Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 2 of 15

PiC900 Controls Motion Solutions Product Guide, pages 11 to 20

Pages 11 to 20 of 150

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Giddings & Lewis 502-03550-02

Page 11

System Racks The 10-slot System Rack

13.375”/340mm

14.0”/355mm

.365 "/9.3 mm

7.0" / 178mm .265 "/6.7mm

14.0" / 356mm

1.4"/35.6 mm

16.8" / 427mm

The 13-slot System Rack

13.375”/340mm

14.0”/355mm

.365 "/9.3 mm

9.4" / 239mm .265 "/6.7mm

1.4"/35.6 mm

Giddings & Lewis

18.8" / 478mm 21.6" / 549mm

PiC900 Controls Motion Solutions Product Guide

7

Page 12

System Racks

8

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 13

PiC900 CONTROLS MOTION SOLUTIONS PRODUCT GUIDE

PiC Family CSM/ RSM Modules

Giddings & Lewis

Page 14

This page is a scan with no text; see it in the PDF.

Page 15

CSM Module/RSM Module

CSM Module/RSM Module The Central Service Module (CSM) and the Remote Service Module (RSM) convert incoming power to regulated DC power. Through the bus, the CSM supplies this power to the modules in the master rack and the RSM supplies this power to the modules in an expansion rack. The CSM has the following additional features: Scan control which includes a key switch to run/stop the scan when power is on. A lithium battery to back up such items as non-volatile RAM in the CPU module and the time-of-day clock on the CSM module when power is turned off. • An internal clock to provide time of day and date when needed by the software. • •

The CSM and the RSM must always be located in the first slot on the left in the master rack and expansion rack respectively. CSM - the Central Service Module (for master rack)

CSM

Name of Module DIAG

RSM - the Remote Service Module (for expansion rack)

RSM

Name of Module DIAG

PWR SCAN BATT

LEDs

PWR SCAN BATT

LEDs

Run

Key slot

Run

Key slot (not used)

Stop

Stop

Door ON

Power switch

OFF

L/LINE1 N/LINE2 E/GRND

Giddings & Lewis

Door ON

Power switch

OFF

Power connector

L/LINE1 N/LINE2 E/GRND

PiC900 Controls Motion Solutions Product Guide

Power connector

11

Page 16

CSM Module/RSM Module Specification Table Characteristic

CSM/RSM specifications

Functions

Supplies regulated DC power to the hardware modules installed in the rack

AC power source 110-230 VAC, 47-63 Hz, 2 A Model

Part Number

CSM-50

M.1016.8879 (old # 502-03512-03)

CSM-60

M.1016.9294 (old # 502-03813-03)

RSM-50

M.1016.9243 (old # 502-03732-03)

RSM-60

M.1016.9308 (old # 502-03817-03)

DC power source 20 - 60 VDC, 3 A Model

Part Number

CSM-50 M.1016.9475 (old # 502-03973-00) (24 VDC) Input connector

3-terminal plug connector, meets all specifications for touch safety in accordance with IEC 529 and DIN VDE 0470 part 1

Power output, total Model

Power

CSM/RSM-50

50 W

CSM/RSM-60

60 W

CSM 24 VDC

50 W

+5 V @ 4.0 A

+5 V @ 8.5 A

Individual outputs +5 V @ 4.0 A

+15 V @ 2.0 A +15 V @ 1.5 A + 15 V @ 1.0 A -15 V @ .5 A

12

-15 V @ 1.5 A -15 V @ .5 A

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 17

CSM Module/RSM Module

Battery (CSM only) Part number

1.2 Ah 3 V, 2/3 A lithium battery M.1015.9316 (old # 401-52446-00)

+ 5 V supply monitor

Trip points ± 5% ± .5%: 4.725 to 4.775 V and 5.225 to 5.275 V PWR LED goes off and PiC shuts down

± 15 V supply monitor

Trip points ± 8% ± 2%: 13.5 to 14.1 V and 15.9 to 16.5 V

Time-of-day clock (CSM only) Access via PiCPro or application program. Clock tolerance (CSM only)

At 25°C, ±1 second per day Over temperature, voltage and aging variation, +2/-12 seconds per day

Logic side power requirements (typical)

25 mA @ +5 V 2 mA @ +15 V 2 mA @ - 15 V 2 µA @ +3 V (from battery during power down on CSM)

Operating temperature range

7°C to 55°C (45°F to 131°F)

Storage temperature range

-40°C to 85°C (-40°F to 185°F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions

Refer to the EMC Guidelines for more information. Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines

Noise immunity

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

13

Page 18

CSM Module/RSM Module CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/ EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN5501/CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61100-4-3, ENV50141, and ENV50204 File No. E126417 NRAQ Programmable Controllers

UL and C/UL Listed (CSM/RSM-50) Physical size

2.4" wide x 12" high x 8.4" deep (including latch) 61 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-7)

10-57 Hz (constant amplitude .15 mm) 57-2000Hz (acceleration 2 g

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

14

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 19

PiC90 RSM I/O Module

PiC90 RSM I/O Module When a PiC90 3- or 5-slot rack is used as a remote or local expansion rack for a PiC900 master rack, an RSM I/O driver module is required in slot 1/2 of the PiC90 rack. The RSM I/O driver module converts AC power to regulated DC power. Through the bus, the RSM supplies this power to the modules in an expansion rack. A PiC900 system may include up to eight expansion racks containing I/O modules. The RSM I/O driver module must be installed in each PiC90 3- or 5-slot expansion rack and an RSM module and an I/O driver module must be installed in each PiC900 7-, 10-, or 13-slot expansion rack. The DIAG LED turns on briefly while the diagnostic tests are running. RSM I/O - the Remote Service Module I/O Driver (for 3- or 5- slot PiC90 expansion rack)

RSM I/O

Name of Module

DIAG PWRSCAN CONFIG DATA IN/OUT

LEDs

(Key slot not used)

Run Stop ON

Power switch

OFF L/LINE1 N/LINE2 E/GRND

Power connector I/O local expansion twisted pair out I/O local expansion twisted pair in

Door

In

Out

Fiber optic connections

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

15

Page 20

PiC90 RSM I/O Module Specification Table

Characteristic

RSM I/O driver specifications

Functions

Supplies regulated DC power to hardware modules installed in the rack and allows additional racks of I/O modules to be connected to a PiC900 master rack

Part number

M.1016.9385 (old # 502-03876-02)

AC power source

120-230 V AC, 47-63 Hz

Input connector

3-terminal plug connector, meets all specifications for touch safety in accordance with IEC 529 and DIN VDE 0470 part 1

Power output, total

40 W

Individual outputs

+5V @ + 15 V @ -15 V @

5.0 A 2.0 A .5 A

+ 5 V supply monitor

Trip points ± 5% ± .5%: 4.725 to 4.775V and 5.225 to 5.275 V PWR LED goes off and PiC900 shuts down

Logic side power requirements (typical)

510 mA @ +5V

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions

Refer to the EMC Guidelines for more information. Operates with emissions below EN55011/ CISPR 11Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines

Noise immunity

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

2.4" wide x 12" high x 8.4" deep (including latch) 61 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11msec)

16

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis