The text of a manual · part 2 of 15
PiC900 Controls Motion Solutions Product Guide, pages 11 to 20
Pages 11 to 20 of 150
The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 11
System Racks The 10-slot System Rack
13.375”/340mm
14.0”/355mm
.365 "/9.3 mm
7.0" / 178mm .265 "/6.7mm
14.0" / 356mm
1.4"/35.6 mm
16.8" / 427mm
The 13-slot System Rack
13.375”/340mm
14.0”/355mm
.365 "/9.3 mm
9.4" / 239mm .265 "/6.7mm
1.4"/35.6 mm
Giddings & Lewis
18.8" / 478mm 21.6" / 549mm
PiC900 Controls Motion Solutions Product Guide
7
Page 12
System Racks
8
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 13
PiC900 CONTROLS MOTION SOLUTIONS PRODUCT GUIDE
PiC Family CSM/ RSM Modules
Giddings & Lewis
Page 14
Page 15
CSM Module/RSM Module
CSM Module/RSM Module The Central Service Module (CSM) and the Remote Service Module (RSM) convert incoming power to regulated DC power. Through the bus, the CSM supplies this power to the modules in the master rack and the RSM supplies this power to the modules in an expansion rack. The CSM has the following additional features: Scan control which includes a key switch to run/stop the scan when power is on. A lithium battery to back up such items as non-volatile RAM in the CPU module and the time-of-day clock on the CSM module when power is turned off. • An internal clock to provide time of day and date when needed by the software. • •
The CSM and the RSM must always be located in the first slot on the left in the master rack and expansion rack respectively. CSM - the Central Service Module (for master rack)
CSM
Name of Module DIAG
RSM - the Remote Service Module (for expansion rack)
RSM
Name of Module DIAG
PWR SCAN BATT
LEDs
PWR SCAN BATT
LEDs
Run
Key slot
Run
Key slot (not used)
Stop
Stop
Door ON
Power switch
OFF
L/LINE1 N/LINE2 E/GRND
Giddings & Lewis
Door ON
Power switch
OFF
Power connector
L/LINE1 N/LINE2 E/GRND
PiC900 Controls Motion Solutions Product Guide
Power connector
11
Page 16
CSM Module/RSM Module Specification Table Characteristic
CSM/RSM specifications
Functions
Supplies regulated DC power to the hardware modules installed in the rack
AC power source 110-230 VAC, 47-63 Hz, 2 A Model
Part Number
CSM-50
M.1016.8879 (old # 502-03512-03)
CSM-60
M.1016.9294 (old # 502-03813-03)
RSM-50
M.1016.9243 (old # 502-03732-03)
RSM-60
M.1016.9308 (old # 502-03817-03)
DC power source 20 - 60 VDC, 3 A Model
Part Number
CSM-50 M.1016.9475 (old # 502-03973-00) (24 VDC) Input connector
3-terminal plug connector, meets all specifications for touch safety in accordance with IEC 529 and DIN VDE 0470 part 1
Power output, total Model
Power
CSM/RSM-50
50 W
CSM/RSM-60
60 W
CSM 24 VDC
50 W
+5 V @ 4.0 A
+5 V @ 8.5 A
Individual outputs +5 V @ 4.0 A
+15 V @ 2.0 A +15 V @ 1.5 A + 15 V @ 1.0 A -15 V @ .5 A
12
-15 V @ 1.5 A -15 V @ .5 A
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 17
CSM Module/RSM Module
Battery (CSM only) Part number
1.2 Ah 3 V, 2/3 A lithium battery M.1015.9316 (old # 401-52446-00)
+ 5 V supply monitor
Trip points ± 5% ± .5%: 4.725 to 4.775 V and 5.225 to 5.275 V PWR LED goes off and PiC shuts down
± 15 V supply monitor
Trip points ± 8% ± 2%: 13.5 to 14.1 V and 15.9 to 16.5 V
Time-of-day clock (CSM only) Access via PiCPro or application program. Clock tolerance (CSM only)
At 25°C, ±1 second per day Over temperature, voltage and aging variation, +2/-12 seconds per day
Logic side power requirements (typical)
25 mA @ +5 V 2 mA @ +15 V 2 mA @ - 15 V 2 µA @ +3 V (from battery during power down on CSM)
Operating temperature range
7°C to 55°C (45°F to 131°F)
Storage temperature range
-40°C to 85°C (-40°F to 185°F)
Humidity
5 to 95%, non-condensing
EMC Compliant Emissions
Refer to the EMC Guidelines for more information. Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines
Noise immunity
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
13
Page 18
CSM Module/RSM Module CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/ EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN5501/CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61100-4-3, ENV50141, and ENV50204 File No. E126417 NRAQ Programmable Controllers
UL and C/UL Listed (CSM/RSM-50) Physical size
2.4" wide x 12" high x 8.4" deep (including latch) 61 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-7)
10-57 Hz (constant amplitude .15 mm) 57-2000Hz (acceleration 2 g
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
14
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 19
PiC90 RSM I/O Module
PiC90 RSM I/O Module When a PiC90 3- or 5-slot rack is used as a remote or local expansion rack for a PiC900 master rack, an RSM I/O driver module is required in slot 1/2 of the PiC90 rack. The RSM I/O driver module converts AC power to regulated DC power. Through the bus, the RSM supplies this power to the modules in an expansion rack. A PiC900 system may include up to eight expansion racks containing I/O modules. The RSM I/O driver module must be installed in each PiC90 3- or 5-slot expansion rack and an RSM module and an I/O driver module must be installed in each PiC900 7-, 10-, or 13-slot expansion rack. The DIAG LED turns on briefly while the diagnostic tests are running. RSM I/O - the Remote Service Module I/O Driver (for 3- or 5- slot PiC90 expansion rack)
RSM I/O
Name of Module
DIAG PWRSCAN CONFIG DATA IN/OUT
LEDs
(Key slot not used)
Run Stop ON
Power switch
OFF L/LINE1 N/LINE2 E/GRND
Power connector I/O local expansion twisted pair out I/O local expansion twisted pair in
Door
In
Out
Fiber optic connections
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
15
Page 20
PiC90 RSM I/O Module Specification Table
Characteristic
RSM I/O driver specifications
Functions
Supplies regulated DC power to hardware modules installed in the rack and allows additional racks of I/O modules to be connected to a PiC900 master rack
Part number
M.1016.9385 (old # 502-03876-02)
AC power source
120-230 V AC, 47-63 Hz
Input connector
3-terminal plug connector, meets all specifications for touch safety in accordance with IEC 529 and DIN VDE 0470 part 1
Power output, total
40 W
Individual outputs
+5V @ + 15 V @ -15 V @
5.0 A 2.0 A .5 A
+ 5 V supply monitor
Trip points ± 5% ± .5%: 4.725 to 4.775V and 5.225 to 5.275 V PWR LED goes off and PiC900 shuts down
Logic side power requirements (typical)
510 mA @ +5V
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
EMC Compliant Emissions
Refer to the EMC Guidelines for more information. Operates with emissions below EN55011/ CISPR 11Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines
Noise immunity
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
2.4" wide x 12" high x 8.4" deep (including latch) 61 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11msec)
16
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis