Spec sheet · Mean Well
Mean Well DRT-480-24 Spec Sheet
Spec sheet2 pagesPDF 128 KB
Both pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
A two-page Mean Well specification sheet (DRT-480-SPEC 2011-06-17) for the DRT-480 series of 480W three phase industrial DIN rail power supplies, covering the DRT-480-24 and DRT-480-48. It gives the output, input, protection, environment and mechanical data, the terminal pin assignment and the derating curve. It helps a technician wire and size the 24V model.
- What it is
- 480W three phase industrial DIN rail power supply p. 1
- Output
- DRT-480-24: 24V DC, 20A rated, 480W p. 1
- Input
- Three-phase 340 ~ 550VAC, 47 ~ 63Hz; dual phase operation possible p. 1
- Efficiency
- 89% typical p. 1
- Working temperature
- -20 ~ +70, per the derating curve p. 1
- Dimensions and weight
- 227*125.2*100mm (W*H*D); 2.5Kg p. 1
- DIN rail
- TS35/7.5 or TS35/15 p. 2
- Overload protection
- 105 ~ 150% rated output power; constant current limiting, recovers automatically p. 1
- Ripple and noise
- 80mVp-p max p. 1
- Input current
- 1.7A/400VAC, 1.3A/500VAC typical; cold start inrush 50A p. 1
- Cooling
- Free air convection p. 1
- MTBF
- 91.1Khrs min. (MIL-HDBK-217F) p. 1
- Case
- Case No.930A p. 2
What this sheet walks you through
- Wiring the AC input and DC output terminals p. 2
- Derating load by ambient temperature and input voltage p. 2
- Protection behavior for overload, over voltage and over temperature p. 1
Good to know
- Dual phase operation needs a 20% derating. p. 1
- The supply is a component; the final equipment must be rechecked for EMC directives. p. 1
- After an over voltage shutdown, the input must be cycled to recover. p. 1
Questions this sheet answers
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
480W Three Phase Industrial DIN RAIL Power Supply
D R T- 4 8 0 s e r i e s
Features : Three-Phase AC 340 ~ 550V wide range input High efficiency 89% and low dissipation Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Built-in constant current limiting circuit Can be installed on DIN rail TS-35/7.5 or 15 UL 508(industrial control equipment)approved EN61000-6-2(EN50082-2) industrial immunity level 100% full load burn-in test 3 years warranty
SPECIFICATION MODELOUTPUTDRT-480-24DRT-480-48DC VOLTAGE24V48VRATED CURRENT20A10ACURRENT RANGE0 ~ 20A0 ~ 10ARATED POWER480W480W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-pVOLTAGE ADJ. RANGE48 ~ 55V 1.0%
24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% LINE REGULATION
0.5%LOAD REGULATION0.5%SETUP, RISE TIME1200ms, 40ms/400VACINPUT
35ms/500VAC at full load
FREQUENCY RANGE47 ~ 63HzEFFICIENCY (Typ.)89%
AC CURRENT (Typ.) INRUSH CURRENT (Typ.)
1.7A/400VAC 1.3A/500VAC COLD START 50A
OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 4) EMC EMISSION
480 ~ 780VDC 90%
<3.5mA / 530VAC 105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 30 ~ 36V 59 ~ 66V Protection type : Shut down o/p voltage, re-power on to recover 110 5 (TSW) detect on heatsink of power switch Protection type : Shut down o/p voltage, recovers automatically after temperature goes down -20 ~ +70
(Refer to "Derating Curve")
20 ~ 90% RH non-condensing -40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50 Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, UL60950-1, TUV EN60950-1 approved I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
91.1Khrs min. MIL-HDBK-217F (25 227*125.2*100mm (W*H*D) 2.5Kg; 6pcs/16Kg/1.75CUFT
DIMENSION PACKING
NOTE
800ms, 40ms/500VAC at full load
Note.5 Three-Phase 340 ~ 550VAC (Dual phase operation possible)
LEAKAGE CURRENTOTHERS0.5%16ms/400VAC
HOLD UP TIME (Typ.) VOLTAGE RANGE
0.5%
)
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Dual phase operation: derating of 20% is required.
File Name:DRT-480-SPEC 2011-06-17
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
D R T- 4 8 0 s e r i e s
480W Three Phase Industrial DIN RAIL Power Supply Mechanical Specification
Case No.930A100Unit:mm125.2227TB1 4 3 2 1LEDTB2 4 3 2 1
Terminal Pin No. Assignment (TB1)
+V ADJ.Pin No. 1 2 3 435
ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15
Assignment AC/L1 AC/L2 AC/L3 FG
Terminal Pin No. Assignment (TB2) Pin No. 1,2 3,4
Assignment DC OUTPUT +V DC OUTPUT -V
Block Diagram
fosc : 70KHz RECTIFIERS & FILTER
EMI FILTERI/PRECTIFIERS & FILTERPOWER SWITCHINGDETECTION CIRCUITFGCURRENT LIMITO.L.P.PWM CONTROLO.T.P.O.V.P.Static CharacteristicsDerating Curve1008090 85 806070LOAD (%)LOAD (%)1004020-20+V -VThree phase operationDual phase operation60 50 4001020304050
AMBIENT TEMPERATURE ( )
6070 (VERTICAL)340355370385400415 430460 475490505 520 550
INPUT VOLTAGE (VAC) 60Hz
File Name:DRT-480-SPEC 2011-06-17