Page 1 of B7A Technical Reference Data

Manual · Omron

B7A Technical Reference Data

Manual10 pagesPDF 244 KB

Technical reference for Omron B7A Series link terminals, including the B7AS-T6B1: PLC connections, I/O conditions, wiring and mounting.

Download the PDF244 KB

Covers · 1 model

The models it covers

Summary

What is in it

Omron technical reference data that applies to all B7A Series Link Modules, input and output link terminals that carry I/O signals to and from a programmable controller. It lists recommended combinations of B7A links (including the B7A-T6B1 and B7AS-T6B1) with C500 and C200H PLC I/O modules, connection examples, peripheral circuits for PCB models, noise protection, transmission errors and output signals, I/O status and ON/OFF conditions, precautions, recommended cables and DIN track mounting.

Its parts

  1. Operation
  2. Precautions

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

This is OMRON's B7A Technical Reference Data, which applies to all B7A Series Link Modules, including the B7AS-T6B1 input module. It shows which OMRON C500 and C200H PLC I/O modules work with each B7A model, sample connections, sensor input and noise protection circuits, error behavior, I/O ON/OFF conditions, and precautions for wiring, cables and mounting.

What it is
B7AS-T6B1: B7A Series input Link Module with screw terminals, used with PLC output modules p. 2, 6, 9
Sensor inputs
B7AS-T6B1: NPN photoelectric and proximity sensors (ON at residual voltage 4 V max.) and two-wire DC proximity sensors (OFF at leakage current 1.5 mA max.) p. 6
PLC outputs accepted
B7AS-T6B1: PLC NPN transistor outputs or relay outputs p. 2
Supply voltage
12 to 24 V ±10% p. 6
Transmission distance
100 m max. with twisted-pair wire of 0.75 mm2 or more (normal speed models) p. 9, 10
Cables
Normal speed, B7A/S: VCTF 0.75 x 3 C with one power supply for two terminals, VCTF 0.75 x 2 C with independent supplies; high speed: shielded wire 0.75 mm2 min. p. 9, 10
Mounting
DIN track; leave 3 mm min. between terminals side by side, PFP-S Spacers recommended p. 10
Screw torque
Wiring terminals 8 to 12 kgf·cm (0.78 to 1.18 N·m); panel mounting screws 6 to 10 kgf·cm (0.59 to 0.98 N·m) p. 9
Color coding
Screw terminal models: input marked IN in white on red; output marked OUT in black on yellow p. 10
Error output modes
Output terminals: HOLD keeps the outputs from just before the error, LOAD OFF turns all outputs off; automatic reset when the error is corrected p. 6
Power noise filter
R 10 to 20 Ω (1/8 W min.) and C 33 µF min. with 50 V min. dielectric strength p. 5
PCB model input levels
Printed circuit board models: ON at 2.2 V min., OFF at 0.8 V max., suitable for TTL circuits p. 5

What this manual walks you through

  • Choosing OMRON PLC I/O modules to pair with B7A link modules p. 1, 2
  • Example connections with C500 and C200H PLC I/O modules p. 3, 4
  • Sensor input circuits for printed circuit board models p. 5
  • Adding noise protection circuits p. 5
  • Input and output ON/OFF conditions by model p. 6, 7, 8
  • Wiring the transmission lines p. 9
  • Choosing cables p. 9, 10
  • Mounting on and removing from a DIN track p. 10

Good to know

  • The B7A cannot be connected to OMRON's SYSMAC BUS Remote I/O System. p. 1, 9
  • 10-point and 16-point models cannot be connected to each other. p. 9
  • Turn off the Link Terminals while wiring to avoid a short circuit that can damage them. p. 9
  • The input and output circuits are not isolated; use photocouplers if external noise affects the Link Terminals. p. 9
  • A wrong combination of B7A and PLC modules can damage the B7A. p. 9

Questions this manual answers

What sensors can be connected to the B7AS-T6B1?

NPN photoelectric and proximity sensors (residual voltage 4 V max.) and two-wire DC proximity sensors (leakage current 1.5 mA max.). p. 6

Can a B7A link module connect to SYSMAC BUS Remote I/O?

No. To pass B7A signals to a PLC, wire the B7A terminals to an I/O module mounted on the PLC. p. 1

How far apart can B7A link terminals be?

For normal speed models with twisted-pair wire, up to 100 m; the wire must be 0.75 mm2 or thicker when a single power supply is used. p. 9, 10

What causes a B7A transmission error?

A disconnected signal or 0 V wire, heavy external noise or a path longer than allowed, supply voltage outside 12 to 24 V ±10%, or the moment right after power-on. p. 6

What do B7A outputs do when a transmission error occurs?

In HOLD mode the outputs stay as they were just before the error; in LOAD OFF mode all outputs turn off. The terminals reset automatically once the error is corrected. p. 6

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Front Page1
  2. Operation1
  3. Precautions9
  4. Contacting Omron10

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10

The file

Revision and size

RevisionCat. No. GC RIO-1, 04/00
PublisherOmron Electronics, Inc.
Pages10
PDF244 KB