Key facts from this manual
Each line names its page in the PDF.
Love Controls installation instructions (Bulletin 949-0527) for the Iso Verter II models SC4380 and SCL4380, DIN rail signal modules whose input and output are each set by switches for current or voltage. It explains setting the four switch banks, mounting, wiring and calibration, and lists the specifications.
- Device
- Iso Verter II with switch-selected current or voltage input and output, uni-polar or bi-polar p. 1, 2
- Power
- SC4380: 85 to 265 VDC/VAC, 50 to 400 Hz (SCL4380: 12 to 24 VDC/AC, 40 to 400 Hz) p. 4
- Isolation
- 1500 VAC p. 4
- Mounting
- 35 mm DIN rail p. 3
- Accuracy
- Linearity 0.1%; drift ±0.02% per °C typical, ±0.05% maximum p. 4
- Output load
- Current output up to 600 ohms; voltage output 20 mA (500 ohms) p. 4
- Input impedance
- Current 10 ohms; voltage 1 Megohm p. 4
- Switch banks
- SW-1 input range, SW-2 input mode, SW-3 output mode, SW-4 output range p. 2, 3
- Zero suppression
- Zero based (0 to 20 mA) or zero suppressed (4 to 20 mA) input and output p. 2
- Calibration
- ZERO and SPAN adjustment screws p. 4
- Terminals
- Compression type wiring terminals p. 4
What this manual walks you through
- Setting the input range and mode switches (SW-1, SW-2) p. 2
- Setting the output mode and range switches (SW-3, SW-4) p. 2, 3
- Mounting on and removing from a DIN rail p. 3, 4
- Wiring input, output and power p. 4
- Calibrating with the ZERO and SPAN screws p. 4
Good to know
- Do not run the unit with the cover off or open it; there are no user serviceable parts inside. p. 3
- Keep Class 2 signal wires out of power wire runs and conduit. p. 4
- With a bipolar output, do not use the zero suppression switch; use the ZERO adjustment instead. p. 2
- Switch eight of SW-3 is not connected and stays OFF. p. 2
- Do not overtighten the terminal screws. p. 4
Questions this manual answers
What power does the SC4380 need?
85 to 265 VDC/VAC at 50 to 400 Hz. The SCL4380 runs on 12 to 24 VDC/AC. p. 4
How do I set the SC4380 for a 4 to 20 mA input?
On SW-2 turn switch one ON for current input and switch four ON for zero suppression, then pick the scale on SW-1. p. 2
How do I calibrate the SC4380?
Apply the low-end input and set the ZERO screw, apply the high-end input and set the SPAN screw, and repeat as needed. p. 4
What load can the SC4380 current output drive?
Up to 600 ohms. p. 4
How does the SC4380 mount?
It clips onto a standard 35 mm DIN rail. p. 3
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
949-0527:Layout 33/25/108:44 AMPage 1Bulletin 949-0527
Iso Verter® II Model SC4380/SCL4380 Installation Instructions Getting Started 1. Using a small screwdriver, ball point pen, etc. set the four switches on the side of the unit (see Input Programming and Output Programming on page 2). 2. Mount unit into panel (see Mounting on page 3). 3. Connect unit to input signal, output signal, and power wiring (see Wiring on page 4). 4. Check calibration (see Calibration on page 4). Specifications are on page 4.
Dimensions 22.5 (0.886)
75 (2.950)35.5 (1.40)98.5 (3.880)
Dimensions shown in mm (inches)
LOVE CONTROLS DIVISION DWYER INSTRUMENTS, INC. P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.
Phone: 219/879-8000 www.love-controls.com Fax: 219/872-9057 e-mail: lit@dwyer-inst.com
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
949-0527:Layout 33/25/108:44 AMPage 2
Input Programming RANGE SELECTION SWITCH BANK (SW-1) Turn ON the switch for the scale desired. All other switches should be OFF. If BI-POLAR INPUT is selected, the scale will be MINUS-SELECTION to PULSE-SELECTION (eg. -10 TO +10 VDC). MODE SELECTION SWITCH BANK (SW-2) 1. For CURRENT INPUT turn switch one ON. For VOLTAGE INPUT turn switch one OFF. 2. For UNI-POLAR INPUT (low end of scale ≥ zero) turn switch two ON and turn switch three OFF. 3. For Bi-POLAR INPUT (low end of scale < zero) turn switch two OFF and turn switch three ON. 4. For ZERO BASED INPUT (eg. 0 TO 20 mA) turn switch four OFF. 5. For ZERO SUPPRESSION (eg. 4 TO 20 mA) turn switch four ON. 6. For DIRECT ACTING INPUT turn switch five OFF and switch six ON. For REVERSE ACTING INPUT turn switch five ON and switch six OFF.
INPUT Output Programming MODE SELECTION SWITCH BANK (SW-3) 1. For VOLTAGE OUTPUT turn switches one and two ON and switch three OFF. 2. For CURRENT OUTPUT turn switches one and two OFF and switch three ON. 3. For UNIPOLAR OUTPUT turn switch four ON and switch five OFF. 4. For BIPOLAR OUTPUT turn switch four OFF and switch five ON. 5. For ZERO BASED OUTPUT (eg. 0 TO 20 mA) turn switch six ON and switch seven OFF. 6. For ZERO SUPPRESSION (eg. 4 TO 20 mA) turn switch six OFF and switch seven ON. If BIPOLAR is selected, do not use the ZERO SUPPRESSION switch. Use the ZERO adjustment to suppress the output. 7. Switch eight is always OFF. (It is not connected to any circuitry. If switch eight is turned ON there is no effect on the operation of the device.)
2
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
949-0527:Layout 33/25/108:44 AMPage 3
RANGE SELECTION SWITCH BANK (SW-4) Turn ON the switch for the scale desired. All other switches should be OFF. If BIPOLAR OUTPUT is selected, the scale will be from MINUS-SELECTION to PLUS-SELECTION (eg. -10 TO +10 VDC).
OUTPUT
WARNING: Do not attempt to operate this device with the cover removed. Potentially lethal voltage is present on some of the internal components. Do not open the unit. There are no internal adjustments or user serviceable parts in the unit.
Mounting Mount the unit in a panel that will not be subject to excessive temperature, shock, or vibration. All models are designed for mounting on an industry standard 35 mm DIN rail. To install hold the SC4380 so that the front is higher than the rear. Place the upper slot on the rear of the SC4380 on the top edge of the DIN rail. Slowly rotate the front down until the bottom spring clip snaps over the bottom edge of the DIN rail.
3
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
949-0527:Layout 33/25/108:44 AMPage 4
To remove from the DIN rail, place a small slotted screwdriver in the slot in the spring clip under the housing. Pry the slot downward to release the SCU from the bottom of the rail.
Wiring The wiring terminals for the SC4380 are compression type. To open the wiring terminal, turn the screw for that terminal counterclockwise. Slide the wire into the terminal space. While holding the wire in place, turn the screw clockwise to tighten. Do not overtighten. The wire should be held snugly in place. Wire the input, output, and power as shown on the wiring label. Do not run Class 2 signal wires adjacent to or in the same conduit as power wires. Calibration 1. Apply the appropriate input for the low end of the scale. 2. Adjust the ZERO screw for the appropriate low end output. 3. Apply the appropriate input for the high end of the scale. 4. Adjust the SPAN screw for the appropriate high end output. 5. Repeat as necessary. SPECIFICATIONS Power Supply: SCL4380: 12 to 24 VDC/AC 40 to 400 Hz ±20%. SC4380: 85 to 265 VDC/VAC 50 to 400 Hz. Isolation: 1500 VAC. Ambient Temperature Range (operating): 0 to 50°C (32 to 131°F). Linearity: 0.1%. Drift: ±0.02% per °C typical, ±0.05% maximum. Maximum Current Output Load: 600 ohms. Maximum Voltage Output Load: 20 mA (500 ohms). Input Impedence - Current: 10 ohms. Input Impedence - Voltage: 1 Megohm.
©Copyright 2010 Dwyer Instruments, Inc.
LOVE CONTROLS DIVISION DWYER INSTRUMENTS, INC. P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.
Printed in U.S.A. 3/10
FR# 949-0527 Rev. 1
Phone: 219/879-8000 www.love-controls.com Fax: 219/872-9057 e-mail: lit@dwyer-inst.com