Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Motorola MOSCAD-L RTU 16DI Digital Input Module Spec Sheet

Spec sheet · Motorola

Motorola MOSCAD-L RTU 16DI Digital Input Module Spec Sheet

Spec sheet2 pagesPDF 75 KB

Both pages are below, each with its text.

What this file really is

The old site listed this file as a spec sheet for the Motorola FRN1494A. The sheet never gives FRN1494A, so it cannot show this is that part.

Download the PDF75 KB

Filed with · 1 model

Also filed with these models on the old site

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

This two-page Motorola spec sheet describes the 16DI module, a 16 digital input accessory for the MOSCAD-L RTU. It gives the input ratings, filtering, isolation and protection, and a terminal chart with sensor wiring examples. The sheet does not print the FRN1494A number the site files it under.

What it is
16 Digital Input (DI) module for the MOSCAD-L RTU, for up to 16 wet or dry closures from switches or relays p. 1
Inputs
Sixteen inputs, 56V dc maximum p. 2
Input signal
On: Vin >9 V or Iin >1.0 ma; Off: Vin <3 V or Iin < 0.3 ma p. 2
Sensors
External 12 or 24 Vac/dc sensors; a floating 24 Vdc output wets dry contacts p. 1
Input frequency
5 Hz maximum without interrupt upon COS, 50 Hz maximum with it p. 2
Filtering
Software control of hardware filtering, 2-38 msec p. 2
Counter inputs
Any of the 16 inputs can be a low-speed counter input, totalized in the CPU module p. 1
Isolation
Optical isolators on all inputs; 2.5 kV between user connection and logic, 100 Mohm @ 500V (IEC 255-5) p. 1, 2
Surge protection
The sheet states ANSI/IEEE C37.90.1-1989: oscillatory wave 2.5 kV, fast transient 4 kV; IEC 801-2 air discharge 8 kV p. 2
Diagnostics
16 input status LEDs on the CPU module p. 2
COS priorities
Interrupt upon COS with 255 priorities p. 2
Terminals
Terms 1-8: In-1 to In-8; 9: com 1-8; 10-17: In-9 to In-16; 18: com 9-16; 19: +24V dc; 20: -24V dc p. 2

What this sheet walks you through

  • Wiring dry contact and open collector sensors, negative ground or switched +24V p. 2
  • Terminal connections of the module p. 2
  • Using inputs for counting and time-tagging events p. 1

Good to know

  • Filtering longer than the 2-38 msec hardware range is done within the application. p. 2

Questions this sheet answers

What does the MOSCAD-L 16DI module do?

It connects up to 16 wet or dry contact closures from switches or relays in other on-site equipment to the MOSCAD-L RTU. p. 1

What voltage turns a 16DI input on?

More than 9 V (or more than 1.0 ma) is on; less than 3 V (or less than 0.3 ma) is off. p. 2

Can the 16DI module power dry contacts?

Yes. It provides a floating 24 Vdc output to wet the contacts on dry-contact sensors. p. 1

What is the maximum input frequency of the 16DI module?

5 Hz without interrupt upon COS, 50 Hz with it. p. 2

The file

Size and text

Pages2
PDF75 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Motorola MOSCAD-L RTU 16DI Digital Input Module Spec Sheet

The text of page 1, from the PDF itself

16DI MODULE for the MOSCAD-L RTU

The 16 Digital Input (DI) module is an accessory to the MOSCAD-L RTU that allows up to 16 wet or dry closures, from switches or relays in other on-site equipment, to be connected to the RTU. Examples include site or equipment door switches, centrifugal switches on motors, equipment malfunction switches, and tank float switches.

FEATURES/BENEFITS Data Input Under the control of the defined application program, the CPU module will read the current instantaneous status of one or more of the 16 inputs. It will move that data from the 16DI module into the CPU module via the motherboard. 8 This data may then be used by the application program to perform the desired functions.

Low-Speed Counter Inputs Each of the 16 digital inputs may be used as lowspeed counter inputs if desired. The totalizing will be done within the CPU module under application control. 8 Any number of counter inputs are easily obtained.

Wet or Dry Inputs Each digital input accepts input currents from external 12 or 24 Vac/dc sensors. The module provides a floating 24 Vdc output to wet the contacts on dry-contact sensors. 8 A single module provides a universal interface to most of the sensors likely to be encountered.

Time-Tagging Any of the 16 digital inputs may be defined to tag the time of the input event with one millisecond accuracy. 8 This time may then be read and used in sequence-of-event actions, etc. or used later for historical reports.

Optical Isolation All inputs are protected by optical isolators on the module. 8 Surge Withstand Capability (SWC) conformance is assured for the safety of the equipment and technicians.

Page 2 of Motorola MOSCAD-L RTU 16DI Digital Input Module Spec Sheet

The text of page 2, from the PDF itself

16DI Module for the MOSCAD-L RTU SPECIFICATIONS SPECIFICATIONS Inputs: Input Frequency: Input Signal: Filtering: Interrupt upon COS: Isolation:

Connections Chart

Sixteen (16) inputs, 56V dc maximum Without interrupt upon COS: 5 Hz maximum With interrupt upon COS: 50 Hz maximum On: Vin >9 V or Iin >1.0 ma Off: Vin <3 V or Iin < 0.3 ma Software control of hardware filtering: 2-38 msec. Longer filtering within the application. Number of priorities = 255. Event time-tag resolution = 5 msec. Per IEC 255-5: between user connection and logic = 2.5 kV; insulation resistance = 100 Mohm @ 500V; insulation impulse = 5 kV

Protection
Per ANSI/IEEE C37.90.1-1989: oscillatory wave = 2.5 kV; fast transient = 4 kV Per IEC 801-2: air discharge = 8 kV Per IEC 801-3: radiation immunity = 10 V/m Per IEC 801-4: fast transient = 500V
Diagnostics
LEDs on CPU module: 16 input status

TermFunctionTermFunctionTermFunctionTermFunction1In-16In-611In-1016In-152In-27In-712In-1117In-163In-38In-813In-1218com 9-164In-49com 1-814In-1319+24V dc5In-510In-915In-1420–24V dc

Specifications subject to change without notice.

Negative Ground Sensor Wiring

Equivalent Input Circuit 3.6k 3.6k

DIDry ContactDIDry ContactSwitched MinusDISwitched Plus +24VOpen Collectorcom

CUSTOMER Communications

SERVICE

Switched +24V Sensor Wiring

1.3k

SUPPORT SERVICES Wherever Motorola sells, our product is backed by service. Our products are serviced throughout the world by a wide network of company or authorized independent distributor service organizations.

DIcom+24V Open CollectorDIDIDIcom+24V+24V-24V-24V

Motorola U.S.A. Motorola Canada Limited 1301 E. Algonquin Road 3900 Victoria Park Avenue Schaumburg, Illinois 60196 North York, Ontario M2H 3H7 In the U.S. call: 1-800-247-2346 In Canada call: 1-800-268-5758 Outside the U.S. and Canada call: (847) 538-6602 , Motorola and MOSCAD are trademarks of Motorola, Inc. ■ ©1997 by Motorola, Inc. ■ Printed in U.S.A. ■ (9708) Merit ■ Produced by Customer Communications. Motorola is an Equal Employment Opportunity/Affirmative Action Employer

R3-11-1013