Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 15 of 15

PiC900 Controls Motion Solutions Product Guide, pages 141 to 150

Pages 141 to 150 of 150

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Giddings & Lewis 502-03550-02

Page 141

Output Stepper Axis Module (8 channel)

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

137

Page 142

SERCOS Module for PiC

SERCOS Module for PiC The SERCOS module is an interface between the PiC and up to two fiber optic rings of from one to eight SERCOS slaves. The module contains an on-board processor. Five LEDs provide diagnostic information and transmit and receive status for the SERCOS ports. There are two SERCOS ports located at the bottom of the module. Each port has a receive and a transmit fiber optic connector. There is also an RS232 port used for loading FLASH memory updates. NOTE: The SERCOS module must be used with an EMC-compliant or CEmarked rack.

SERCOS Module

Name of Module Diagnostic LED

SERCOS Port 1 Port 2

SERCOS LEDs

RS232 port 9-pin D

Port 2

R

T R

T Port 1

Key T = Transmit R = Receive

SERCOS Ports Fiber Optic Connections

138

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 143

SERCOS Module for PiC Specification Table

Characteristic

SERCOS Module Specifications

Function

Interfaces with up to two rings with from one to eight digital drives

Part number

One-Ring Module M.1016.9429 (old # 502-03944-10) Two-Ring Module M.1016.9428 (old # 502-03944-00)

SERCOS port

SMA female connectors for interfacing to 1000 µ meter plastic fiber optic cable with SMA male connectors

Update port

RS232 interface Fiber optic receiver specifications: Peak input power (optical level low) Peak input power (optical level high Fiber optic transmitter specifications: Peak output power (optical level high)

Logic side power require.

-31.2 dBm max -20.0 dBm min -5 .0 dBm max -10.5 -5.5 dBm min dBm max

575 mA @ 5V

Operating temperature range 7° C to 55° C (45° F to 131° F) Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

139

Page 144

SERCOS Module for PiC Specification Table for the Fiber Optic Cable

Characteristics

Fiber optic cable specifications

Function

For use with SERCOS rings with segments from 0 to 30 meters (98 feet)

Type

Plastic with step index profile

Core diameter Fiber diameter

980µm ±60µm 1000µm ±60µm

Operating tempera- 0° C to 55° C (32° F to 131° F) ture Minimum bend radius

One time:

30mm

Continuous:

80mm

Tensile strength

One time:

250N

Continuous:

100N

Connectors

SMA style which accommodates 1000µm size cable

140

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 145

PiC900 CONTROLS MOTION SOLUTIONS PRODUCT GUIDE

PiC 900 Options and Accessories

Giddings & Lewis

Page 146

This page is a scan with no text; see it in the PDF.

Page 147

I/O Wiring Harness

PiC Options and Accessories I/O Wiring Harness There is an optional wiring harness available which can be used to replace the discrete wiring from some of the PiC input and output modules (see table below) to field side terminal blocks. It consists of a cable and a terminal strip interface connector as shown below. The pinouts on the terminal strip interface replicate the pinouts for the hardware module as depicted in the Hardware Manual; i.e., pin 1 on the connector is pin 1 on the module.

Cable

Terminal Strip Interface

*Cables are 5’ in length. Other lengths are available. Consult factory for information.

OPTIONS FOR OUTPUT MODULES Module Part No.

Order Cable Part No.

Order Terminal Block Interface Part No.

32

M.1016.9070 (old # 502-03640-02)

M.1016.9537 (old # 502-04046-05)

M.1016.1595 (old # 401-56417-00)

16

M.1016.8933 (old # 502-03640-02)

M.1016.9542 (old # 502-04048-05)*

M.1016.1597 (old # 401-56419-00)

16 Clamped 16 Unclamped

M.1016.9127 (old # 502-03674-02)

M.1016.9537 (old # 502-04046-05)*

M.1016.9537 (old # 401-56417-00)

32 Clamped

M.1016.9130 (old # 502-03674-22)

M.1016.9537 (old # 502-04046-05)

M.1016.9537 (old # 502-056417-00)

32 Unclamped

M.1016..9133 (old # 502-03674-42)

M.1016.9537 (old # 502-04046-05)

M.1016.9537 (old # 502-056417-00)

32

M.1016.9076 (old # 502-03641-03)

M.1016.9537 (old # 502-04046-05)

M.1016.9537 (old # 502-056417-00)

16

M.1016.8943 (old # 502-03551-03)

M.1016.9542 (old # 502-04048-05)*

M.1016.1597 (old # 401-56419-00)

Voltage

No. of Points

24 VDC Source

24 VDC Sink

120/240 VAC

*This part number is for a 5-foot cable. Other lengths are available. Please consult the factory for information

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

143

Page 148

I/O Wiring Harness

OPTIONS FOR INPUT MODULES Voltage

No. of Points

Module Part No.

Order Cable Part No.

Order Terminal Block Interface Part No.

24 VDC

32 (Sink or Soucrce)

M.1016.9010 (old # 502-03605-00)

M.1016.9532 (old # 502-04043-05)*

M.1016.1596 (old # 401-56418-00)

16 (Sink or Soucrce)

M.1016.8929 (old # 502-03548-00)

M.1016.9540 (old # 502-04047-05)*

M.1016.1598 (old # 401-56419-01)

12 VDC

32 (Sink or Source)

M.1016.9085 (old # 502-03643-02)

M.1016.9532 (old # 502-04043-05)*

M.1016.1596 (old # 401-56418-00)

120 VAC

16

M.1016.9076 (old # 502-03550-02))

M.1016.9540 (old # 502-04047-05)*

M.1016.1598 (old # 401-56419-01)

*This part number is for a 5-foot cable. Other lengths are available. Please consult the factory for information

Description

New Part Number Old Part Number

Discrete I/O Wiring Harness Cable for 16DC and 16 AC Inputs

M.1016.9540*

502-04047-05*

Discrete I/O Wiring Harness Cable for 16 DC and 16 AC Outputs

M.1016.9542*

502-04048-05*

Discrete I/O Wiring Harness Cable for 32 DC Inputs

M.1016.9532*

502-04043-05*

Discrete I/O Wiring Harness Cable for 32 DC and 16 AC Outputs

M.1016.9537*

502-04046-05*

Terminal Block for 16-Point Input Modules

M.1016.1598

401-56419-01

Terminal Block for 16-Point Output Modules

M.1016.1597

401-56419-00

Terminal Block for 32-Point Input Modules

M.1016.1596

401-56418-00

Terminal Block for 32-Point Output Modules

M.1016.1595

401-56417-00

PiC900 CPU Battery Backup Module with Battery Test

M.1016.9521

502-04030-00

*This part number is for a 5-foot cable. Other lengths are available. Please consult the factory for information

144

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 149

Battery Backup Board

Battery Backup Board There is a battery backup board available to use with PiC CPUs. It maintains the memory contents when the CPU is not in a rack; i. e., when it is in transit. Battery Clip

Test LED

Board Connector

+ 502-04030-00 Battery

Test Push button

Item

Battery Backup Board Part Number

Replacement Battery

Battery Backup Board with LED and Test Push Button

M.1016.9521 (old # 502-04030-00)

3V Panasonic BR2330 or equivalent

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

145

Page 150

Battery Backup Board

NOTES

146

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis