Spec sheet · Hirschmann
Hirschmann RT1-TP/FL Spec Sheet
Spec sheet2 pagesPDF 93 KB
Both pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
This is a two-page Hirschmann product information sheet for the RT1-TP/FL, an industrial Ethernet media converter between 10BASE-FL multimode fiber and 10BASE-T twisted pair. It lists ports, cable lengths, power, dimensions, ambient conditions, test levels, approvals and accessories.
- What it is
- Industrial Ethernet media converter, 10BASE-FL multimode fiber to 10BASE-T p. 1
- Ports
- 1 x 10BASE-FL with ST (BFOC) sockets for multimode cable; 1 x 10BASE-T with RJ45 socket p. 1
- Power
- 24 V DC (-25% to +30%), max. 105 mA; redundant 24 V supply possible p. 1
- Dimensions
- 40 mm x 134 mm x 80 mm (W x H x D) p. 1
- Weight
- 520 g p. 1
- Operating temperature
- 0 °C to +60 °C p. 1
- Mounting
- DIN Rail 35 mm p. 1
- Cable lengths
- Twisted pair 0 - 100 m; multimode 50/125 µm 0 - 2600 m; multimode 62.5/125 µm 0 - 3400 m p. 1
- Order number
- 943 633-002 p. 1
- Diagnostics
- LEDs (power, data, link status) and a signal contact (24 V DC / 1 A) p. 1
- Power connector
- 1 plug-in terminal block, 5-pin, for power supply and signaling contact p. 1
- Storage temperature
- -25 °C to +75 °C p. 1
- Protection class
- IP 30 p. 1
- Accessories
- Rail power supply RPS 30, RPS 60 or RPS 120; 19" installation frame p. 2
What this sheet walks you through
Good to know
- The manual states approvals including cUL 508, cUL 1604 Class 1 Div 2, cUL 60950, FM 3611 Class 1 Div 2 and Germanischer Lloyd. p. 2
- The published data may change without notice. p. 2
Questions this sheet answers
How far can the Hirschmann RT1-TP/FL reach over fiber?
Up to 2600 m on 50/125 µm multimode fiber and up to 3400 m on 62.5/125 µm multimode fiber. p. 1
What power supply does the RT1-TP/FL need?
24 V DC (-25% to +30%), drawing at most 105 mA at 24 V DC. p. 1
What fiber connector does the RT1-TP/FL use?
ST (BFOC) sockets for multimode cable. p. 1
What comes with the RT1-TP/FL?
The device, a terminal block and an operating manual. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
Product information RT1-TP/FL
Industrial Ethernet:Archive - Industrial Ethernet:Entry Level Hubs And Switches:Rail Transceiver:RT1-TP/FL http://www.e-catalog.beldensolutions.com/link/57078-24455-49814-49855-24477-34247/en/conf/uistate
Name
RT1-TP/FL
Industrial ETHERNET media converter, 10BASE-FL multimode and 10BASE-T Delivery informations Availability
no longer available
Product description Description
Industrial ETHERNET media converter, 10BASE-FL multimode and 10BASE-T
Port type and quantity
1 x 10BASE-FL, MM cables, ST (BFOC) sockets, 1 x 10BASE-T, TP cable, RJ45 socket
TypeRT1-TP/FLOrder No.943 633-002
More Interfaces Power supply/signaling contact
1 plug-in terminal block, 5-pin
Network size - length of cable Twisted pair (TP)
0 - 100 m
Multimode fiber (MM) 50/125 µm
0 - 2600 m, 11 dB link budget at 850 nm, A = 3 dB/km, 3 dB reserve, B = 400 MHz x km
Multimode fiber (MM) 62.5/125 µm
0 - 3400 m, 14 dB link budget at 850 nm, A = 3.2 dB/km, 3 dB reserve, B = 200 MHz x km
Network size - cascadibility Propagation equivalent
100 mPath variability value1 BT
Power requirements Operating voltage
24 V DC (-25% to +30%)
Current consumption at 24 V DC
Max. 105 mA
Service Diagnostics
LEDs (power, data, link status), signal contact (24 V DC / 1 A)
Redundancy Redundancy functions
redundant 24 V power supply
Mechanical construction Dimensions (W x H x D)
40 mm x 134 mm x 80 mmMountingDIN Rail 35 mmWeight520 gProtection classIP 30
Ambient conditions Operating temperature
0 °C to +60 °C
Storage/transport temperature
-25 °C to +75 °C
Relative humidity (non-condensing)
10% to 95%
MTBF
136.5 years; MIL-HDBK 217F: Gb 25 °C
Mechanical stability IEC 60068-2-27 shock
15 g, 11 ms duration, 18 shocks
IEC 60068-2-6 vibration
1 mm, 2 Hz - 13.2 Hz, 90 min.; 0.7g, 13.2 Hz - 100 Hz resonance, 90 min.; 3.5 mm, 3 Hz - 9 Hz, 10 cycles, 1 octave/min.; 1g, 9 Hz - 150 Hz, 10 cycles, 1 octave/min.
EMC interference immunity EN 61000-4-2 electrostatic discharge (ESD)
6 kV contact discharge, 8 kV air discharge
EN 61000-4-3 electromagnetic field
10 V/m (80 - 1000 MHz)
EN 61000-4-4 fast transients (burst)
2 kV power line, 1 kV data line
EN 61000-4-5 surge voltage
power line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line
EN 61000-4-6 conducted immunity
3 V (10 kHz - 150 kHz), 10 V (150 kHz - 80 MHz)
Hirschmann Automation and Control GmbH
www.beldensolutions.com
13-08-2012 Page 1 of 2
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
Industrial Ethernet:Archive - Industrial Ethernet:Entry Level Hubs And Switches:Rail Transceiver:RT1-TP/FL http://www.e-catalog.beldensolutions.com/link/57078-24455-49814-49855-24477-34247/en/conf/uistate
EMC emitted immunity FCC CFR47 Part 15
FCC CFR47 Part 15 Class A
EN 55022
EN 55022 Class A
Approvals Safety of industrial control equipment
cUL 508 (E175531)
Hazardous locations
cUL 1604 Class 1 Div 2 (E203960)
Safety of information technology equipment
cUL 60950 (E168643)
FM 3611 Class 1 Div 2
FM 3611 Class 1 Div 2 (3012532)
Germanischer Lloyd
Germanischer Lloyd (15 662 - 00 HH)
Scope of delivery and accessories Scope of delivery
device, terminal block, operating manual
Accessories to order separately
rail power supply RPS 30, RPS 60 or RPS 120, 19" installation frame
For more information please contact: Hirschmann Automation and Control GmbH Stuttgarter Strasse 45-51 72654 Neckartenzlingen Germany Phone: +49 7127/14-1809 E-Mail: inet-sales@belden.com
The information published in the websites has been compiled as carefully as possible. It is subject to alteration without notice in technical as well as in price-related/commercial respect. The complete information and data were available on user documentation. Mandatory information can only be obtained by a concrete query.
Hirschmann Automation and Control GmbH
www.beldensolutions.com
13-08-2012 Page 2 of 2