A two-page Mean Well specification sheet (DRT-480-SPEC 2011-06-17) for the DRT-480 series of 480W three phase industrial DIN rail power supplies, covering the DRT-480-24 and DRT-480-48. It gives the output, input, protection, environment and mechanical data, the terminal pin assignment and the derating curve. It helps a technician wire and size the 24V model.

What it is
480W three phase industrial DIN rail power supply p. 1
Output
DRT-480-24: 24V DC, 20A rated, 480W p. 1
Input
Three-phase 340 ~ 550VAC, 47 ~ 63Hz; dual phase operation possible p. 1
Efficiency
89% typical p. 1
Working temperature
-20 ~ +70, per the derating curve p. 1
Dimensions and weight
227*125.2*100mm (W*H*D); 2.5Kg p. 1
DIN rail
TS35/7.5 or TS35/15 p. 2
Overload protection
105 ~ 150% rated output power; constant current limiting, recovers automatically p. 1
Ripple and noise
80mVp-p max p. 1
Input current
1.7A/400VAC, 1.3A/500VAC typical; cold start inrush 50A p. 1
Cooling
Free air convection p. 1
MTBF
91.1Khrs min. (MIL-HDBK-217F) p. 1
Case
Case No.930A p. 2

What this sheet walks you through

  • Wiring the AC input and DC output terminals p. 2
  • Derating load by ambient temperature and input voltage p. 2
  • Protection behavior for overload, over voltage and over temperature p. 1

Good to know

  • Dual phase operation needs a 20% derating. p. 1
  • The supply is a component; the final equipment must be rechecked for EMC directives. p. 1
  • After an over voltage shutdown, the input must be cycled to recover. p. 1

Questions this sheet answers

What input voltage does the Mean Well DRT-480-24 need?

Three-phase 340 ~ 550VAC at 47 ~ 63Hz. Dual phase operation is possible with a 20% derating. p. 1

How much current can the DRT-480-24 supply?

20A at 24V, for 480W. p. 1

What DIN rail fits the DRT-480 series?

TS35/7.5 or TS35/15. p. 2

The file

Size and text

Pages2
PDF128 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Mean Well DRT-480-24 Spec Sheet

The text of page 1, from the PDF itself

480W Three Phase Industrial DIN RAIL Power Supply

D R T- 4 8 0 s e r i e s

Features : Three-Phase AC 340 ~ 550V wide range input High efficiency 89% and low dissipation Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Built-in constant current limiting circuit Can be installed on DIN rail TS-35/7.5 or 15 UL 508(industrial control equipment)approved EN61000-6-2(EN50082-2) industrial immunity level 100% full load burn-in test 3 years warranty

SPECIFICATION MODELOUTPUTDRT-480-24DRT-480-48DC VOLTAGE24V48VRATED CURRENT20A10ACURRENT RANGE0 ~ 20A0 ~ 10ARATED POWER480W480W

RIPPLE & NOISE (max.) Note.2 80mVp-p

80mVp-pVOLTAGE ADJ. RANGE48 ~ 55V 1.0%

24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% LINE REGULATION

0.5%LOAD REGULATION0.5%SETUP, RISE TIME1200ms, 40ms/400VACINPUT

35ms/500VAC at full load

FREQUENCY RANGE47 ~ 63HzEFFICIENCY (Typ.)89%

AC CURRENT (Typ.) INRUSH CURRENT (Typ.)

1.7A/400VAC 1.3A/500VAC COLD START 50A

OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 4) EMC EMISSION

480 ~ 780VDC 90%

<3.5mA / 530VAC 105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 30 ~ 36V 59 ~ 66V Protection type : Shut down o/p voltage, re-power on to recover 110 5 (TSW) detect on heatsink of power switch Protection type : Shut down o/p voltage, recovers automatically after temperature goes down -20 ~ +70

(Refer to "Derating Curve")

20 ~ 90% RH non-condensing -40 ~ +85

, 10 ~ 95% RH

0.03%/ (0 ~ 50 Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, UL60950-1, TUV EN60950-1 approved I/P-O/P:3KVAC

I/P-FG:1.5KVAC

O/P-FG:0.5KVAC

I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3

EMC IMMUNITY

Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A

MTBF

91.1Khrs min. MIL-HDBK-217F (25 227*125.2*100mm (W*H*D) 2.5Kg; 6pcs/16Kg/1.75CUFT

DIMENSION PACKING

NOTE

800ms, 40ms/500VAC at full load

Note.5 Three-Phase 340 ~ 550VAC (Dual phase operation possible)

LEAKAGE CURRENTOTHERS0.5%16ms/400VAC

HOLD UP TIME (Typ.) VOLTAGE RANGE

0.5%

)

1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Dual phase operation: derating of 20% is required.

File Name:DRT-480-SPEC 2011-06-17

Page 2 of Mean Well DRT-480-24 Spec Sheet

The text of page 2, from the PDF itself

D R T- 4 8 0 s e r i e s

480W Three Phase Industrial DIN RAIL Power Supply Mechanical Specification

Case No.930A100Unit:mm125.2227TB1 4 3 2 1LEDTB2 4 3 2 1

Terminal Pin No. Assignment (TB1)

+V ADJ.Pin No. 1 2 3 435

ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15

Assignment AC/L1 AC/L2 AC/L3 FG

Terminal Pin No. Assignment (TB2) Pin No. 1,2 3,4

Assignment DC OUTPUT +V DC OUTPUT -V

Block Diagram

fosc : 70KHz RECTIFIERS & FILTER

EMI FILTERI/PRECTIFIERS & FILTERPOWER SWITCHINGDETECTION CIRCUITFGCURRENT LIMITO.L.P.PWM CONTROLO.T.P.O.V.P.Static CharacteristicsDerating Curve1008090 85 806070LOAD (%)LOAD (%)1004020-20+V -VThree phase operationDual phase operation60 50 4001020304050

AMBIENT TEMPERATURE ( )

6070 (VERTICAL)340355370385400415 430460 475490505 520 550

INPUT VOLTAGE (VAC) 60Hz

File Name:DRT-480-SPEC 2011-06-17