Manual · AutomationDirect
AutomationDirect D3-05B-1, Koyo D3-05B-1, PLC Direct D3-05B-1 and Siemens D3-05B-1 Manual
Manual4 pagesPDF 557 KB
All 4 pages are below, each with its text.
Covers · 4 models
The models it covers
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Four catalog pages on DL305 bases: a specification table for the D3-05B-1, D3-05BDC, D3-08B-1, D3-10B-1 and D3-10BDC, a worked power budget example, the DL305 power requirements chart, and dimensions and installation. It helps check the D3-05B-1 power supply ratings and whether a set of modules fits its power budget.
- Type
- D3-05B-1: 5-slot DL305 I/O base with built-in power supply, local or expansion p. 1
- Input voltage
- D3-05B-1: 85-264VAC, 47-63Hz p. 1
- Power consumption
- D3-05B-1: 85 VA max. p. 1
- 9V and 24V supplied
- D3-05B-1: 9 VDC 2.0A; 24 VDC 0.5A p. 1
- Auxiliary 24 VDC
- D3-05B-1: 100mA max p. 1, 3
- Run relay
- 250VAC 4A (resistive load) p. 1
- Fuse
- D3-05B-1: 2A (250V), non-replaceable p. 1
- Inrush current
- D3-05B-1: 30A 1ms max. p. 1
- Weight
- D3-05B-1: 37oz. (1050g) p. 1
- Internal voltages
- 5V, 9V and 24V from the base power supply p. 3
- Insulation resistance
- >10Mohm at 500VDC p. 1
- Expansion cable
- D3-EXCBL I/O expansion cable p. 1
- DL305 CPUs
- D3-330, D3-340 and D3-350 in the power chart p. 3
What this manual walks you through
- Comparing DL305 base specifications p. 1
- Calculating the power budget for a DL305 base p. 2
- Looking up power supplied by bases and used by DL305 devices p. 3
- Base dimensions, mounting orientation and clearances p. 4
Good to know
- Keep the 24 VDC output at the base terminal to 100 mA or less; what it supplies reduces the internal 24 VDC. p. 3
- DL305 bases must be mounted horizontally for cooling airflow. p. 4
- Exceeding the power budget may make the system operate unpredictably. p. 2
- The catalog is no replacement for the user manuals, D3-USER-M and D3-350-M. p. 4
Questions this manual answers
What input voltage does the D3-05B-1 base accept?
85-264VAC at 47-63Hz, with 85 VA max. power consumption. p. 1
How much 24 VDC can the D3-05B-1 supply to outside devices?
Its auxiliary 24 VDC output is rated 100mA max, and that draw reduces the internal 24 VDC available to modules. p. 1, 3
Is the fuse in the D3-05B-1 replaceable?
No. The table lists a 2A (250V) non-replaceable fuse. p. 1
Can the D3-05B-1 be used as an expansion base?
Yes. It is a 5-slot I/O base for use as a local or expansion base. p. 1
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
DL305 Base Specifications 1.6’ 0.5 M
5-slot I/O base (local or expansion)
1.115” 29.9mm I/O Expansion Cable (D3-EXCBL) 8-slot I/O base (local or expansion) 94--240V
RUN
10-slot I/O base (local or expansion)
94-240 VAC Terminal Strip
24V OUT LG G
(Bases provide built-in power supplies)
D3-05B-1 <--->D3-05BDC <--->D3-08B-1 <--->D3-10B-1 <--->D3-10BDC <--->Number of Slots5581010Local CPU BaseYesYesYesYesYesExpansion Base
Yes Yes Yes (D3-350 only) Yes Yes CPU base and two expansion CPU base and two expansion CPU base and two expansion CPU base and one expansion CPU base and one expansion bases. If CPU base is 5-slot, bases. If CPU base is 5-slot, bases. If CPU base is 8-slot, bases. If CPU base is 10-slot, bases. If CPU base is 10-slot, then the expansion bases must then the expansion bases must then the expansion bases must then the expansion bases must then the expansion bases must be 5-slot also. be 5-slot also. be 8-slot or 5-slot be 10-slot or 5-slot be 10-slot or 5-slot.
Input Voltage Range85-264VAC 47-63Hz20.5-30VDC <10% ripple85-264VAC 47-63Hz85-264VAC 47-63Hz20.5-30VDC <10% ripple
Base Power Consumption 85 VA Max
48 Watts85VA Max85VA Max65 WattsInrush Current Max.30A 1ms30A30A 1ms30A 1ms30ADielectric Strength
1500VAC for one minute 1500VAC for one minute between terminals of AC P/S, between 24VDC input termirun output, common, 24VDC nals and run output
1500VAC for one minute 2000VAC for one minute 1500VAC for one minute between terminals of AC P/S, between terminals of AC P/S, between 24VDC input termirun output, common, 24VDC run output, common, 24VDC nals and run output
Insulation Resistance>10Mohm at 500VDC>10Mohm at 500VDC>10Mohm at 500VDC>10Mohm at 500VDC>10Mohm at 500VDC
Power Supply Output (Voltage Ranges and Ripple)
(5VDC) 4.75-5.25V 5% ripple (9VDC) 8.5-10V 5% ripple (24VDC) 20-28V 5% ripple
(5VDC) 4.75-5.25V 5% ripple (9VDC) 8.5-10V 5% ripple (24VDC) 20-28V 5% ripple
(5VDC) 4.75-5.25V 5% ripple (9VDC) 8.5-10V 5% ripple (24VDC) 20-28V 5% ripple
(5VDC) 4.75-5.25V 5% ripple (9VDC) 8.5-10V 5% ripple (24VDC) 20-28V 5% ripple
(5VDC) 4.75-5.25V 5% ripple (9VDC) 8.5-10V 5% ripple (24VDC) 20-28V 5% ripple
5 VDC Current Supplied.7A1.4A1.0A1.0A1.4A9 VDC Current Supplied2.0A0.8A2.0A2.0A1.7A
24 VDC Current Supplied 0.5A
0.5A0.5A0.5A0.5A
Auxiliary 24 VDC Output
100mA maxNone100mA max100mA maxNoneRun Relay
250VAC 4A (resistive load)
250VAC 4A (resistive load)
250VAC 4A (resistive load)
250VAC 4A (resistive load)
250VAC, 4A (resistive load)
Fuses
2A (250V) Non-replaceable
4A (250V) User-replaceable D3-FUSE-3 <--->
2A (250V) Non-replaceable
2A (250V) Non-replaceable
4A (250V) User-replaceable D3-FUSE-3 <--->
Dimensions W/H/D
11.42x4.85x4.41 in. (290x123x112 mm)
11.42x4.85x4.41 in. (290x123x112 mm
15.55x4.85x4.41 in. (395x123x112 mm)
18.3x4.85x4.41 in. (465x123x112 mm)
18.34x4.85x4.41 in. (465x123x112 mm)
Weight37oz. (1050g)34oz. (964g)44oz. (1250g)51.1oz. (1450g)50.5oz. (1432g)Volume 13e5-22
Programmable Controllers
1 - 80 0 - 633 - 0405
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
Power Budget Managing your power resource The I/O configuration depends on your choice of I/O modules, bases and I/O location. When determining the types and quantity of I/O modules you will be using, it’s important to remember there is a limited amount of power available from the power supply. The chart on the next page indicates the power supplied and used by each DL305 device. The adjacent chart shows an example of how to calculate the power used by your particular system. These two charts should make it easy for you to determine if the devices you have chosen fit within the power budget of your system configuration. If the I/O you have chosen exceeds the maximum power available from the power supply, you can resolve the problem by shifting some of the modules to an expansion base.
Company Information
WARNING: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner, which may result in a risk of personal injury or equipment damage.
3. Add the current used by the system devices (columns 3, 4, and 5), starting with Slot 1, then put the total in the row labeled “Maximum Current Required” (Row E). 4. Subtract the row labeled “Maximum Current Required” (Row E), from the row labeled “Current Supplied” (Row B). Place the difference in the row labeled “Remaining Current” (Row F). 5. If “Maximum Current Required” is greater than “Current Supplied” in columns 3, 4 or 5, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your I/O configuration.
Example: how to calculate your power usage The following example shows how to calculate the power budget for the DL305 system. The examples are constructed around a single 5-slot base using the devices shown. It is recommended you construct a similar table for each base in your DL305 system. 1. Using a chart similar to the one below, fill in column 2. 2. Using the tables on the opposite page, enter the current supplied and used by each device (columns 3, 4, and 5). Devices which fall into the “Other” category (Row D) are devices such as the Handheld Programmer or a Data Communication Unit, which also have power requirements, but do not directly plug into the base.
Systems Overview Programmable Controllers
Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches
Use ZIPLinks to reduce power requirements If your application requires a lot of relay outputs, consider using the ZipLink AC or DC relay output modules. These modules can switch high current (10A) loads without putting a load on your base power budget. Refer to the Wiring Solutions section in this catalog for more information. This logo is placed next to I/O modules that are supported by the ZIPLink connection systems. See the I/O module specifications at the end of this section.
AColumn 1 Base # 0Column 2 Device TypeColumn 3Column 4Column 55 VDC (mA)9VDC (mA)24V(mA)Current Sensors1400800500Pressure Sensors
B Current Supplied 5-slot Base
D3-05BDC
C Current Required CPU Slot Slot 0 Slot 1 Slot 2 Slot 3
EncodersTemperature SensorsD3-330300500D3-16NE301300D3-16NE301300D3-08TA-101600D3-08TA-1016005050036068001040120500
Pushbuttons/ Lights Process Relays/ Timers
D Other Handheld prog D3-HPP
E Maximum Current Required F Remaining Current
Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index
Volume 13
w w w. a u to m at i o n d i re c t . c o m / d l 305
Programmable Controllers
e5-23
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
DL305 Power Requirements This section shows the amount of power supplied by the base power supplies and the amount of power used by each DL305 device. Note the base power supplies provide three internal voltages (5V, 9V, 24V). The chart shows how much power from each of these power sources is required for each DL305 device. Use this information when calculating the power budget for your system. In addition to the three internal power sources, the DL305 bases provide an external power connection. There is 24 VDC available from the 24 VDC output terminals on the bases (except D3-05BDC and D3-10BDC). The 24 VDC can be used to power external devices or DL305 modules that require external 24 VDC. The power used from this external 24 VDC output reduces the internal system 24 VDC that is available to the modules by an equal amount. When using the 24 VDC output at the base terminal, it is recommended that 100 mA not be exceeded.
Power Consumed Device
Power Supplied
5V(mA) 9V(mA) 24V(mA) Ext req.
CPUs D3-330 D3-340 D3-350
300 300 50050 20 00 0 00 0 010 25 25 148112 224 224 680 0 0 010 10 1000 0 00 0 00 00 0
DC Input Modules D3-08ND2 D3-16ND2-1 D3-16ND2F F3-16ND3F
0 0 0 0
Device
D3-05B-1 900 D3-08B-1 900 D3-10B-1 900 D3-05BDC 900 D3-10BDC 900 D3-05B-NR 900 D3-08B-NR 900 D3-10B-NR 900 D3-05BDC-NR 900 D3-10BDC-NR 900
0 0 0
AC/DC Input Modules D3-08NE3 D3-16NE3
0 0
10 130
DC Output Modules D3-04TD1 D3-08TD1 D3-08TD2 D3-16TD1-1 D3-16TD2
0 0 0 0 012 20 30 40 1805 24 0 96 00 0 0 0 012 200 160 160 250 4000 0 0 0 0 00 0 0 0 0 0
AC Output Modules D3-04TAS F3-08TAS-1 D3-08TA-1 D3-08TA-2 F3-16TA-2 D3-16TA-2
0 0 0 0 0 0
2000 2000 2000 2000 2000 2000 2000 2000 2000 2000
500 500 500 500 500 500 500 500 500 500
100 100 100 None None 100 100 100 None None
Power Consumed Device
AC Input Modules D3-08NA-1 D3-08NA-2 D3-16NA
5V(mA) 9V(mA) 24V(mA) 24 V (mA)
5V(mA) 9V(mA) 24V(mA) External required
Relay Output Modules D3-08TR F3-08TRS-1 F3-08TRS-2 D3-16TR
0 0 0 0360 296 296 4800 0 0 00 0 0 0
Analog Temperature and Thermocouple Modules F3-04ADS F3-08AD-1 F3-08THM-n F3-16AD F3-04DA-1 F3-04DAS
0 0 0 0 0 0183 45 50 55 144 15450 55 34 65 108 1450 0 0 0 0 0
Communications and Networking D3-232 DCU D3-422 DCU FA-UNICON D3- DCM
500 500 0 00 0 0 3000 0 0 0
Optional 5V@500mA Optional 5V@500mA 24V or 5V@ 100mA 0
10 70 5112 0 00 0 050 50 00 0 00 0 00 0 0 00 150 0 00 0 0 00 00 00 0
Specialty Modules D3-08SIM D3-HSC D3-TCSU
0 0 40
Programming D3-HP D3-HPP D2-HP
50 50 200
Specialty CPUs F3-OMUX-1 F3-OMUX-2 F3-PMUX F3-RTU
409 262 455 416
Operator Interface DV-1000 150 210 C-more Micro-Graphic
Volume 13
e5-24
Programmable Controllers
1 - 80 0 - 633 - 0405
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
Dimensions and Installation It is important to understand the installation requirements for your DL305 system. This will help ensure that the DL305 products operate within their environmental and electrical limits.
Plan for safety This catalog should never be used as a replacement for the user manual. The user manuals, D3-USER-M and D3-350-M (available for download from our web site), contain important safety information that must be followed. The system installation should comply with all appropriate electrical codes and standards.
Company InformationSpecificationSystems OverviewRating
Storage Temperature Ambient Operating Temperature Ambient Humidity Vibration Resistance Shock Resistance Noise Immunity
-4°F - 158°F (-20°C to 70°C) Programmable Controllers
32°F - 131°F (0° to 55°C) 30% - 95% relative humidity (non-condensing) MIL STD 810C, Method 514.2
Field I/O
MIL STD810, Method 516.2
SoftwareNEMA (ICS3-304)C-more & other HMIDL305 mounting depthsDrivesOK
Soft Starters Motors & Gearbox
4.41” 112mm
Base dimensions and mounting orientation
5” 127mm
Use the diagrams to the right to make sure the DL305 system can be installed in your application. DL305 bases must be mounted horizontally to ensure proper airflow for cooling purposes. It is important to check these dimensions against the conditions required for your application. For example, it is recommended that you leave 1.5" depth for ease of access and cable clearance. However, your distance may be greater or less. Also, check the installation guidelines for the recommended cabinet clearances.
Base and CPUSteppers/ ServosAirflowMotor Controls
With 8-pt., 16-pt. I/O, or handheld
Proximity Sensors Photo Sensors Limit Switches 5.94” 151mm 6.75” 171mm
Encoders
Base and CPU with DCU, or Thumbwheel interface
Current Sensors
With PROM Writer Unit (-lines) Pressure Sensors
9.0” 229mm
With DCU and D3-DSCBL-2 connected
See the Enclosures section in this catalog for an enclosure that may be suitable for your application
Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm.
2" 50mm minA BCBase
D3-05B-1 <---> D3-08B-1 <---> D3-10B-1 <--->
ABPower2" 50mm minDPrice
Terminal Blocks & Wiring
C
11.41" 290mm 10.63" 270mm 4.84” 123mm 3.54”
Circuit Protection2" 50mm minDEnclosures Tools90mm P anel
15.55" 395mm 14.76" 375mm 4.84” 123mm 3.54”
90mm
18.30" 465mm 17.51" 445mm 4.84” 123mm 3.54”