV < 10 mVRMS at 30 KHz
Short circuit protection
Current limited outputs
Analog Input section (4 ch) Input channels 4 Resolution 12 bits, or 4096 steps over the full input range Input sensitivity (software selectable) Voltage ranges Unipolar Bipolar 0 to 10V ±10V 0 to 5V ±5V 0 to 2.5V ±2.5V 0 to 1.25V ±1.25V 0 to 1V ±1V 0 to .5V ±.5V 0 to .25V ±.25V 0 to 20 mA, 4 to 20 mA ±40V
Current range Common mode maximum voltage (The maximum voltage that can safely be applied between either input terminal and circuit common.) Common mode operating voltage ±11V (The maximum voltage that can be applied between either input terminal and circuit common with inputs still operating properly.) Internal current sense resistor 250 ohms Maximum current sense resistor .12 W power
124
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 129
Servo Encoder with Analog I/O Module Differential input resistance (each 1 M Ohms input to ground) Filter time constant - software selec- 1 ms, 10 ms, 100 ms tion Accuracy .5% of FSR at 25oC ± 100 PPM /oC 0 Offset From ±2 counts @ 10 V to ±8 counts @ .125 V Encoder Input section (3 ch) Input Encoder (3 ch) (A, B, and index) Guaranteed on, min. Input voltage, max. Input current, max. Signal pulse width, min. Quadrature signal frequency, max. Pulse encoder signal frequency, max. Encoder device
Stored position value range Fast input
Voltage max. Guaranteed on Guaranteed off Input impedance On/off time, max. Cable length, max.
Giddings & Lewis
Differential or single ended; differential recommended 2.5V DC @ 2.5 mA 7V DC 22 mA @ 7V DC .6 µs(600 ns) 250 KHz for A or B input (1 M FU count rate) 500 KHz for A or B input (500 KFU count rate) 1. Quadrature type incremental encoder (recommended) 2. Pulse type incremental encoder 24-bit up/down counter 24-bit latch Nominal 24V DC, switched externally to the module Active high or low Reverse polarity protected 30V DC 15V DC 5V DC 2.7 K 50 µs 200 ft. @ 250 KHz and 45° quad error (with differential driver)
PiC900 Controls Motion Solutions Product Guide
125
Page 130
Servo Encoder with Analog Output Module
Servo Encoder with Analog Output Module Depending on the model you have, the Servo encoder with analog output module provides: • Four, three, or two analog output channels • Three, two or one encoder input channels • Three, two, or one fast inputs
An LED goes on when the fast input for each encoder channel is energized. The DIAG LED goes on briefly while the diagnostic tests are running.
Servo Module (Encoder)
SERVO ENCODER
Name of Module Diagnostic LED Indicator LEDs for fast inputs
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
126
Screw terminal connector
Door
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis