Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 2 of 3

Industrial Line: Rail Family, pages 9 to 16

Pages 9 to 16 of 23

The original document is the PDF (3.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hirschmann RT1-TP/FL

Page 9

• Rugged, heavy-duty design • Fault tolerant by means of redundant voltage supply • Ultimate reliability due to no-fan operation

The Rail Hub Family provides you with a flexible and cost-effective solution for designing ETHERNET networks in compliance with IEEE 802.3 based on fiber optic and copper technology. It is especially suitable for use in a harsh industrial environment.

• Fault tolerant Redundant ring structure • Flexible topology structures (Line-Ring-Star) • Easily installed on a standard DIN Rail and simple maintenance • Signaling contacts for function control (e.g. to PLC´s) • Operating temperature

With the Rail Hubs you can configure small to medium sized networks easily and cost-effectivly. An important feature is the fast media redundancy in an optical ring structure. The failure of a fiber optic cable or a Rail Hub will be recognized instantly (< 20 ms). By switching to the redundant fiber optic link operation will continue without any loss of data. An additional benefit of the Hirschmann ring topology is network expansion which can be performed without impacting the network availability.

from 0ºC to +60ºC (32ºF to 140ºF)

The Rail Hubs provide three twisted pair and two fiber optic ports integrated into a compact and rugged chassis. This allows you to connect up to

Rail Hub Family three terminals, PLC´s, I/O modules or twisted pair segments. Various network structures can be realized with the Rail Hubs: Line structures via fiber optic or twisted pair and redundant optical ring structures via the fiber optic ports. The Rail Hubs can also be combined with fiber optic interface cards of the ASGE-, ALS and AMC families for integration at the plant network. The Rail hubs are available in two versions: The OTP3-FL2 offers you three twisted pair ports with DB9 connectors, the RH1-TP/FL provides three twisted pair ports with standard RJ45 connectors. The integrated fast media redundancy in an optical ring structure guarantees you a fault-tolerant network. The Rail Hubs can be easily fixed on a standard DIN Rail without any further configurations. The 24 V DC operating voltage is supplied over the terminal block and can also be configured for redundancy. Integrated into the terminal block is a signaling contact which sends fault messages of the Rail Hub as High/Low signal, e.g. to an I/O block of a PLC or any other control device. This is activated as soon as any event occurs in the Rail Hub, i.e., voltage supply malfunction or at least one fiber optic or twisted pair port reports a faulty link status. Built-in LED´s indicate collisions, link status, power failure and data receipt for on-site diagnostics.

Page 10

Product

Order No.:

OTP3-FL2

943 440-001

Technology

ETHERNET 10 Mbit/s

Interfaces

3 10BASE-T ports with DB9 connectors (shielded) 2 10BASE-FL ports with BFOC connectors 1 x 5 pin pluggable terminal block

Product

Order No.:

RH1-TP/FL

943 613-001

Technology

ETHERNET 10 Mbit/s

Interfaces

3 10BASE-T ports with RJ45 connectors (shielded) 2 10BASE-FL ports with BFOC connectors 1 x 5 pin pluggable terminal block

Operating voltage

18 to 32 V DC, Safety low voltage (redundant inputs)

Power consumption typ. 160 mA, max. 280 mA

Maximum range

OTP3-FL2; RH1-TP/FL:

OTP3-FL2

50/125µm-fiber: max. 2.600 m (max. 8.500 ft) > 11 dB Link Budget 62,5/125µm-fiber: max. 3.100 m (max. 10.000 ft) > 14 dB Link Budget TP-line length: max. 100 m (max. 330 ft) LED indicators

Power, Data, Collision, Link status per port

Mechanical construction - Dimensions W x H x D

80 x 140 x 85 mm (31.5 x 55.1 x 33.5 in)

- Weight

900 g (2 lb)

- Operating temperature

0 °C to +60 °C (32° F to 140° F)

- Operating humidity

10% to 95% (non condensing)

- Enclosure

IP 30

- Approvals

CE, cUL, FCC, FM

Scope of delivery

Rail Hub OTP3-FL2 or RH1-TP/FL Terminal block for supply voltage Description and operating instructions

RH1-TP/FL

Page 11

• Rugged, heavy-duty design • Fault tolerant by means of redundant voltage supply • Ultimate reliability due to no-fan operation

The Rail Hub RH1-TP allows you the fast and cost-effective expansion of your network. It has four twisted pair ports. Via twisted pair you can connect up to four devices or further twisted pair segments. The Rail Hubs can be easily fixed on a standard DIN Rail without any furt-

• Fast and cost-effective expansion of your network • Easily fixed on a standard DIN Rail and simple commissioning • Signaling contacts for function control (e.g. to PLC´s) • Operating temperature her configurations. The 24 V DC operating voltage is supplied over the terminal block and can also be configured for redundancy. Integrated into the terminal block is a signaling contact which sends fault messages of the Rail Hub as High/Low signal, e.g. to an I/O block of a PLC or any other control device. This is activated as soon as any event from 0ºC to +60ºC occurs in the Rail Hub, i.e., voltage supply malfunction or at least one twi-

(32ºF to 140ºF)

sted pair port reports a faulty link status. Built-in LED´s indicate collisions, link status, power failure and data receipt

Rail Hub Family for on-site diagnostics.

Control Network

RH1-TP/FL

RH1-TP/FL

Port 1

Port 1

Port 2

Port 2

Port 3

Port 3

Robot

Redundant ETHERNET (10 Mbps) shared fiber ring

Operator station

PLC

RH1-TP/FL

RH1-TP/FL

Port 1

Port 1

Soft -PLC

Port 2

Port 2

RH1-TP/FL

Port 3

Port 3

Port 1

I/O - Block

Port 2

Port 3

RH1-TP

Port 1

Port 2

Port 3

Port 4

RH1-TP

Port 1

Port 2

Port 3

Port 4

Page 12

Product

Order No.:

RH1-TP

943 639-001

Technology

ETHERNET 10 Mbit/s

Interfaces

4 10BASE-T ports with RJ45 connectors (shielded) 1 x 5 pin pluggable terminal block

Operating voltage

DC 18 to 32 V Safety low voltage (redundant inputs)

Power consumption typ. 90 mA

Maximum range

TP-line length: max. 100 m (max. 330 ft)

LED indicators

Power, Data, Collision, Link status per port

Mechanical construction - Dimensions W x H x D

40 x 125 x 80 mm (15.8 x 49.2 x 31.5 in)

- Weight

520 g (1.2 lb)

- Operating temperature

0 °C to +60 °C (32° F to 140° F)

- Operating humidity

10% to 95% (non condensing)

- Enclosure

IP 30

- Approvals

CE, cUL, FCC, FM

Scope of delivery

Rail Hub RH1-TP Terminal block for supply voltage Description and operating instructions

RH1-TP

Page 13

• Rugged, heavy-duty design • Fault tolerant by means of redundant voltage supply • Ultimate reliability due to no-fan operation • Fault tolerant Redundant

The Rail Switch Family provides you with a flexible and cost-effective solution for designing ETHERNET networks in compliance with IEEE 802.3 based on fiber optic and copper technology. It is especially suitable for use in a harsh industrial environment.

ring structure - Fast Media

With the Rail Switches you can configure medium to large sized net-redundancy (< 300 ms)

works easily and cost-effective. An important feature is the fast

• Very high cascading depth/ network expansion (up to media redundancy in an optical ring structure. The failure of a fiber

50 Switches)

optic cable or a Rail Switch will be recognized promptly (< 300 ms).

• Operating temperature from 0°C to +60°C ( 32° F to 140° F )

By switching to the redundant fiber optic link operation will continue without any loss of data. The integrated fast media redundancy

• Cost effectiv DIN-Rail guarantees you a fault-tolerant network.

mounting

Rail Switch Family

An additional benefit of the Hirschmann ring topology is network expansion, which can be performed without impacting the network availability. The Rail Switches offers a very high network expansions of up to 2000 km in a ring structure and several thousands of kilometers in a bus structure. The Rail Switches provide you with ten switched ports integrated into a compact and rugged chassis. They are available with eight twisted pair ports based on 10BASE-T to connect terminals, PLC´s, I/O blocks or other twisted pair segments and two 100 Mbit/s ports based on the Fast Ethernet Standard. The Rail Switches are available in four versions offering combinations of twisted pair and multimode as well as singlemode 100 M Interfaces.

Robot

100 M

Operator station

100 M Rail Switch RS1-TP

PLC

RH1-TP/FL

Soft PLC RH1-TP Port 1

Port 2

Port 1

Port 2

Port 3

Port 4

Port 3

I/O - Block

RH1-TP

RH1-TP/FL

Port 1

Port 2

Port 3

Redundant ETHERNET (10 Mbps) shared fiber ring

RH1-TP/FL

Port 1

Port 2

Port 3

Port 1

Port 2

Port 3

Port 4

RH1-TP/FL

Port 1

Port 2

RH1-TP

Port 3

Port 1

Port 2

Port 3

Port 4

Page 14

Product

Order No.:

RS1-FX/FX

943 606-031

Interfaces

8 10BASE-T ports with RJ45 connectors (shielded) 2 100BASE-FX ports with SC connectors 1 x 5 pin pluggable terminal block

Product

Order No.:

RS1-TX/TX

943 606-001

Interfaces

8 10BASE-T ports with RJ45 connectors (shielded) 2 100BASE-TX ports with RJ45 connectors 1 x 5 pin pluggable terminal block

Product

Order No.:

RS1-TX/FX

943 606-032

Interfaces

8 ports based on 10BASE-T with RJ45 connectors (shielded) 1 100BASE-TX port with RJ45 connector 1 100BASE-FX-multimode port with SC connector 1 x 5 pin pluggable terminal block

Product

Order No.:

RS1-TX/FX-SM

943 606-033

Interfaces

8 10BASE-T ports with RJ45 connectors (shielded) 1 100BASE-TX port with RJ45 connector 1 100BASE-FX-singlemode port with SC connectors 1 x 5 pin pluggable terminal block

Technology

ETHERNET 10 Mbit/s and Fast ETHERNET 100 Mbit/s

Operating voltage

DC 18 to 32 V Safety low voltage (redundant inputs)

Power consumption max. 500 mA/max. 0.9 A

Maximum range

FX-multimode port: 50/125µm-fiber: max. 3.000 m (max. 8.500 ft) > 11 dB Link Budget 62,5/125µm-fiber: max.3.000 m (max. 10.000 ft) > 14 dB Link Budget FX-singlemode port: 10/125 µm-fiber: max. 40.000 m (max. 130.000 ft) > 11 dB Link Budget TP-line length: max. 100 m (max. 330 ft)

LED indicators

Power, Data, Collision, Link status per port

Mechanical construction - Dimensions W x H x D

209 x140x 85 mm (82.3 x 55.1x33.5 in)

- Weight

1.4 Kg (3.2 lb)

- Operating temperature

0 °C to +60 °C (32° F to 140° F)

- Operating humidity

10% to 95% (non condensing)

- Enclosure

IP 20

- Approvals

CE, cUL, FCC, FM

Scope of delivery

Rail Switch RS1-xx/xx or RM1 Terminal block for supply voltage Description and operating instruction

RS 1

Page 15

• Fault tolerant redundant

The Redundancy Manager RM1 has been specifically designed for use ring structure - Fast Media Redundancy (< 300 ms)

in redundant ring structures together with the Rail Switches.

• Fault tolerant by means of

The control of the redundant ring is handled by the Redundancy Manager.

redundant voltage supply

It supervises the ring and is responsible for detection and dynamic bypass

• ultimate reliabitity due to of network fault, all within 300 ms.

no fan operation • Signaling contacts for

The Redundancy Manager is built into a 19“ chassis and suitable for use in function control control rooms.

(e.g. to PLC´s)

It provides eight twisted pair ports based on 10BASE-T to connect operator stations, PLC´s, I/O blocks or other twisted pair segments as well as two free slots for 100 Mbit/s modules. You can select between modules for 100BASE-TX and 100BASE-FX.

Rail Switch Family

The 24 V DC operating voltage is supplied over the terminal block and can also be configured for redundancy. Integrated into the terminal block is a signaling contact which sends fault messages of the Redundancy Manager as High/Low signal, e.g. to an I/O block of a PLC or any other control device. This is activated as soon as any event occurs in the Redundancy Manager, i.e., voltage supply malfunction or at least one fiber optic or twisted pair port reports a faulty link status.

Fast media redundancy using electrical or optical cables RM1

Rail Switch RS1-TP

Redundant fast ETHERNET (100 Mbps) switched ring

Robot Operator station Rail Switch RS1-TP

PLC

I/O - Block

Rail Switch RS1-TP

Page 16

Product

Order No.:

RM1

943 632-001

Interfaces

8 10BASE-T ports with RJ45 connectors (shielded) 2 free slots for 100BASE-X-Modules 1 x 5 pin pluggable terminal block

100BASE-X-Modules:

ETSXM-01TP(FE)

943 567-001

Interface

1 100BASE-FX port Full duplex with RJ45 connector

ETSXM-01MM(FE)

943 568-001

Interface

1 100BASE-FX port Full duplex with SC connectors

Technology

ETHERNET 10 Mbit/s and Fast ETHERNET 100 Mbit/s

Operating voltage

DC 18 to 32 V Safety low voltage (redundant inputs)

Power consumption max. 500 mA / max. 0.9 A

Maximum range

FX-multimode port: 50/125µm-fiber: max. 3.000 m (max. 8.500 ft) > 11 dB Link Budget 62,5/125µm-fiber: max. 3.000 m (max. 10.000 ft) > 14 dB Link Budget FX-singlemode port: 10/125 µm-fiber: max. 40.000 m (max. 130.000 ft) > 11 dB Link Budget

TP-line length:

max. 100 m (max. 330 ft)

LED indicators

Power, Data, Collision, Link status per port

Mechanical construction - Dimensions W x H x D

434 x 44 x 279 mm (170.9 x 17.3 x 109.8 in)

- Weight

3.6 kg (8 lb)

- Operating temperature

0 °C to +40 °C (32° F to 140° F)

- Operating humidity

10% to 95% (non condensing)

- Enclosure

IP 30

- Approvals

CE, cUL, FCC, FM

Scope of delivery

Rail Switch RS1-xx/xx or RM1 Terminal block for supply voltage Description and operating instruction

RM1