Spec sheet · National Instruments
National Instruments FP-1601 Spec Sheet
Spec sheet3 pagesPDF 188 KB
All 3 pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
A three-page National Instruments catalog data sheet for the NI FP-1601, an Ethernet network interface for FieldPoint distributed I/O. It describes the networking, power, security, watchdog and power-up output features, the configuration software, ordering numbers and specifications.
- Device type
- Ethernet network interface for up to nine FieldPoint I/O modules p. 1
- Network
- 1 Ethernet port, RJ-45, 10BaseT and 100BaseTX, autonegotiates 10 Mb/s or 100 Mb/s; TCP/IP based p. 1
- Power
- 11 to 30 VDC, with extra screw terminals for a backup UPS or battery p. 2
- Order number
- NI FP-1601: 777792-01 p. 3
- Related parts
- NI FP-TB-1: 777519-01; NI PS-4 Power Supply: 778586-90 p. 3
- Software
- Measurement & Automation Explorer and OPC server (2.0 compliant) included; Windows 2000/NT/XP p. 1
- Compatible software
- LabVIEW, LabWindows/CVI, Measurement Studio, Lookout, VI Logger p. 1
- Host systems
- A [c]FP-20xx embedded controller or a Windows computer p. 1
- Operating temperature
- -25 to 55 °C; storage -55 to 85 °C p. 3
- Humidity, altitude
- 10 to 90%, noncondensing; up to 2,000 m p. 3
- Weight
- 235 g (8.3 oz) p. 3
- Terminal torque
- 0.5-0.6 N m (4.4-5.3 lb in.) p. 3
- Security
- IP address pattern filtering, access rights of none, read only or read/write, and a password p. 2
- Mounting
- Snaps together with the terminal bases and mounts on a DIN rail p. 2
What this sheet walks you through
- Configuring the network, modules and I/O with Measurement & Automation Explorer p. 3
- Restricting access by IP pattern, access rights and password p. 2
- Setting power-up output states with Snapshot p. 2
- Using the network watchdog to set outputs when the Ethernet link is lost p. 2
- Cutting network traffic with event-driven communication and dead bands p. 1, 2
Good to know
- FieldPoint modules are for indoor use only; outdoors they must be in a suitable sealed enclosure. p. 3
- For EMC compliance the device should be run with shielded cabling. p. 3
- Out of the box the module grants all clients full access until an IP pattern is set. p. 2
Questions this sheet answers
What power supply does the NI FP-1601 need?
An 11 to 30 VDC supply, with extra screw terminals for a backup UPS or battery. p. 2
How many FieldPoint modules can one FP-1601 run?
One FP-1601 manages a bank of up to nine FieldPoint bases and their I/O modules. p. 2
What is the NI part number for the FP-1601?
777792-01. p. 3
What happens to FP-1601 outputs if the Ethernet link is lost?
With the watchdog timer enabled, it can set the output channels to configured output states. p. 2
What software configures the FP-1601?
Measurement & Automation Explorer (MAX), included with FieldPoint hardware. p. 3
The file
Size and text
Every page · 3
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 3
Open in the PDF
The text of page 1, from the PDF itself
FieldPoint Ethernet Network Interface
Ethernet Network Interface for FieldPoint NI FP-1601
- PC-based distributed I/O Ethernet network interface
- High-performance networking
- 10BaseT/100BaseTX
- Event-driven communications and configurable deadbanding
- Secure Ethernet access with IP filtering and password protection
- Industrial-grade reliability
- Automatic self-diagnostics
- Redundant power supply inputs
- Isolated communication bus to I/O modules
- Network watchdog timer
- Configurable I/O powerup states
Module FP-1601
Ethernet Ports 1
Operating Systems
- Windows 2000/NT/XP
Recommended Software
- LabVIEW
- LabVIEW Datalogging and Supervisory Control Module
Other Compatible Software
- LabWindows/CVI
- Measurement Studio
- Lookout
- VI Logger
Driver Software (included)
- Measurement & Automation Explorer
- OPC server (2.0 compliant)
Event Driven Protocol
10/100 BaseTX
Industrial Control and Distributed I/O
Overview and Applications
538
The National Instruments FP-1601 network interface connects up to nine FieldPoint I/O modules to a high-speed Ethernet network. With up to 100 Mb/s data communication rates and event-driven communications, the NI FP-1601 delivers a high-performance network connection for FieldPoint that is easy to interface with a PC and easy to use. The FP-1601 manages communications between the host PC and the I/O modules over a local high-speed bus formed by FieldPoint terminal bases. The network interface module also provides diagnostic and autoconfiguration features to simplify installation, use, and maintenance. Applications can easily communicate with the FP-1601 interface to exchange data. The FP-1601 interface can communicate with a [c]FP-20xx embedded controller or with a Windows computer running LabVIEW, LabWindows/CVI, Measurement Studio, Lookout, or your choice of OPC client application software. Using the FP-1601, you can rapidly build flexible, modular distributed measurement and automation systems.
Network Communications Interface The NI FP-1601 connects directly to Ethernet networks, autonegotiating on the network for 10 Mb/s or 100 Mb/s communication rates. It includes an RJ-45 connector for connection to 10BaseT and 100BaseTX networks and uses a protocol based on standard TCP/IP to maintain full compatibility with existing networks. FieldPoint builds on standard TCP/IP network protocols and adds a number of key enhancements, including event-driven communications and publisher-subscriber networking. In a publishersubscriber architecture one or more client PCs subscribe to I/O data from FieldPoint banks. The network interface monitors connected I/O modules and publishes I/O data only when the value changes. Analog signals can change value within selectable ranges, called dead bands, without causing the system to report data. This event-driven method, along with data compression, helps you avoid unnecessary Ethernet traffic and maximizes communications efficiency.
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • info@ni.com • ni.com
Page2of 3
Open in the PDF
The text of page 2, from the PDF itself
Ethernet Network Interface for FieldPoint PC or PXI Running LabVIEW
A single FP-1601 interface manages a bank of up to nine FieldPoint bases and attached I/O modules. The network interface module and terminal bases snap together and mount as a unit on a DIN rail. The network interface module and terminal bases form a high-speed data bus for communication between the network module and the I/O modules. With modular terminal bases, it is easy to expand your FieldPoint system to meet changing application needs.
Ethernet Industrial Switch
For more details on configuring a FieldPoint system, see page 532.
Decrease Network Traffic with Event-Driven Communication Using an event-driven communication protocol, the FieldPoint Ethernet network interface transmits data via Ethernet only when data values change. This eliminates unnecessary network traffic, resulting in more efficient communication. The data values can consist of individual I/O module channels or user-defined variables in the embedded LabVIEW program.
FP-1601 Ethernet Remote I/O Nodes
FP-1601 Ethernet Remote I/O Nodes
FP-1601 Ethernet Remote I/O Nodes
Figure 1. Ethernet provides an open, high-performance network for FieldPoint Distributed I/O
Configurable Output States with Snapshot
Power Supply Backup and Regulation
Security
An 11 to 30 VDC supply powers the FP-1601. An extra set of screw terminals is available for a backup UPS or battery. The network interface filters and regulates the power input, redistributing power to all I/O modules in the node through the backplane bus in the terminal bases.
The FP-1601 offers advanced security features so that only authorized clients can access the FieldPoint system. Authorized clients are Ethernet nodes with IP addresses that match user-defined patterns. You can also further qualify the list of clients by their access rights – none, read only, and read/write (with access to configuration). Initially, the network module grants all clients full access. The user then can select an IP pattern that corresponds to the required list of clients. In addition, you can set a password that any user can enter for full access rights to the FieldPoint System.
For external power supply options, see FieldPoint Accessories on page 550.
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • info@ni.com • ni.com
Industrial Control and Distributed I/O
The FP-1601 can detect and respond to network failures. If you enable the watchdog timer and the Ethernet link becomes inactive or is lost, the FP-1601 can automatically set the output channels to configured output states.
With the Snapshot feature, you can easily define the default output states and I/O configurations for the entire FieldPoint node after system power-up. The SnapShot command instructs the Ethernet network interface to memorize the current settings of the I/O modules in the node, storing the information in nonvolatile storage on the FP-1601. After power-up, the FP-1601 will initialize the I/O modules to the configurable output states you defined with Snapshot.
Network Watchdog Timers
FieldPoint Ethernet Network Interface
System Configurations
539
Page3of 3
Open in the PDF
The text of page 3, from the PDF itself
FieldPoint Ethernet Network Interfaces
Ethernet Network Interface for FieldPoint Easy Configuration Software National Instruments Measurement & Automation Explorer (MAX) configuration software, included with your FieldPoint hardware, simplifies the use and integration of FieldPoint systems. With MAX, you configure the entire system, including network parameters, module and I/O settings, and named-channel items. MAX will search your Ethernet network and return configuration settings on all your FieldPoint nodes. MAX will also automatically detect the I/O modules on each bank so you can easily configure I/O parameters, such as input ranges, power-up output states, and watchdog states, using intuitive dialog windows. To get your system up and running quickly, from MAX you can also interactively test I/O modules and channels, viewing input data values and setting output values,without writing any software code. In addition to configuring hardware parameters, MAX also configures and manages named-channel items used in your higherlevel programming software. From your application software package, such as LabVIEW, LabWindows/CVI, Measurement Studio, or Lookout, you simply address a named-channel item to access the I/O values.
Ordering Information NI FP-1601 ....................................................................777792-01 Recommended Compact FieldPoint System Products
NI FP-TB-1 ....................................................................777519-01 NI PS-4 Power Supply ..................................................778586-90 NI Developer Suite Standard Control Edition ............777905-03
BUY ONLINE! Visit ni.com/info and enter fp1601.
For more details on configuring a FieldPoint system, see page 532.
Specifications Network Network interface ............................................ Compatibility .................................................... Communications rate ....................................... Maximum cabling distance.............................. Maximum number of I/O modules per bank ...................................... Maximum power supplied to terminal bases....................................... Maximum number of banks .............................
Environmental 10BaseT and 100BaseTX Ethernet IEEE 802.3 10 Mb/s, 100 Mb/s, autonegotiated 100 m/segment 9 terminal bases 9W Determined by network topology
Safety The FP-1601 is designed to meet the requirements of the following standards for safety and electrical equipment for measurement, control, and laboratory use:
- EN 61010-1, IEC 61010-1
- UL 3121-1, UL 61010C-1
- CAN/CSA C22.2 No. 1010.1 For UL and other safety certifications, refer to the product label or to ni.com
Industrial Control and Distributed I/O
Power Requirements
FieldPoint modules are intended for indoor use only. For outdoor use, they must be installed in a suitable sealed enclosure. Operating temperature..................................... -25 to 55 °C Storage temperature ........................................ -55 to 85 °C Relative Humidity ............................................. 10 to 90%, noncondensing Maximum altitude ............................................ 2,000 m Pollution Degree............................................... 2
Power supply range.......................................... Recommended power supply FP-1601 with up to 5 modules .................. FP-1601 with 6 to 9 modules .................... Power consumption..........................................
540
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • info@ni.com • ni.com
11-30 VDC 15 W (FP-PS-4 or equivalent) 20 W 4.5 W + 1.1 (I/O module power requirements)
Physical Characteristics LED indicators POWER (green) .......................................... STATUS (red).............................................. LINK (green) ............................................... SPEED (yellow) .......................................... ACTIVE (green)........................................... Tx (green) ................................................... Rx (green)................................................... User-defined .............................................. Screw-terminal wiring .....................................
Valid power to module Failure condition Valid network connection 100 Mb/s (10 Mb/s when unlit) Ethernet activity Transmit activity Receive activity 3 bi-color, 1 green 16–26 AWG copper conductor wire with 7 mm (0.28 in.) of insulation stripped from the end Torque for screw terminals .............................. 0.5-0.6 N m (4.4-5.3 lb in.) Weight ............................................................ 235 g (8.3 oz)
Electromagnetic Compatibility CE, C-Tick and FCC Part 15 (Class A) Compliant Emissions.......................................................... EN 55011 Class A at 10 m FCC Part 15A above 1 GHz Immunity........................................................... EN 61326: 1997+A2:2001, Table 1 For EMC compliance, operate this device with shielded cabling.
CE Compliance This product meets the essential requirements of applicable European Directives, as amended for CE Marking, as follows: Low-Voltage Directive (safety)......................... 73/23/EEC Electromagnetic Compatibility Directive (EMC).......................................... 89/336/EEC Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance information. To obtain the DoC for this product, visit ni.com/hardref.nsf/ and search by model number or product line.