JUMO data sheet 709010 for the TYA 432 thyristor power switch, in the two stock types 709010/1-25-240 and 709010/1-50-480. It gives the load and control ratings, general specifications, heat sink sizing, connections, dimensions and order details. The sheet does not name a TYA 432-100.

Device
Thyristor power switch for contactless switching of AC loads, including ohmic-inductive loads at high switching frequency p. 1
25 A type
709010/1-25-240: 24 to 265 Veff, 25 Aeff, part no. 00673976 p. 4
50 A type
709010/1-50-480: 42 to 530 Veff, 50 Aeff, part no. 00673981 p. 4
Control signal
DC 4 to 32 V, compatible with JUMO controller logic outputs p. 1
Switch-on/off
On above DC 2.75 V (709010/1-25-240) or DC 3.75 V (709010/1-50-480); off below DC 2 V p. 1
Input current
≤ 10 mA at DC 32 V p. 1
Switching mode
Zero voltage switch: on at zero voltage, off at zero current p. 1
Isolation
Control and power sections isolated by optocouplers, insulation voltage ≥ 4 kV p. 2
Frequency, minimum load
45 to 65 Hz; minimum load current 150 mAeff p. 1
Terminals
Screw terminals: load 16 mm2 max., control 2.5 mm2 max. p. 2
Temperature
Ambient -20 to +70 °C; storage -40 to +100 °C; 95 % relative humidity, non-condensing p. 2
Thermal resistance
0.8 K/W (709010/1-25-240); 0.5 K/W (709010/1-50-480) p. 2
Protection, weight
IP20; 60 g p. 2
Approval
The data sheet states UL approval (E223137) p. 1

What this sheet walks you through

  • Sizing the heat sink with the reduction tables p. 2
  • Connecting the control and load terminals p. 3
  • Reading the order code and choosing a stock version p. 4

Good to know

  • Load current and load voltage cannot be combined freely; only the two stock versions exist. p. 4
  • Use silicone-based heat-conducting paste between the heat sink and the switch, or check that a silicone-free paste does not harm the plastic housing. p. 2
  • For maximum output, the thermal requirements in the reduction tables must be followed. p. 2
  • The sheet recommends a matching semiconductor fuse for fault-free operation. p. 4

Questions this sheet answers

What control voltage does the JUMO TYA 432 need?

A DC control signal of 4 to 32 V, compatible with JUMO controller logic outputs. p. 1

What is the part number of the 50 A 480 V JUMO thyristor switch?

Type 709010/1-50-480, part no. 00673981, rated 42 to 530 Veff and 50 Aeff. p. 4

What is the maximum load current of the TYA 432?

25 Aeff for type 709010/1-25-240 and 50 Aeff for type 709010/1-50-480. p. 4

How do I size the heat sink for a TYA 432?

Use the reduction tables; in the sheet's example, 15 A resistive at 40 °C on the 709010/1-25-240 needs a heat sink of at most 3.8 K/W. p. 2

The file

Size and text

Pages4
PDF435 KB
TextText from the PDF itself.

Every page · 4

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Jumo TYA 432-100 Spec Sheet

The text of page 1, from the PDF itself

JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net

JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM 20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk

JUMO Process Control, Inc. 6733 Myers Road East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com

Data sheet 709010

Page 1/4

JUMO TYA 432 Thyristor Power Switch Brief description Thyristor power switches are required for contactless switching of alternating current consumers. A typical application is the switching of ohmic-inductive loads at a high switching frequency. This applies especially to the industrial sector in areas such as the plastic packaging industry, air conditioning and heat technology, and industrial furnace construction. The control and power sections are galvanically isolated by optocouplers. The control signal range is compatible with the logic outputs of JUMO controllers. The power section operates as a zero voltage switch. As a result, it is switched on at zero voltage and switched off at zero current, irrespective of the time when the control signal changes. This way, interference voltage is avoided. A varistor is internally integrated on the output side to protect against voltage peaks from the mains voltage. The input status is displayed by an LED.

Type 709010/1-50-480

  • Load currents 25 A and 50 A (max.)
  • Load voltages 240 V and 480 V
  • Control voltage DC 4 to 32 V

Technical data

  • UL approval (E223137)

Load circuit Type709010/1-25-240709010/1-50-480Load voltage24 to 265 Veff42 to 530 VeffLoad current (maximal)25 Aeff50 AeffLoad current (minimal)150 mAeff

Fuse maximum load integral ≤ 310 A2 · s I2 · t (t = 10ms) Frequency

45 to 65 HzPeak blocking voltage≥ 650 VsLeakage current≤ 3 mAcos ϕ> 0.5 at 230 Veff≤ 1800 A2 · s

≥ 1400 Vs > 0.5 at 480 Veff

Control Control signal range

DC 4 to 32 V

Switch-on voltage

Higher than DC 2.75 V for 709010/1-25-240 Higher than DC 3.75 V for 709010/1-50-480

Switch-off voltageLower than DC 2 VInput current≤ 10 mA at DC 32 VResponse delay≤ 0.5 · pulse periodV3.00/EN/0007373970901000T10Z001K000

Page 2 of Jumo TYA 432-100 Spec Sheet

The text of page 2, from the PDF itself

JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net

JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM 20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk

JUMO Process Control, Inc. 6733 Myers Road East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com

Data sheet 709010

Page 2/4

General specifications Operating mode

Zero point control

Galvanic isolation

Between the control and power section through optocouplers; insulation voltage ≥ 4 kV

Thermal resistance Barrier housing

0.8 K/W for 709010/1-25- 240 0.5 K/W for 709010/1-50- 480

Admissible ambient temperature

–20 to +70 °CStorage temperature-40 to +100 °C

Resistance to climatic conditions

95 % relative air humidity, non-condensing

Electrical connection

By means of screw terminals (load:  16 mm2 (max.)/control:  2.5 mm2 (max.))

Electromagnetic compatibility

DIN EN 61000 - 6 - 4 DIN EN 61000 - 6 - 2

Electrical safety

Overvoltage category III Pollution degree 3 (from outside) Pollution degree 2 (in housing)

HousingNoryl 6FN 1Protection typeIP20Weight60 g

Reduction tables The maximal thermal resistance between the thyristor power switch's base plate and the surrounding environment R(thSA) is determined depending on the load currents and the various ambient temperatures. The matrix below should be used for this purpose. You can also use this matrix to check the power loss for a given nominal current. Example: Current I = 15 A resistive load TA = 40 °C (measured during operation when installed in a control cabinet) Selected thyristor power switch: 709010/1-25- 240 The matrix shows that the maximal thermal resistance of the heat sink is 3.8 K/W. Important information: Use a silicone-based heat-conducting paste between the heat sink and the thyristor power switch. If you use a silicone-free heat-conducting paste, please check to make sure that the chemical silicone replacement does not affect the Noryl SE 1 GFN 1 in the plastic housing. A recommended heat-conducting paste based on silicone is, for example, Dow Cornering. In order to ensure operational safety at maximal output, please pay close attention to the thermal requirements listed in the reduction tables. 709010/1-25-240

V3.00/EN/00073739709010/1-50-48070901000T10Z001K000

Page 3 of Jumo TYA 432-100 Spec Sheet

The text of page 3, from the PDF itself

JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net

JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM 20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk

JUMO Process Control, Inc. 6733 Myers Road East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com

Data sheet 709010Page 3/4Connection 3/A1+2/T1ControlLoad circuit4/A2-1/L1DimensionsV3.00/EN/0007373970901000T10Z001K000

Page 4 of Jumo TYA 432-100 Spec Sheet

The text of page 4, from the PDF itself

JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM 20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk

JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net

JUMO Process Control, Inc. 6733 Myers Road East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com

Data sheet 709010Page 4/4Order details (1)Basic type(2)Circuit type(3)Load current709010TYA 4321einphasig2525 A5050 A (4)Load voltage240AC 240 V480AC 480 V

Note: Load current and load voltage cannot be combined arbitrarily. Only the stock versions are available. (1) Order code

/ (2) - (3) /-(4)-Stock versions TypeLoad voltageLoad currentPart no.709010/1-25-24024 to 265 Veff25 Aeff00673976709010/1-50-48042 to 530 Veff50 Aeff00673981

In order to ensure fault-free operation and improved availability in applications with thyristor power switches, we recommend using a corresponding semiconductor fuse (e.g. by the company Ferraz).

V3.00/EN/00073739

70901000T10Z001K000