Page 164
Section
Coding Right-hand Instructions
5-6
The following diagram and corresponding mnemonic code illustrates the points described above. 00000
Address Instruction
00001 DIFU(013) 22500 00002
00100
00200
22500 BCNT(067)
01001 01002
LR 6300
Data
00000
LD
00000
00001
AND
00001
00002
OR
00002
00003
DIFU(013)
22500
00004
LD
00100
00005
AND NOT
00200
00006
LD
01001
00007
AND NOT
01002
00008
AND NOT
LR 6300
00009
OR LD
00010
AND
00011
BCNT(067)
#0001 004 HR 00
00005 TIM 000
–– 22500
#0150 TIM 000
–– #0001
MOV(021)
004
HR 00
HR 00
LR 00
HR 0015
00012
LD
00013
TIM
00005 000 #0150
00500
00014
LD
00015
MOV(021)
TIM 000 –– HR 00 LR 00
152
00016
LD
00017
OUT NOT
HR 0015 00500
Page 165
Section
Coding Right-hand Instructions Multiple Instruction Lines
00000
If a right-hand instruction requires multiple instruction lines (such as KEEP(011)), all of the lines for the instruction are entered before the right-hand instruction. Each of the lines for the instruction is coded, starting with LD or LD NOT, to form ‘logic blocks’ that are combined by the right-hand instruction. An example of this for SFT(010) is shown below. Address Instruction
00001
I SFT(010)
00002
P HR 00
00100
00200
01001 01002
5-6
22500
R
HR 00
Data
00000
LD
00000
00001
AND
00001
00002
LD
00002
00003
LD
00100
00004
AND NOT
00200
00005
LD
01001
LR 6300
HR 0015 00500
00006
AND NOT
01002
00007
AND NOT
LR 6300
00008
OR LD
00009
AND
00010
SFT(010)
–– 22500 –– HR 00 HR 00
END(001)
00011
LD
00012
OUT NOT
HR 0015 00500
When you have finished coding the program, make sure you have placed END(001) at the last address.
153
Page 166
Section
Instruction Set Lists
5-7
5-7
Instruction Set Lists This section provides tables of the instructions in the C200HX/HG/HE. The first table can be used to find instructions by function code. The second table can be used to find instruction by mnemonic. In both tables, the @ symbol indicates instructions with differentiated variations.
5-7-1 Function Codes The following table lists the instructions that have fixed function codes and the expansion instructions that have default function codes. Each instruction is listed by mnemonic and by instruction name. Use the numbers in the leftmost column as the left digits and the number in the column heading as the right digit of the function code. Right digit
Left digits
2
3
5
6
7
8
00
NOP NO OPERATION
END END
IL INTERLOCK
ILC INTERLOCK CLEAR
JMP JUMP
JME JUMP END
(@) FAL FAILURE ALARM AND RESET
FALS SEVERE FAILURE ALARM
STEP STEP DEFINE
SNXT STEP START
01
SFT SHIFT REGISTER
KEEP KEEP
CNTR REVERSIBLE COUNTER
DIFU DIFFERENTIATE UP
DIFD DIFFERENTIATE DOWN
TIMH HIGHSPEED TIMER
(@) WSFT WORD SHIFT
(@) ASFT ASYNCHRONOUS SHIFT REGISTER
(@) SCAN CYCLE TIME
(@) MCMP MULTIWORD COMPARE
02
CMP COMPARE
(@) MOV MOVE
(@) MVN MOVE NOT
(@) BIN BCD TO BINARY
(@) BCD BINARY TO BCD
(@) ASL SHIFT LEFT
(@) ASR SHIFT RIGHT
(@) ROL ROTATE LEFT
(@) ROR ROTATE RIGHT
(@) COM COMPLEMENT
03
(@) ADD BCD ADD
(@) SUB BCD SUBTRACT
(@) MUL BCD MULTIPLY
(@) DIV BCD DIVIDE
(@) ANDW LOGICAL AND
(@) ORW LOGICAL OR
(@) XORW EXCLUSIVE OR
(@) XNRW EXCLUSIVE NOR
(@) INC INCREMENT
(@) DEC DECREMENT
04
(@) STC SET CARRY
(@) CLC CLEAR CARRY
---
---
---
TRSM TRACE MEMORY SAMPLE
(@) MSG MESSAGE DISPLAY
(@) LMSG LONG MESSAGE
(@) TERM TERMINAL MODE
---
05
(@) ADB BINARY ADD
(@) SBB BINARY SUBTRACT
(@) MLB BINARY MULTIPLY
(@) DVB BINARY DIVIDE
(@) ADDL DOUBLE BCD ADD
(@) SUBL DOUBLE BCD SUBTRACT
(@) MULL DOUBLE BCD MULTIPLY
(@) DIVL DOUBLE BCD DIVIDE
(@) BINL DOUBLE BCD-TODOUBLE BINARY
(@) BCDL DOUBLE BINARY-TODOUBLE BCD
06
CMPL DOUBLE COMPARE
(@) MPRF GROUP-2 HIGH-DENSITY I/O REFRESH
(@) XFRB TRANSFER BITS
(@) LINE COLUMN TO LINE
(@) COLM LINE TO COLUMN
(@) SEC HOURS-TOSECONDS
(@) HMS SECONDSTO-HOURS
(@) BCNT BIT COUNTER
(@) BCMP BLOCK COMPARE
(@) APR ARITHMETIC PROCESS
07
(@) XFER BLOCK TRANSFER
(@) BSET BLOCK SET
(@) ROOT SQUARE ROOT
(@) XCHG DATA EXCHANGE
(@) SLD ONE DIGIT SHIFT LEFT
(@) SRD ONE DIGIT SHIFT RIGHT
(@) MLPX 4-TO-16/ 8-TO-256 DECODER
(@) DMPX 16-TO-4/ 256-TO-8 ENCODER
(@) SDEC 7-SEGMENT DECODER
(@) FDIV FLOATING POINT DIVIDE
08
(@) DIST SINGLE WORD DISTRIBUTE
(@) COLL DATA COLLECT
(@) MOVB MOVE BIT
(@) MOVD MOVE DIGIT
(@) SFTR REVERSIBLE SHIFT REGISTER
(@) TCMP TABLE COMPARE
(@) ASC ASCII CONVERT
TTIM TOTALIZING COUNTER
ZCP AREA RANGE COMPARE
(@) INT INTERRUPT CONTROL
09
(@) SEND NETWORK SEND
(@) SBS SUBROUTINE ENTRY
SBN SUBROUTINE DEFINE
RET SUBROUTINE RETURN
(@) WDT WATCHDOG TIMER REFRESH
---
---
(@) IORF I/O REFRESH
(@) RECV NETWORK RECEIVE
(@) MCRO MACRO
11
---
---
---
---
(@) CPS SIGNED BINARY COMPARE
(@) CPSL DOUBLE SIGNED BINARY COMPARE
(@) ZCPL DOUBLE AREA RANGE COMPARE
---
---
---
12
---
---
---
---
---
(@) BXFR EM BANK TRANSFER
---
---
---
---
16
(@) NEG 2’S COMPLEMENT
(@) NEGL DOUBLE 2’S COMPLEMENT
(@) HEX ASCII-TOHEXADECIMAL
---
---
---
---
---
---
---
18
(@) FCS FRAME CHECKSUM
(@) SRCH DATA SEARCH
(@) MAX FIND MAXIMUM
(@) MIN FIND MINIMUM
(@) SUM SUM
---
---
---
---
---
19
(@) PID PID CONTROL
---
---
---
(@) SCL SCALING
(@) AVG AVERAGE VALUE
---
---
---
---
21
DSW DIGITAL SWITCH INPUT
TKY TEN KEY INPUT
HKY HEXADEC. KEY INPUT
MTR MATRIX INPUT
7SEG 7-SEGMENT DISPLAY OUTPUT
---
---
---
---
---
22
---
---
(@) IORD SPECIAL I/O UNIT READ
(@) IOWR SPECIAL I/O UNIT WRITE
---
---
---
---
---
---
154
0
1
4
9
Page 167
Section
Instruction Set Lists Left digits
5-7
Right digit 0
1
2
3
4
5
6
7
8
9
23
---
---
---
---
---
(@) RXD RECEIVE
(@) TXD TRANSMIT
(@) STUP CHANGE RS-232C SETUP
---
---
26
(@) PMCR PROTOCOL MACRO
(@) CMCR PCMCIA CARD MACRO
---
---
---
---
---
---
---
FPD FAILURE POINT DETECTION
28
(@) XDMR EXPANSION DM READ
(@) EMBC SELECT EM BANK
---
---
---
---
---
---
---
---
30
= EQUAL
=L DOUBLE EQUAL
=S SIGNED EQUAL
=SL DOUBLE SIGNED EQUAL
---
<> NOT EQUAL
< >L DOUBLE NOT EQUAL
< >S SIGNED NOT EQUAL
<>SL DOUBLE SIGNED NOT EQUAL
---
31
< LESS THAN
<L DOUBLE LESS THAN
<S SIGNED LESS THAN
<SL DOUBLE SIGNED LESS THAN
---
<= LESS THAN OR EQUAL
<=L DOUBLE LESS THAN OR EQUAL
<=S SIGNED LESS THAN OR EQUAL
<=SL DOUBLE SIGNED LESS THAN OR EQUAL
---
32
> GREATER THAN
>L DOUBLE GREATER THAN
>S SIGNED GREATER THAN
>SL DOUBLE SIGNED GREATER THAN
---
>= GREATER THAN OR EQUAL
>=L DOUBLE GREATER THAN OR EQUAL
>=S SIGNED GREATER THAN OR EQUAL
>=SL DOUBLE SIGNED GREATER THAN OR EQUAL
---
35
TST BIT TEST
TSTN BIT TEST
---
---
---
---
---
---
---
---
40
(@) + SIGNED BINARY ADD
(@) +L DOUBLE SIGNED BINARY ADD
(@) +C SIGNED BINARY ADD W/CARRY
(@) +CL DOUBLE SIGNED BINARY ADD W/CARRY
(@) +B SIGNED BCD ADD
(@) +BL DOUBLE BCD ADD
(@) +BC BCD ADD W/CARRY
(@) +BCL DOUBLE BCD ADD W/CARRY
---
---
41
(@) – SIGNED BINARY SUBTRACT
(@) –L DOUBLE SIGNED BINARY SUBTRACT
(@) –C SIGNED BINARY SUBTRACT W/CARRY
(@) –CL DOUBLE SIGNED BINARY SUBTRACT W/CARRY
(@) –B BCD SUBTRACT
(@) –BL DOUBLE BCD SUBTRACT
(@) –BC BCD SUBTRACT W/CARRY
(@) –BCL DOUBLE BCD SUBTRACT W/CARRY
---
---
42
(@) * SIGNED BINARY MULTIPLY
(@) *L DOUBLE SIGNED BINARY MULTIPLY
(@) *U UNSIGNED BINARY MULTIPLY
(@) *UL DOUBLE UNSIGNED BINARY MULTIPLY
(@) *B BCD MULTIPLY
(@) *BL DOUBLE BCD MULTIPLY
---
---
---
---
43
(@) / SIGNED BINARY DIVIDE
(@) /L DOUBLE SIGNED BINARY DIVIDE
(@) /U UNSIGNED BINARY DIVIDE
(@) /UL DOUBLE UNSIGNED BINARY DIVIDE
(@) /B BCD DIVIDE
(@) /BL DOUBLE BCD DIVIDE
---
---
---
---
48
(@) ADBL DOUBLE BINARY ADD
(@) SBBL DOUBLE BINARY SUBTRACT
(@) MBSL DOUBLE SIGNED BINARY MULTIPLY
(@) DBSL DOUBLE SIGNED BINARY DIVIDE
(@) MBS SIGNED BINARY MULTIPLY
(@) DBS SIGNED BINARY DIVIDE
---
---
---
---
155
Page 168
Section
Instruction Set Lists
5-7
5-7-2 Alphabetic List by Mnemonic The following table lists the C200HX/HG/HE instructions in alphabetical order. Default function codes for expansion instructions are in parentheses. (A code of (–––) is shown for expansion instructions without default function codes.) Mnemonic
Code
Words
7SEG
(214)
5
7-SEGMENT DISPLAY OUTPUT
387
ADB (@)
050
4
BINARY ADD
280
ADBL (@)
(–––)
4
DOUBLE BINARY ADD
286
ADD (@)
030
4
BCD ADD
266
ADDL (@)
054
4
DOUBLE BCD ADD
267
AND
–––
1
AND
160
AND LD
–––
1
AND LOAD
161
AND NOT
–––
1
AND NOT
160
ANDW (@)
034
4
LOGICAL AND
314
APR (@)
(069)
4
ARITHMETIC PROCESS
300
ASC (@)
086
4
ASCII CONVERT
234
ASFT(@)
(017)
4
ASYNCHRONOUS SHIFT REGISTER
191
ASL (@)
025
2
ARITHMETIC SHIFT LEFT
187
ASR (@)
026
2
ARITHMETIC SHIFT RIGHT
187
AVG (@)
(195)
5
AVERAGE VALUE
297
BCD (@)
024
3
BINARY TO BCD
221
BCDL (@)
059
3
DOUBLE BINARY-TO-DOUBLE BCD
222
BCMP (@)
(068)
4
BLOCK COMPARE
210
BCNT (@)
(067)
4
BIT COUNTER
346
BIN (@)
023
3
BCD-TO-BINARY
220
BINL (@)
058
3
DOUBLE BCD-TO-DOUBLE BINARY
221
BSET (@)
071
4
BLOCK SET
193
BXF2 (@)
(–––)
4
BLOCK TRANSFER TO OTHER EM BANK
202
BXFR (@)
(125)
4
EM BANK TRANSFER
204
CLC (@)
041
1
CLEAR CARRY
265
CMCR (@)
261
5
PCMCIA CARD MACRO
393
CMP
020
3
COMPARE
206
CMPL
(060)
4
DOUBLE COMPARE
209
CNT
–––
2
COUNTER
178
CNTR
012
3
REVERSIBLE COUNTER
181
COLL (@)
081
4
DATA COLLECT
197
COLM(@)
(064)
4
LINE TO COLUMN
241
COM (@)
029
2
COMPLEMENT
313
CPS
(114)
4
SIGNED BINARY COMPARE
215
CPSL
(115)
4
DOUBLE SIGNED BINARY COMPARE
216
DBS (@)
(–––)
4
SIGNED BINARY DIVIDE
292
DBSL (@)
(–––)
4
DOUBLE SIGNED BINARY DIVIDE
293
DEC (@)
039
2
BCD DECREMENT
265
DIFD
014
2
DIFFERENTIATE DOWN
162
DIFU
013
2
DIFFERENTIATE UP
162
DIST (@)
080
4
SINGLE WORD DISTRIBUTE
196
DIV (@)
033
4
BCD DIVIDE
273
DIVL (@)
057
4
DOUBLE BCD DIVIDE
274
DMPX (@)
077
4
16-TO-4/256-TO-8 ENCODER
228
156
Name
Page
Page 169
Section
Instruction Set Lists Mnemonic
Code
Words
Name
DSW
(210)
5
DIGITAL SWITCH
376
DVB (@)
053
4
BINARY DIVIDE
285
EMBC (@)
281
2
SELECT EM BANK
355
END
001
1
END
170
FAL (@)
006
2
FAILURE ALARM AND RESET
338
FALS
007
2
SEVERE FAILURE ALARM
338
FCS (@)
(180)
5
FCS CALCULATE
346
FDIV (@)
079
4
FLOATING POINT DIVIDE
275
FPD
(269)
5
FAILURE POINT DETECT
348
HEX (@)
162
5
ASCII-TO-HEXADECIMAL
235
HKY
(212)
5
HEXADECIMAL KEY INPUT
382
HMS (@)
066
4
SECONDS TO HOURS
224
IEMS (@)
(–––)
4
INDIRECT EM ADDRESSING
354
IL
002
1
INTERLOCK
167
ILC
003
1
INTERLOCK CLEAR
167
INC (@)
038
2
INCREMENT
265
INT (@)
(089)
4
INTERRUPT CONTROL
325
IORD (@)
222
5
SPECIAL I/O UNIT READ
391
IORF (@)
097
3
I/O REFRESH
344
IOWR (@)
223
5
SPECIAL I/O UNIT WRITE
392
JME
005
2
JUMP END
169
JMP
004
2
JUMP
169
KEEP
011
2
KEEP
165
LD
–––
1
LOAD
160
LD NOT
–––
1
LOAD NOT
160
LINE (@)
(063)
4
COLUMN TO LINE
240
LMSG (@)
(047)
4
32-CHARACTER MESSAGE
342
MAX (@)
(182)
5
FIND MAXIMUM
294
MBS (@)
(–––)
4
SIGNED BINARY MULTIPLY
290
MBSL (@)
(–––)
4
DOUBLE SIGNED BINARY MULTIPLY
291
MCMP (@)
(019)
4
MULTI-WORD COMPARE
205
MCRO (@)
099
4
MACRO
323
MIN (@)
(183)
5
FIND MINIMUM
295
MLB (@)
052
4
BINARY MULTIPLY
285
MLPX (@)
076
4
4-TO-16/8-TO-256 DECODER
225
MOV (@)
021
3
MOVE
192
MOVB (@)
082
4
MOVE BIT
200
MOVD (@)
083
4
MOVE DIGIT
200
MPRF (@)
(061)
4
GROUP-2 HIGH-DENSITY I/O REFRESH
345
MSG (@)
046
2
MESSAGE
341
MTR
(213)
5
MATRIX INPUT
385
MUL (@)
032
4
BCD MULTIPLY
271
MULL (@)
056
4
DOUBLE BCD MULTIPLY
272
MVN (@)
022
3
MOVE NOT
193
NEG (@)
(160)
4
2’S COMPLEMENT
242
NEGL (@)
(161)
4
DOUBLE 2’S COMPLEMENT
243
NOP
000
1
NO OPERATION
170
OR
–––
1
OR
160
OR LD
–––
1
OR LOAD
161
5-7
Page
157
Page 170
Section
Instruction Set Lists Mnemonic
Code
Words
OR NOT
–––
1
OR NOT
160
ORW (@)
035
4
LOGICAL OR
315
OUT
–––
2
OUTPUT
161
OUT NOT
–––
2
OUTPUT NOT
161
PID (@)
(190)
5
PID CONTROL
303
PMCR (@)
260
5
PROTOCOL MACRO
374
RECV (@)
098
4
NETWORK RECEIVE
362
RET
093
1
SUBROUTINE RETURN
322
ROL (@)
027
2
ROTATE LEFT
188
ROOT (@)
072
3
SQUARE ROOT
278
ROR (@)
028
2
ROTATE RIGHT
188
RSET
–––
2
RESET
164
RXD(@)
(235)
5
RECEIVE
368
SBB (@)
051
4
BINARY SUBTRACT
282
SBBL (@)
(–––)
4
DOUBLE BINARY SUBTRACT
288
SBN
092
2
SUBROUTINE DEFINE
322
SBS (@)
091
2
SUBROUTINE ENTRY
321
SCAN (@)
(018)
4
CYCLE TIME
339
SCL (@)
(194)
5
SCALING
238
SDEC (@)
078
4
7-SEGMENT DECODER
231
SEC (@)
(065)
4
HOURS TO SECONDS
223
SEND (@)
090
4
NETWORK SEND
356
SET
–––
2
SET
164
SFT
010
3
SHIFT REGISTER
183
SFTR (@)
084
4
REVERSIBLE SHIFT REGISTER
185
SLD (@)
074
3
ONE DIGIT SHIFT LEFT
189
SNXT
009
2
STEP START
329
SRCH (@)
(181)
5
DATA SEARCH
352
SRD (@)
075
3
ONE DIGIT SHIFT RIGHT
189
STC (@)
040
1
SET CARRY
265
STEP
008
2
STEP DEFINE
329
STUP (@)
237
4
CHANGE RS-232C SETUP
373
SUB (@)
031
4
BCD SUBTRACT
268
SUBL (@)
055
4
DOUBLE BCD SUBTRACT
270
SUM (@)
(184)
5
SUM CALCULATION
299
TCMP (@)
085
4
TABLE COMPARE
212
TERM (@)
(048)
4
TERMINAL MODE
343
TIM
–––
2
TIMER
171
TIMH
015
3
HIGH-SPEED TIMER
176
TKY
(211)
5
TEN KEY INPUT
380
TRSM
045
1
TRACE MEMORY SAMPLE
340
TST
350
5
BIT TEST
166
TSTN
351
5
BIT TEST NOT
166
TTIM
087
4
TOTALIZING TIMER
177
TXD (@)
(236)
5
TRANSMIT
370
WDT (@)
094
2
WATCHDOG TIMER REFRESH
344
WSFT (@)
016
3
WORD SHIFT
190
XCHG (@)
073
3
DATA EXCHANGE
195
XDMR (@)
(280)
5
EXPANSION DM READ
353
158
Name
Page
5-7
Page 171
Section
Instruction Set Lists Mnemonic
Code
Words
Name
XFER (@)
070
4
BLOCK TRANSFER
195
XFR2 (@)
(–––)
4
EM BLOCK TRANSFER
202
XFRB (@)
(062)
4
TRANSFER BITS
201
XNRW (@)
037
4
EXCLUSIVE NOR
317
XORW (@)
036
4
EXCLUSIVE OR
316
ZCP
(088)
4
AREA RANGE COMPARE
213
ZCPL
(116)
5
DOUBLE AREA RANGE COMPARE
214
=
300
4
EQUAL
217
=L
301
4
DOUBLE EQUAL
217
=S
302
4
SIGNED EQUAL
217
=SL
303
4
DOUBLE SIGNED EQUAL
217
<>
305
4
NOT EQUAL
217
<>L
306
4
DOUBLE NOT EQUAL
217
<>S
307
4
SIGNED NOT EQUAL
217
<>SL
308
4
DOUBLE SIGNED NOT EQUAL
217
<
310
4
LESS THAN
217
<L
311
4
DOUBLE LESS THAN
217
<S
312
4
SIGNED LESS THAN
217
<SL
313
4
DOUBLE SIGNED LESS THAN
217
<=
315
4
LESS THAN OR EQUAL
217
<=L
316
4
DOUBLE LESS THAN OR EQUAL
217
<=S
317
4
SIGNED LESS THAN OR EQUAL
217
<=SL
318
4
DOUBLE SIGNED LESS THAN OR EQUAL
217
>
320
4
GREATER THAN
217
>L
321
4
DOUBLE GREATER THAN
217
>S
322
4
SIGNED GREATER THAN
217
>SL
323
4
DOUBLE SIGNED GREATER THAN
217
>=
325
4
GREATER THAN OR EQUAL
217
>=L
326
4
DOUBLE GREATER THAN OR EQUAL
217
>=S
327
4
SIGNED GREATER THAN OR EQUAL
217
>=SL
328
4
DOUBLE SIGNED GREATER THAN OR EQUAL
217
5-7
Page
159
Page 172
Section
Ladder Diagram Instructions
5-8
5-8
Ladder Diagram Instructions Ladder Diagram instructions include Ladder instructions and Logic Block instructions and correspond to the conditions on the ladder diagram. Logic block instructions are used to relate more complex parts.
5-8-1 LOAD, LOAD NOT, AND, AND NOT, OR, and OR NOT Ladder Symbols
Operand Data Areas
B
B: Bit
LOAD – LD
IR, SR, AR, HR, TC, LR, TR
B: Bit
B
LOAD NOT – LD NOT
IR, SR, AR, HR, TC, LR
B: Bit
B
AND – AND IR, SR, AR, HR, TC, LR
B: Bit
B
AND NOT – AND NOT
IR, SR, AR, HR, TC, LR
B: Bit
OR – OR
B
OR NOT – OR NOT
B
IR, SR, AR, HR, TC, LR
B: Bit IR, SR, AR, HR, TC, LR
Limitations
There is no limit to the number of any of these instructions, or restrictions in the order in which they must be used, as long as the memory capacity of the PC is not exceeded.
Description
These six basic instructions correspond to the conditions on a ladder diagram. As described in Section 4 Writing and Inputting the Program, the status of the bits assigned to each instruction determines the execution conditions for all other instructions. Each of these instructions and each bit address can be used as many times as required. Each can be used in as many of these instructions as required. The status of the bit operand (B) assigned to LD or LD NOT determines the first execution condition. AND takes the logical AND between the execution condition and the status of its bit operand; AND NOT, the logical AND between the execution condition and the inverse of the status of its bit operand. OR takes the logical OR between the execution condition and the status of its bit operand; OR NOT, the logical OR between the execution condition and the inverse of the status of its bit operand. The ladder symbol for loading TR bits is different from that shown above. Refer to 4-4-3 Ladder Instructions for details.
Flags
160
There are no flags affected by these instructions.
Page 173
Section
Bit Control Instructions
5-9
5-8-2 AND LOAD and OR LOAD AND LOAD – AND LD Ladder Symbol
00000
00002
00001
00003
OR LOAD – OR LD 00000
00001
00002
00003
Ladder Symbol
Description
When instructions are combined into blocks that cannot be logically combined using only OR and AND operations, AND LD and OR LD are used. Whereas AND and OR operations logically combine a bit status and an execution condition, AND LD and OR LD logically combine two execution conditions, the current one and the last unused one. In order to draw ladder diagrams, it is not necessary to use AND LD and OR LD instructions, nor are they necessary when inputting ladder diagrams directly, as is possible from SYSMAC-CPT Support Software. They are required, however, to convert the program to and input it in mnemonic form. The procedures for these, limitations for different procedures, and examples are provided in 4-7 Inputting, Modifying, and Checking the Program. In order to reduce the number of programming instructions required, a basic understanding of logic block instructions is required. For an introduction to logic blocks, refer to 4-4-6 Logic Block Instructions.
Flags
There are no flags affected by these instructions.
5-9
Bit Control Instructions There are five instructions that can be used generally to control individual bit status. These are OUT, OUT NOT, DIFU(013), DIFD(014), and KEEP(011). These instructions are used to turn bits ON and OFF in different ways.
5-9-1 OUTPUT and OUTPUT NOT – OUT and OUT NOT OUTPUT – OUT
Ladder Symbol
Operand Data Areas B: Bit B
OUTPUT NOT – OUT NOT
Ladder Symbol
IR, SR, AR, HR, LR, TR
Operand Data Areas B: Bit B
IR, SR, AR, HR, LR
Limitations
Any output bit can generally be used in only one instruction that controls its status. Refer to 3-3 IR Area for details.
Description
OUT and OUT NOT are used to control the status of the designated bit according to the execution condition.
161