Page 1

Programmable Logic Controllers

Micro3 Series

Micro3C

The True Micro PLC Ambassador Key features of the Micro3C include: • All the features of the Micro3 • Talks both ASCII and binary • Equipped with two serial ports, RS232 and RS485 • Capable of connecting to dial-up modem, serial printer, and bar code reader • Up to 500 data registers • Handles a wide range of analog input signals • Comes with an easy reset button • Available in 2 sizes: 16- and 24-I/O with relay output UL Listed File No. E102542 CSA Certified File No. LR66809 CE Certified EMC Approved File No. B950913332312

Micro3

J Programmable Logic Controllers

The Benchmark for Micro-PLCs Key features of the Micro3 include: • Built-in communications and networking • Input/output analog capability • User program password protection • Catch input, pulse output • Real-time clock and calendar available • Built-in power supply for sensors • Arithmetic, comparison, and Boolean computation • High-speed: 400µ/100 steps, 10kHz

UL Listed File No. E102542 CSA Certified File No. LR66809 CE Certified EMC Approved File No. B950913332312

J-38 www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Page 2

Programmable Logic Controllers

General Specifications

Standard Mode

Micro3 Series High-Speed Mode

Program Capacity

1012 steps

100 steps (approximately)

Processing

2.9ms/1k steps (average)

400µs/100 steps (average)

Internal Relay

232 points

40 points

Data Register

Micro3: 100 points Micro3C: 500 points

32 points

Control Data Register

10 points, Counter/Timer

32 points total

16 points total

Shift Register

64 points

32 points, Communication Channel

Data link channel: RS485 Baud rate: 19,200 bps (fixed) Cable length: 656' (200m) (maximum) Data link: 6 slave stations (maximum) Expansion: 1 unit (maximum)

Programming channel: complies with EIA RS485 (Micro3)/RS232 (Micro3C) standards Baud rate: 1,200/2,400/4,800/9,600/19,200 bps (selectable); Extension: 16.4' (5m) (maximum) Micro3: 22 basic, 33 advanced Micro3C: 22 basic, 35 advanced

Memory

EEPROM

I/O

See configurations shown on page J-42

Catch Input Relays

8 points

Special Internal Relay

16 points

Power Failure Protection

Internal relay, shift register, counter, data register; backup time, lithium battery fully charged - With clock: 30 days at 25°C (approximately); Without clock: 50 days at 25°C (approximately)

Self-Diagnostic Function

CPU error (WDT), user program CRC error, user program sum check error, communication error, sensor power overload, transistor output overload

Catch Input

8 points; Minimum detectable pulse width (when hard filter is set to 10); Input I0 ON pulse = 28µs, OFF pulse = 30µs; Inputs I1 to I7 ON pulse = 37µs, OFF pulse = 120µs (depending on input filter settings)

Input Filter Function (DC input type only)

Normal input: 0ms, 3ms, 7ms, 10ms; Catch input: Input I0 ON pulse = 4 to 616µs, OFF pulse = 6 to 618µs; Input I1 to I7 ON pulse = 20 to 625µs, OFF pulse = 120 to 618µs

High-Speed Counter

1 point, single-phase, 10kHz (maximum), 32 bits

Analog Potentiometer

Micro3: 1 point (10-point), 2 points (16-, 24-point) Micro3C: 1 point only

Pulse Output

1 channel, frequency/PWM output (not available in Micro3C)

Real Time Clock

Clock accuracy ±30s/month (maximum) at 25°C (typical); year, month, day, hour, minute, second

Sensor Power Supply

24V ±3.6V DC, 150mA (maximum) including input current, overload detected

J Programmable Logic Controllers

Instructions

Micro3C only available in 16 I/O or 24

.

Electrical Specifications

AC Power

DC Power

Rated Power Range

100 to 240V AC, 50/60Hz (85 to 264V)

24V DC (19 to 30V DC)

Power Consumption

Approximately 30VA (240V AC)

Approximately 14W (24V DC)

Inrush Current

40A (maximum)

Power Disruption

25ms (momentary disruption) allowed

Dielectric Strength

Between power terminal and ground: 2,000V AC, 1 minute

Between power terminal and ground: 1,500V AC, 1 minute

Between I/O terminal and ground: 1,500V AC, 1 minute

Temperature

Operating: 0 to 60°C, Storage: –20 to +70°C

Operating Humidity

45 to 85% RH (avoid condensation)

Vibration Resistance

5 to 55Hz, 6G, 2 hours in each of 3 axes

Shock Resistance

30G, 3 shocks in each of 3 axes

Noise Resistance

Between power terminal and ground: 1.3kV, 1µs; Between I/O terminal and ground: 1kV, 1µs (with noise simulator), complies with IEC1131-2

Insulation Resistance

Between power or I/O terminal and ground: 10MΩ (minimum), 500V DC

Ground Resistance

100Ω (maximum)

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-39

Page 3

Programmable Logic Controllers

Micro3 Series Part Numbers: Micro3 Item

Remarks

Part Number

16 I/O: 9 inputs and 7 outputs

Inputs: 120V AC (85-132V AC) 50/60Hz (housing = 24 I/O size)

FC2A-CA16A1

10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs

FC2A-C10A1 FC2A-C16A1 FC2A-C24A1

Output: Transistor Sink 24V DC, 0.5A

10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs

FC2A-C10B1 FC2A-C16B1 FC2A-C24B1

Output: Relay 240V AC, 2A 30V DC, 2A

10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs

Output: Transistor Sink 24V DC, 0.5A

10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs

FC2A-C10B4 FC2A-C16B4 FC2A-C24B4

Output: Transistor Source 24V DC, 0.5A

10 I/O: 6 inputs and 4 outputs 16 I/O: 9 inputs and 7 outputs 24 I/O: 14 inputs and 10 outputs

FC2A-C10D4 FC2A-C16D4 FC2A-C24D4

Programming Starter Kits

Micro3 10 I/O, WindLDR, computer link cable, input switch simulator Micro3 16 I/O, WindLDR, computer link cable, input switch simulator Micro3 24 I/O, WindLDR, computer link cable, input switch simulator Micro3C 16 I/O, WindLDR, computer link cable, input switch simulator Micro3C 24 I/O, WindLDR, computer link cable, input switch simulator WindLDR, 3 computer link cables for Micro-1, Micro3 and Micro3C

MM-MICRO3-10 MM-MICRO3-16 MM-MICRO3-24 MM-MICRO3C-16 MM-MICRO3C-24 MM-Cables

Program Loader

Program loader with cable

FC2A-HL1EC

Loader Cable

6.56' (2m) long 16.4' (5m) long

Loader Adaptor

5V power supply adaptor for using program loader when not connected to CPU

PSR-GA05005

Programming Cable

Connects Micro3 or loader to PC (1:1 link), 6.56' (2m)

FC2A-KC2

Memory Card

Used with program loader to store user programs in SRAM memory

FC2A-MC1

Expansion Cable

Close proximity Micro3 link expansion, 9.84" (250mm) long

FC2A-KE1

J

1:N Computer Link Interface Unit

One required to connect each Micro3 in a 1:N computer link system (all connected to one central RS232C/RS485 converter)

FC2A-LC1

Programmable Logic Controllers

100 to 240V AC 50/60Hz Power Micro3 CPU

Output: Relay 240V AC, 2A 30V DC, 2A

Description

1:N Computer Link Interface Cable

One required to connect each Micro3 in a 1:N computer link system (connected to each interface unit), 32.8' (10m) long

FC2A-KC3

1:N RS232C/RS485 Converter

One required to connect all Micro3 units in a 1:N computer link system

HD9Z-T11

24V DC Power Micro3 CPU

Inputs: 24V DC sink/source Only the 16- and 24-I/O units have real-time clock/calendar

Connects program loader to Micro3

FC2A-C10A4 FC2A-C16A4 FC2A-C24A4

FC2A-KL1 FC2A-KL2

One required to connect all Micro3 units in a 1:N computer link system;

1:N RS232C/RS485 Converter

Additionally, the DS783 should be used in applications requiring PC to Micro3 communications via modem

1:N PC Cable

Connects RS232C/RS485 converter to PC in a 1:N computer link system, 4.92' (1.5m) long (D-sub 9-pin female computer connector)

HD9Z-C52

Analog Input Unit

0 to 5V 0 to 10V ±5V 4 to 20mA ±10V

Converts analog signals to digital and sends to input I0 of Micro3 (not for use with AC input type units)

FC2A-AD1 FC2A-AD2 FC2A-AD3 FC2A-AD4 FC2A-AD5

Analog Output Unit

0 to 5V 0 to 10V ±5V 4 to 20mA ±10V

Converts digital (PWM) signal from output Q0 of Micro3 to analog (not for use with relay output type units)

FC2A-DA1 FC2A-DA2 FC2A-DA3 FC2A-DA4 FC2A-DA5

Analog Timer Unit

For fine adjustment of analog timer preset value

PFA-1U11

Input simulator switches (6) for 10 I/O Micro3

HD9Z-T11-DS783

Input Switches

Input simulator switches (9) for 16 I/O Micro3 Input simulator switches (14) for 24 I/O Micro3

FC2A-SW6 FC2A-SW9 FC2A-SW14

WindLDR™

Windows-based application software, performs ladder programming and monitors all IDEC PLCs including the Micro series, FA series, and Open NET controllers.

WINDLDR

Micro3 User’s Manual

EM317

Micro3C User’s Manual (order both EM317 and EM318-0)

EM318-0

Manuals

J-40 www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Page 4

Programmable Logic Controllers Part Numbers: Micro3C Item AC Power (100 to 240V AC, 50/60Hz power supply) DC Power (24V DC, 19 to 30V DC) Program Loader

Optional Item Loader Cable (2m) Loader Cable (2m) Modem Cable (3m) PC Interface Cable (3m) PC Interface Cable (2m) User Communication Cable (2.4m) PC Connect Cable (5m) Memory Card (RAM) AC Adaptor Expansion Cable (25cm) 1:N Link Adaptor RS232C Cable (4 lines, 1.5m) WindLDR™

Description Base units: Input (24V DC sink/source) Relay output (240V AC/30V DC, 2A)

Micro3 Series Part Number

24 I/O (14 in, 10 out) 16 I/O (9 in, 7 out) 24 I/O (14 in, 10 out) 16 I/O (9 in, 7 out)

Version 2.0+; also compatible with Micro3

Description Connects basic unit (loader port) and program loader Connects basic unit (data link terminal) and program loader Connects basic unit (loader port) and modem (1:1 communications) Connects basic unit (loader port) and PC (1:1 communications) Connects basic unit (data link terminal) and PC (1:1 communications) Connects basic unit (loader port) and user’s equipment Connects basic unit (loader port) and Micro O/I™ Memory to store user’s programs (64K) Connects basic unit (data link terminal) and program loader/PC Connects basic unit and expansion function unit Connects basic unit (data link terminal) and PC Connects link adaptor and PC (1:N communications), D-sub 9-pin Windows-based application software, performs ladder programming and monitors all IDEC PLCs including Micro series, FA series, MicroSmart and ONC

FC2A-C24A1C FC2A-C16A1C FC2A-C24A4C FC2A-C16A4C FC2A-HL1EC

Part Number FC2A-KL3C FC2A-KL4C FC2A-KM1C FC2A-KC4C FC2A-KC6C FC2A-KP1C HG9Z-XC183 FC2A-MC1 PSR-GA05005 FC2A-KE1 FC2A- MD1 HD9Z-C52 WINDLDR

J Programmable Logic Controllers www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J-41

Page 5

Programmable Logic Controllers

Micro3 Series Micro3C I/O Expansion

16

9 Inputs 7 Outputs

Micro3 and Micro3C Data Link

1. These Micro3C expansions listed are examples. You may create your own combinations as well.

A data link network is simple to3 set up. No3 special cables or junctions are required. Just wire up to 6 Micro s or Micro Cs in a bus configuration, over a total distance of 656’ (200m). Using a built-in data link, the master initiates communication automatically - no special programming is required. Values from 2 read registers and 2 write registers are exchanged between the master and each slave.

24

14 Inputs 10 Outputs

Data link channel 19200, RS485 is fixed. 3. The expansion link and data link cannot be used concurrently. 18 Inputs 14 Outputs

32

23 Inputs 17 Outputs

40

Programmable Logic Controllers

16

6 Inputs 4 Outputs

Slave #1

Slave #2

Slave #3

Slave #6

Slave #5

Slave #4

14 Inputs 10 Outputs

15 Inputs 11 Outputs

18 Inputs 14 Outputs

34

20 Inputs 14 Outputs

23 Inputs 17 Outputs

28 Inputs 20 Outputs

48

J-42

Slave #4

Using a built-in data link, the master initiates communication automatically when executing a network communication program. Values from 2 read registers and 2 write registers are exchanged between the master and each slave.

12 Inputs 8 Outputs

32

40

Slave #5

A high-performance FA3S CPU an PF3S-SIF4 interface module can manage data transfer with up to 6 Micro3s. Two interface modules can be used with each FA3S CP12 or CP13, making it possible to network up to 12 Micro3s total.

Master: FA3S

26

Slave #6

Micro3 and Micro3C Link with FA3S Master

2. These Micro3 expansions listed are examples. You may create your own combinations as well.

9 Inputs 7 Outputs

20

24

Slave #3

Master

Micro3 I/O Expansion

J

Slave #2

28 Inputs 20 Outputs

48

10

Slave #1 www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Page 6

Programmable Logic Controllers

Micro3 Series

Computer Link 1:1 Communication

The Micro3 and Micro3C can be programmed from a PC using WindLDR ladder programming software. A computer link cable is required to connect the PC’s RS232 serial port with the Micro’s programming port.

Micro3

Programming Port RS485

Computer Link Cable FC2A-KC4C 9.84’ (3m) long

Computer Link Cable FC2A-KC2 7.87’ (2m) long To RS232C Port

To Loader Port (RS232C)

To RS232C Port

Built-in RS232/RS485 Converter

Micro3C

D-sub 9-pin Female Connector

Computer Link 1:N Communication (Micro3 only)

A network of Micro3s can be set up for programming and monitoring with WindLDR. The network can also be used3 for supervisory control and data acquisition (SCADA). Up3 to 32 Micro s can be networks with a PC as the master. Each Micro should be programmed with a specific device number in FUN9. FUN9 can be set with a program loader or with a PC in 1:1 mode running WindLDR.

J Programmable Logic Controllers

N ≤ 32

RS232C/RS485 Converter HD9Z-T11

Link Interface FC2A-LC1

RS232 Cable HD9Z-C52

Link Cable FC2A-KC3

AC Adaptor or 24V DC P/S

Slave #1 www.idec.com

Slave #2

Slave #3

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Slave #N

J-43

Page 7

Programmable Logic Controllers

Micro3 Series

Instruction Set Instruction

Description

1 1 1 1 1 1 2 2 2 1 1 1 1 1 1 1, 1 1 1 1 1 1 1 2 2 1 1 2 2 2

AND AND LOD ANDN BPP BPS BRD CNT CC= CC≥ END JEND JMP LOD LODN MCS MCR NOT OR OR LOD ORN OUT OUTN RST SET SFR SFRN SOTD SOTU TIM TM TMS

And And load And not Bit pop Bit push Bit read Counter Counter compare = Counter compare ≥ End Jump end Jump Load Load not Master control set Master control reset Not Or Or load Or not Output Output not Reset Set Shift register Shift register not Single output falling Single output rising 100ms timer 10ms timer 1ms timer

Steps

Instruction

Description

NOP

No operation

11 12 13 14

MOV MOVN IMOV IMOVN

Word move Word move not Word indirect move Word indirect move not

4–5 4–5 4–5 4–5 4–5 4–5

21 22 23 24 25 26

CMP= CMP<> CMP< CMP> CMP<= CMP>=

Equal compare Not equal compare Less than compare Greater than compare Less than or equal compare Greater than or equal compare

4–5 4–5 4–5 4–5

31 32 33 34

ADD SUB MUL DIV

Addition Subtraction Multiplication Division

4–5 4–5 4–5

41 42 43

ANDW ORW XORW

And word Or word Exclusive or word

3 3 3 3

51 52 53 54

SFTL SFTR ROTL ROTR

Shift left Shift right Rotate left Rotate right

2 2 2 2 1

71 72 73 74 75

CALR CALW CLKR CLKW ADJ

Calendar read* Calendar write* Clock read* Clock write* Adjust*

4 4 2

81 82 83

DISP DGRD ANR0

Display Digital switch read Analog potentiometer 0 read

2

84

ANR1

Analog potentiometer 1 read*

J

3 3 2

91 92 93

PULS PWM A/D

Pulse output Pulse width modulation Convert analog to digital

4 2 4 2

A1 A2 A3 A4

HSC0 HSC1 HSC2 HSC3

H/S counter 0 (32 bits) H/S counter 1 (32 bits) H/S counter 2 (32 bits) H/S counter 3 (16 bits)

5 – 404

B1

TXD

Transmit (Micro3C only)

5 – 404

B2

RXD

Receive (Micro3C only)

4–5

B3

COMP2

Double word compare (Micro3C only)

Advanced Instructions

0

3–4 3–4 5–6 5–6

Basic Instructions

1

Programmable Logic Controllers

Steps

Instructions designated by * are not affected by the change to the year 2000.

J-44 www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

Page 8

Programmable Logic Controllers

Micro3 Series

Dimensions

Micro3 and Micro3C Base Units

Mounting Hole Layout

C 3.031" (77mm)

M4 tapped or Ø 0.177" (Ø 4.5mm)

3.346" (85mm)

W 2.362" (60mm)

Key to Dimensions W

AC Input Units

C

10 I/O

4.134" (105mm)

3.386" (86mm)

16 I/O

5.315" (135mm)

4.567" (116mm)

24 I/O*

6.496" (165mm)

5.748" (146mm)*

*Dimensions are the same for the 16 I/O AC input unit.

A/D and D/A Analog Converters

Ø 0.17" (4.3mm) 2 holes

3.740" (95mm)

1.77" (45mm)

1.181" (30mm)

2.76" (70mm)

2.76" (70mm)

3.15" (80mm) 7.283" (185mm)

3.150" (80mm)

www.idec.com

Programmable Logic Controllers

1.38" (35mm)

J

Program Loader

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

0.984" (25mm)

J-45