User's Manual Visual KV Series 3 Programming, pages 51 to 60

Pages 51 to 60 of 79

The original document is the PDF (355 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Keyence KV-16R

Page 51

1.5 Extended Ladder Diagrams

1.4.6 Contact Comment Save Function •

This function transfers contact comments to the Visual KV Series using the "KV IncrediWare (DOS)" or "LADDER BUILDER for KV" programming support software.

•

The Visual KV Series can store not only programs but also comments registered to each contact using the "KV IncrediWare (DOS)" or "LADDER BUILDER for KV" programming support software. A program may not be easy to understand if only device Nos. are used. By registering comments to the contacts, the program can be easily debugged and more efficiently maintained.

•

The number of contact comments that can be transferred is up to 1,000 for both normal transfer and compression transfer.

•

The KV-D20 operator interface panel includes the contact comment display function.

➮

For more about operating procedures, refer to "2.5 Entering Comments/Labels" (p.1-46) and "4.2.2 Setting the comment transfer" (p.2-138).

Note 1: Line comments cannot be stored. Note 2: The KV-P3E(01) handheld programmer cannot read or write contact comments. Note 3: The KV-D20 operator interface panel cannot display contact comments which have been compressed and transferred.

Chapter 1 Programming

3-27

11

Page 52

1.4 Special Functions

1.4.7 Special Functions

KV-300 PLC only

Constant Scan Time Mode In this mode, operation can take place according to a preset scan time (in ms). ■ Setting Write the desired scan time into TM29 (temporary data memory), then turn on special utility relay No. 2303. The scan time can also be written into TM31. Specify a scan time in increments of 10 ms (a value of less than 10 ms is invalid). Here, write a value into TM equivalent to 10 times the scan time.

Example Set the constant scan time to 20 ms. 02008

1

#00200 LDA

TM29 STA

2303 SET

Note 1: The set value for the constant scan time must be greater than the actual scan time. Otherwise, special utility relay 2304 turns on during every scan to disable constant scan time mode. Note 2: If the scan time exceeds the set value, special utility relay no. 2304 turns on during the next scan.

Output Disabled Function During checking of a program, this function clears output from output relays regardless of the program currently running. ■ Setting Turn on special utility relay No. 2300. After one scan is completed, all output relays (00500 to 00503, 07500 to 17915) are cleared.

Example Use the output disabled function by executing FORCED RESET/RESET to special utility relay No. 2300 from the monitor display. ➮

To execute FORCED RESET or RESET, refer to "Chapter 6 Handheld Programmer" (p.1-195).

Input Refresh Disabled Function Set this function if it is desired to turn ON/OFF input relays from the monitor display without activating the machine when checking a program. ■ Setting Turn ON special utility relay No. 2301 to skip input refresh (reading from input relays). Input relays can then be turned ON/OFF with the KV-P3E(01) or with KV IncrediWare (DOS) on the monitor display.

Example Set input relay No. 0000 to ON to disable input refresh; set to OFF to enable input refresh. 0000

2301

Note: If input refresh is disabled, it is not enabled until input relay No. 0000 is turned on from the handheld programmer.

3-28 Chapter 1 Programming

Page 53

1.5 Extended Ladder Diagrams

1.5 Extended Ladder Diagrams This section describes KEYENCE’s unique extended ladder diagram.

1.5.1 Features of Extended Ladder Diagrams The extended ladder diagram is a programming method developed to reduce problems related to design, testing, operation, and maintenance of programs. In a conventional ladder diagram, output instructions can be written only on the right side of a ladder diagram. On the other hand, in an extended ladder diagram, output instructions can be written anywhere except on the left. As the result, the programs shown below can be written. Mixture of input and output circuits Conventional ladder diagram

Only input circuits can be written.

Only output circuits can be written.

Extended ladder diagram

Only input circuits can be assembled.

Both input circuits and output circuits can be assembled.

Only output circuits can be assembled.

Connection of two or more instructions on one line Conventional ladder diagram Extended ladder diagram

Instructions can be written only from the left end to the right end on one line.

Many instructions can be connected.

Branch from output coil Conventional ladder diagram

Branches can be made only from input contacts.

Extended ladder diagram

Branches can also be made from output coils.

There is only a single line, so the ladder diagram is easier to understand. Three lines are required.

Chapter 1 Programming

3-29

11

Page 54

1.5 Extended Ladder Diagrams

1.5.2 Advantages of Extended Ladder Diagrams The number of lines in a ladder diagram can be reduced. Because both output instructions and input instructions can be written side by side, the number of program lines can be reduced. As the result, the contents of the program can be seen at a glance.

Example When DM0000 stores 1000, 0500 turns ON. 2000, 0501 turns ON. 3000, 0502 turns ON. Conventional ladder diagram

1

Extended ladder diagram DM0000 #01000 LDA CMP

2010

0500

#01000 CMP

#02000 CMP

2010

0501

2010

0500

#03000 CMP

2010

0502

2002

#02000 CMP

2010

0501

2002

#03000 CMP

2010

0502

DM0000 LDA

2002

2002

In a conventional ladder diagram, operations performed by the program cannot be easily understood. In an extended ladder diagram, operations performed by the program can be understood at a glance.

Processing sequence is clear. Ladder symbols can be laid out in processing sequence, so the program flow is easier to understand. In addition, maintainability is considerably improved.

Example When the start switch is set to ON, a lamp is lit for three seconds, a buzzer is sounded for two seconds, and then the motor starts to rotate. 0000

1100 DIFU

1100

1000 STG

0500

#00030 T000

T000

1001 JMP

1001 STG

0501

#00020 T001

T001

1002 JMP

1002 STG

0502

0000

1000 SET

ENDS

Conventional ladder diagram 0000 1000

T000

1001

T001

T001

T002

1001

#00020 T001

#00030 T002

1001

0500

1003

3-30 Chapter 1 Programming

Extended ladder diagram

1001 STG

1003

1003

When the start switch (0000) is set to OFF, the motor is stopped and all operations are reset.

#00010 T000

1003

1002

When timer 1 turns ON two seconds later, the buzzer is stopped and the motor (0502) starts to rotate.

0000

1002

1002

When timer 0 turns ON three seconds later, the lamp goes out, a buzzer (0501) is sounded, and timer 1 is activated.

1000 DIFU

T002 T000

When the start switch (0000) is set to ON, a lamp (0500) is lit and timer 0 is activated.

0501

1000 DIFU

1000

1001 SET

0500

#00010 T000

T000

1002 JMP

1002 STG

0501

#00020 T001

T001

1003 JMP

1003 STG

0500

#00030 T002

T002

1001 JMP

0501

By using an extended ladder diagram as shown above, the program can be executed in the sequence of the processing to be performed. So even a person who uses a relay sequence for the first time can understand the processing contents. By combining the STG instruction, double coils can also be used.

Page 55

1.5 Extended Ladder Diagrams Note: When an extended ladder diagram is used, the number of lines in ladder diagram may be reduced. However, this may not necessarily reduce the number of mnemonics in the program. Conventional ladder diagram 0000

Extended ladder diagram

0500

0000

0500

0501

0501

LD 0000 OUT 0500 OUT 0501

LD 0000 OUT 0500 CON OUT 0501 The CON instruction for connection is added. (The scan time is not affected.)

1.5.3 Example of an Extended Ladder Diagram ■ Using W-UE Only when inputs are given in the order "0000 ➞ 0001 ➞ 0002", output 0500 turns ON. Conventional ladder diagram 1002 DIFU

0001 0002 1002

1003 DIFU 0000

1000

1000

1001

1000 1003

At the rising edge of input 0001, 1002 turns ON. At the rising edge of input 1003, 1002 turns ON. If input 0000 is ON, 1000 turns ON.

Extended ladder diagram 0000

0001 1000

1000

0002

1001

0500

1001

Input 0000 Input 0001 Input 0002 Output 0500 turns ON. turns ON. turns ON. turns ON.

If 1000 is ON, 1001 turns ON.

1001 1001

0500

When 1001 turns ON, output 0500 turns ON.

Because the program can be written in only one line when an extended adder diagram is used, it is easier to look at and understand compared with a program written using a conventional ladder diagram.

Chapter 1 Programming

3-31

11

Page 56

1.5 Extended Ladder Diagrams

1

3-32 Chapter 1 Programming

Page 57

Chapter 2 Instructions Describes the concrete usage of instructions in the KV Series. Refer to "Chapter 3 Interrupts" on page 3-191 for details of interrupt instructions. Refer to "Chapter 4 High-speed counters" on page 3-203 for details of the highspeed counters used in the application instruction. 2.1

Instruction List [Visual KV Series] ....................................... 3-34

2.1.1 2.1.2 2.1.3 2.1.4 2.1.5

Basic Instructions ................................................................................. 3-34 Application Instructions ........................................................................ 3-36 Arithmetic Instructions .......................................................................... 3-38 Interrupt Instructions ............................................................................ 3-41 Function No. List (Alphabetical order) .................................................. 3-41

2.2

Instruction List [KV-300 Series, KV-10/80] .......................... 3-42

2.2.1 2.2.2 2.2.3 2.2.4

Basic Instructions ................................................................................. 3-42 Application Instructions ........................................................................ 3-45 Arithmetic Instructions .......................................................................... 3-48 Interrupt Instructions ............................................................................ 3-54

2.3

Convention Details ................................................................. 3-55

2.4

Instruction Details .................................................................. 3-56

2.4.1 2.4.2 2.4.3

Basic Instructions ................................................................................. 3-56 Application Instructions ........................................................................ 3-95 Arithmetic Instructions .......................................................................... 3-134

2.5

Programming Notes ............................................................... 3-189

Page 58

2.1 Instruction List

Visual KV Series

2.1 Instruction List

Visual KV Series

The KV Series uses 80 instructions. The instructions are divided into four categories according to their functions: basic instructions, application instructions, arithmetic instructions, and interrupt instructions. The following is an overview of applications and functions. For details, refer to the respective description pages for each instruction.

2.1.1 Basic Instructions Instruction LOAD

2

Symbol nnnn

LOAD BAR nnnn

AND nnnn

Function

Exec.time (µs)

Bytes

Page

LD

Connects N.O. contact to bus.

0.7 to 1.6

3 (12)

3-57

LDB

Connects N.C. contact to bus.

0.7 to 1.6

3 (12)

3-57

0.7 to 0.9

3 (8)

3-58

0.7 to 0.9

3 (8)

3-58

Mnemonic Operand Operand value

ANB

Connects N.O. contact in 0000 to 17915 series with previous contact. T000 to T249 C000 to C249 Connects N.C. contact in CTC0 to CTC3 series with previous contact.

nnnn

OR

Connects N.O. contact in parallel with previous contact.

0.7 to 0.9

3 (8)

3-60 nnnn

ORB

Connects N.C. contact in parallel with previous contact.

0.7 to 0.9

3 (8)

3-60

0.8

1 (4)

3-61

0.8

1 (4)

3-63

1.5

3 (12)

3-65

1.5

3 (12)

3-65

1.9 to 12.8

3 (14)

3-66

0500 to 1915 2009 2100 to 17915 Forces R/T/C OFF when input 1.9 to 20.5 T000 to T249 is ON. C000 to C249 CTH0 to CTH1 CTC0 to CTC3

3 (14)

3-66

16-bit on-delay T that counts down in 0.1-s decrements.

12.0 to 17.8

2 (6)

3-67

16-bit on-delay T that counts down in 0.01-s decrements.

12.0 to 17.8

2 (6)

3-68

AND BAR nnnn

OR

OR BAR

AND R No. T/C No.

AND LOAD

ANL

OR LOAD

ORL

OUT nnnn

Connects in series blocks made of one or more contacts. Connects in parallel blocks made of one or more contacts.

OUT R No.

OUT BAR

SET nnnn nnnn SET

OUB

0500 to 1915 2009 2300 to 17915 Forces relay ON and holds T000 to T249 this status when input is ON. C000 to C249

SET R No. T/C No.

nnnn RES

RES

0.1-s TIMER

#ddddd Txxx

TMR

0.01-s TIMER

#ddddd T Txxx H

TMH (FUN49)

RESET

Outputs input ON/OFF status 0500 to 1915 to R coil. 2009 2300 to 17915 Outputs inverted input ON/ OFF status to R coil.

T No., # preset value

3-34 Chapter 2 Instructions

000 to 249 #00000 to #65535

Page 59

2.1 Instruction List

Exec.time (µs)

Bytes

Page

16-bit on-delay T that T No., 000 to 249 # preset value #0000 to #65535 counts down in 1-ms decrements.

12.0 to 17.8

2 (7)

3-69

#00000 to # preset value, #65535 Sets 16-bit up-counter. C No., counter 000 to 249 input R 0000 to 17915

12.0 to 17.8

4 (7)

3-72

13.0 to 24.0

2 (10)

3-76

3 (10)

3-78

3 (10)

3-78

3 (11)

3-80

(*)

5 (15)

3-82

Reduces input relay time constant to 10 µs for higher input response.

3.8 to 9.4

3 (8)

3-86

Instruction

Symbol

Mnemonic

1-ms TIMER

#ddddd T S Txxx

TMS (FUN51)

COUNTER

#ddddd Cxxx nnnn

C

UP-DOWN COUNTER

UP DW #ddddd RES

DIFFERENTIATE UP nnnn DIFU

DIFU (FUN10)

DIFFERENTIATE DOWN nnnn DIFD

DIFD (FUN09)

KEEP

KEEP (FUN22)

R No.

SFT (FUN39)

nnnn: 1st R No. mmmm: Last R No.

KEEP

UDC xxx

UDC (FUN52)

SFT

SHIFT

Operand

C No., # preset value

R No.

SET nnnn RES

D nnnn CLK RES mmmm

Visual KV Series

Operand value

000 to 249 #00000 to #65535

Function

Sets a 16-bit up-down counter.

Turns ON R for 1 scan 11.2 to 13.2 time at rising edge of 1000 to 1915 input. 3000 to 9915 Turns ON R for 1 scan 10.0 to 12.8 time at falling edge of input. Turns ON R and holds this 0500 to 1915 status when SET input is ON. 8.2 to 19.8 2009 Turns OFF R when RESET 2100 to 17915 input is ON. 1000 to 1915 Sets shift register. 3000 to 9915 (KV-10) 0000 to 0005 (KV-16) 0000 to 0009 (KV-24) 0000 to 0015 (KV-40) 0000 to 0107

HIGH SPEED

HSP nnnn

HSP (FUN18)

MASTER CONTROL

MC

MC (FUN24)

Selects ON/OFF status of R coils, Ts, or Cs.

0.2

1 (4)

3-89

MCR

MCR (FUN25)

Represents end of MC.

0.2

1 (0)

3-89

MEMSW $xxxx

MEMSW (FUN26)

Sets memory switches.

––

3 (0)

3-92

NOP (FUN30)

Performs no operation.

––

1 (0)

3-94

END

Indicates end of each routine of program.

––

1 (1)

3-94

ENDH

Indicates end of entire program.

––

1 (0)

3-94

MASTER CONTROL RESET MEMORY SWITCH NOP

END

END HI

END

ENDH

• • • •

R No.

$ constant

$ 0000 to $ FFFF

Number of bytes represents the memory capacity required for each instruction. Number in ( ) represents the memory capacity required for object code of each instruction. *1 34 + 0.25 + n x 0.25 (n: No. of shift steps) All operand values are shown in normal notation. The corresponding relay numbers in X-Y-M notation are shown below: Normal notation 0000 to 0415 0500 to 0915 1000 to 6915 7000 to 17915

X-Y-M notation X000 to X04F Y050 to Y09F M1000 to M6915 X700 to X174F or Y750 to Y179F

Chapter 2 Instructions

3-35

12

Page 60

2.1 Instruction List

Visual KV Series

2.1.2 Application Instructions Instruction

Symbol

Mnemonic

WAIT ON nnnn ON mmmm

W-ON

WAIT OFF nnnn OFF mmmm

W-OFF

WAIT UP EDGE WAIT DOWN EDGE

W-UE nnnn

W-DE mmmm

CONNECT

CON (FUN 06)

PUSH

MPS

READ

MRD

POP

MPP

STAGE

2 nnnn mmmm nnnn STG nnnn JMP

JMP (FUN 21)

END STAGE

ENDS

ENDS (FUN 14)

STEP

STP nnnn

STP (FUN 45)

STE

STE (FUN 43)

• • •

Function

Exec.time (µs)

Bytes

Page

5 (12)

3-96

5 (12)

3-96

5 (12)

3-98

1 (0)

3-98

1 (4)

3-102

3.2

1 (4)

3-103

6.8

1 (4)

3-103

10.5 to 13.0

3 (10)

3-103

Executes instructions in STG block when R (operand) is ON. 4.5 to 12.5

3 (8)

3-106

1 (4)

3-106

2.5

3 (10)

3-106

5 (12)

1 (0)

3-114

Turns ON

3-114

R (output operand [mmmm]) when R, T, or C (input operand 10.4 to 12.6 17915 T000 to T249 [nnnn]) is ON. nnnn: R, T, C C000 to C249 Turns ON R (output operand CTC0 to CTC3 [mmmm]) when R, T, or C (input 13.6 to 18.5 Nos. operand [nnnn]) is OFF. mmmm: mmmm: 1000 to 1915 Turns ON R (output operand 3000 to 9915 [mmmm]) at rising edge of R, T, 13.6 to 18.5 R No. 1000 to 1915 or C (input operand [nnnn]). R No. Turns ON R (output operand [mmmm]) at falling edge of R, T, 6.8 to 5.3 or C (input operand [nnnn]). Represents series connection of output instruction together with another instruction. Stores input status and arithmetic flag. Reads input status and arithmetic flag stored with PUSH. Reads & clears input status and arithmetic flag stored with PUSH.

STG (FUN 44)

JUMP

STEP END

Operand Operand value

R, T, C Nos.

3000 to 9915 0000 to 0009 When input is ON, turns R of current stage OFF and moves 4.3 to 7.5 to stage specified by operand. Turns current stage OFF and next stage ON when input is ON.

R No. nnnn: 0000 to

0500 to 9915 Executes program between T000 to T249 STP & STE when R (operC000 to C249 and) is ON. CTC0 to CTC3 11.2 to 13.4 Is used with STEP to make program step.

Number of bytes represents the memory capacity required for each instruction. Number in ( ) represents the memory capacity required for object code of each instruction. All operand values are shown in normal notation. The corresponding relay numbers in X-Y-M notation are shown below: Normal notation 0000 to 0415 0500 to 0915 1000 to 6915 7000 to 17915

3-36 Chapter 2 Instructions

X-Y-M notation X000 to X04F Y050 to Y09F M1000 to M6915 X700 to X174F or Y750 to Y179F